7.6 FlameIonisationDetectorType

The FlameIonisationDetectorType is a subtype of the ProcessAnalyserType. It is formally defined in Table 119.

Table 119 - FlameIonisationDetectorType definition
AttributeValue
BrowseNameFlameIonisationDetectorType
IsAbstractFalse
ReferencesNodeClassBrowseName DataTypeTypeDefinitionOther
Subtype of ProcessAnalyserType defined in 7.3, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentObjectDeviceConditionSet0:BaseObjectTypeO
0:HasDictionaryEntryObject3:0112/2///61987#ABP410#002 0:IrdiDictionaryEntryType
Conformance Units
PA-DIM FlameIonisationDetectorType
PA-DIM FlameIonisationDetectorType CatalystTemperature
PA-DIM FlameIonisationDetectorType FuelGasPressure
PA-DIM FlameIonisationDetectorType CombustionAirPressure
PA-DIM FlameIonisationDetectorType BlockTemperature

3:0112/2///61987#ABP410#002 is an FID device specific manifestation of the 3:<DictionaryEntryName> placeholder described in PADIMType.

FlameIonisationDetectorType is defined by IRDI as ABP410#002 which states "process analyser that uses flame ionisation to measure the concentration of one or more components in a gas phase by means of the resulting ionisation current".

DeviceConditionSet is a container object for the condition parameters of the device. It is inherited from PADIMType and has an additional interface reference to IFlameIonisationDeviceConditionSetType to add FID device specific condition variables.

The components of FlameIonisationDetectorType have additional references which are defined in Table 120.

Table 120 - FlameIonisationDetectorType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
DeviceConditionSet0:HasInterfaceTrueIFlameIonisationDeviceConditionSetType
DeviceConditionSet
CatalystTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
DeviceConditionSet
FuelGasPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
DeviceConditionSet
CombustionAirPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
DeviceConditionSet
BlockTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004

The components of FlameIonisationDetectorType have additional subcomponents which are defined in Table 121.

Table 121 - FlameIonisationDetectorType additional subcomponents
BrowsePathReferencesNodeClassBrowseNameDataTypeTypeDefinitionOthers
Applied from IFlameIonisationDeviceConditionSetType
DeviceConditionSet0:HasComponentVariableCatalystTemperature0:Float0:AnalogUnitTypeO
DeviceConditionSet0:HasComponentVariableFuelGasPressure0:Float0:AnalogUnitTypeO
DeviceConditionSet0:HasComponentVariableCombustionAirPressure0:Float0:AnalogUnitTypeO
DeviceConditionSet0:HasComponentVariableBlockTemperature0:Float0:AnalogUnitTypeO

The child Nodes of the FlameIonisationDetectorType have additional Attribute values defined in Table 122.

Table 122 - FlameIonisationDetectorType Attribute values for child Nodes
BrowsePathValue Attribute
DeviceConditionSet
CatalystTemperature

0.0
DeviceConditionSet
CatalystTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
DeviceConditionSet
FuelGasPressure

0.0
DeviceConditionSet
FuelGasPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
DeviceConditionSet
CombustionAirPressure

0.0
DeviceConditionSet
CombustionAirPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
DeviceConditionSet
BlockTemperature

0.0
DeviceConditionSet
BlockTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius