10.4.27 BACnetReinitializedStateofDevice

This DataType is an enumeration that represents the BACnet reinitialization state of a device. Its values are defined in Table 156.

Table 156 – BACnetReinitializedStateofDevice Values
Name Value Description
Coldstart0The precise interpretation of COLDSTART shall be defined by the vendor.
Warmstart1WARMSTART shall mean to reboot the device and start over, retaining all data and programs that would normally be retained during a brief power outage.
Startbackup2Starts a backup procedure.
Endbackup3Ends a backup procedure.
Startrestore4Starts a restore procedure.
Endrestore5Ends a restore procedure.
Abortrestore6Aborts a restore procedure.

Its representation in the AddressSpace is defined in Table 157.

Table 157 – BACnetReinitializedStateofDevice Definition
Attribute Value
BrowseNameBACnetReinitializedStateofDevice
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the Enumeration type defined in OPC 10000-5
0:HasPropertyVariable0:EnumStrings0:LocalizedText[]0:PropertyType