7.1.27 IGasChromatographSignalConditionSetType

The IGasChromatographSignalConditionSetType provides the interface to gaschromatograph measurement signal specific condition variables and is formally defined in Table 91

Table 91 - IGasChromatographSignalConditionSetType definition
AttributeValue
BrowseNameIGasChromatographSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariablePeakWidth0:Float0:AnalogUnitTypeO
0:HasComponentVariablePeakHeight0:Float0:AnalogUnitTypeO
0:HasComponentVariablePeakArea0:Float0:AnalogUnitTypeO
0:HasPropertyVariableTailingFactor0:Float0:PropertyTypeO
0:HasComponentVariableExpectedRetentionTime0:Float0:AnalogUnitTypeO
0:HasComponentVariableActualRetentionTime0:Float0:AnalogUnitTypeO
0:HasPropertyVariableInjectionTime0:DateTime0:PropertyTypeO
0:HasPropertyVariableComponentName0:String0:PropertyTypeO
Conformance Units
PA-DIM GasChromatographSignalType
PA-DIM GasChromatographSignalType Peak
PA-DIM GasChromatographSignalType RetentionTime
PA-DIM GasChromatographSignalType InjectionTime
PA-DIM GasChromatographSignalType ComponentName

PeakWidth is defined by IRDI as ABQ022#001 which states "width of a chromatogram peak in time units, measured at 10% of peak height".

PeakHeight is defined by IRDI as ABQ023#001 which states "magnitude of a Process GC output signal in units defined by the manufacturer, measured from the peak tip perpendicular to the baseline".

PeakArea is defined by IRDI as ABQ042#001 which states "integral of the area under the output peak of a chromatogram signal in units defined by the manufacturer".

TailingFactor is defined by IRDI as ABQ033#001 which states "asymmetry of a substance peak in a chromatogram expressed as the ratio of the back part to the front part of the peak, referred to the peak maximum, at 10 % peak height above the baseline".

ExpectedRetentionTime is defined by IRDI as ABQ034#001 which states "anticipated time a component needs between injection into the column and detection of the peak".

ActualRetentionTime is defined by IRDI as ABQ035#001 which states "measured time a component needs between injection into the column and detection of the peak".

InjectionTime is defined by IRDI as ABQ006#001 which states "time stamp of sample injection to the chromatograph".

ComponentName is defined by IRDI as ABQ045#001 which states "name of the medium".

The components of IGasChromatographSignalConditionSetType have additional references which are defined in Table 92.

Table 92 - IGasChromatographSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
PeakWidth0:HasDictionaryEntryTrue3:0112/2///61987#ABQ022#001
PeakHeight0:HasDictionaryEntryTrue3:0112/2///61987#ABQ023#001
PeakArea0:HasDictionaryEntryTrue3:0112/2///61987#ABQ042#001
TailingFactor0:HasDictionaryEntryTrue3:0112/2///61987#ABQ033#001
ExpectedRetentionTime0:HasDictionaryEntryTrue3:0112/2///61987#ABQ034#001
ActualRetentionTime0:HasDictionaryEntryTrue3:0112/2///61987#ABQ035#001
InjectionTime0:HasDictionaryEntryTrue3:0112/2///61987#ABQ006#001
ComponentName0:HasDictionaryEntryTrue3:0112/2///61987#ABQ045#001

The child Nodes of the IGasChromatographSignalConditionSetType have additional Attribute values defined in Table 93.

Table 93 - IGasChromatographSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
PeakWidth0
PeakHeight0
PeakArea0
TailingFactor1.0
ExpectedRetentionTime0
ActualRetentionTime0
InjectionTime1/1/1601 12:00:00 AM
ComponentName