7.1 PA-DIM Interfaces

7.1.1 IAdministrationType

The IAdministrationType provides the interface to administration variables and methods of the device and is formally defined in Table 16.

Table 16 - IAdministrationType definition
AttributeValue
BrowseNameIAdministrationType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableDisplayLanguage0:LocaleId0:BaseDataVariableTypeO
0:HasComponentVariableDateOfLastChange0:DateTime0:BaseDataVariableTypeO
0:HasComponentMethodFactoryResetDefined in 9.1 O
Conformance Units
PA-DIM IAdmin DisplayLanguage
PA-DIM IAdmin DateOfChange
PA-DIM IAdmin FactoryReset

DisplayLanguage: is the language used for the local display of the device. ABN597#004 defines language or languages set on the display.

DateOfLastChange: ABN604#001 defines parameter indicating the date and time at which one of the device parameters was changed the last time.

FactoryReset: ABN609#002 property the value of which indicates the kind of reset function to be executed. Note: Properties can be variables or methods according IEC 61987 CDD.

The components of IAdministrationType have additional references which are defined in Table 17.

Table 17 - IAdministrationType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
DisplayLanguage0:HasDictionaryEntryTrue3:0112/2///61987#ABN597#004
DateOfLastChange0:HasDictionaryEntryTrue3:0112/2///61987#ABN604#001
FactoryReset0:HasDictionaryEntryTrue3:0112/2///61987#ABN609#002

The child Nodes of the IAdministrationType have additional Attribute values defined in Table 18.

Table 18 - IAdministrationType Attribute values for child Nodes
BrowsePathValue Attribute
DisplayLanguageen
DateOfLastChange1/1/1601 12:00:00 AM

7.1.2 ISignalSetType

The ISignalSetType provides the interface to process variables of the device and is formally defined in Table 19.

Table 19 - ISignalSetType definition
AttributeValue
BrowseNameISignalSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentObjectSignalSetSignalSetTypeO
Conformance Units
PA-DIM ISignal

SignalSet is a container object for the process variables of the device.

7.1.3 ICalibrationType

The ICalibrationType provides the interface to calibration variables of the sensor resp. signal and is formally defined in Table 20.

Table 20 - ICalibrationType definition
AttributeValue
BrowseNameICalibrationType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableCalibrationTimestamp0:DateTime0:PropertyTypeO
0:HasComponentVariableTypeOfCalibration0:UInt320:MultiStateDictionaryEntryDiscreteTypeO
0:HasComponentObjectCalibrationPointSetCalibrationPointSetTypeO
Conformance Units
PA-DIM ICalibration
PA-DIM ICalibration CalibrationTimestamp
PA-DIM ICalibration TypeOfCalibration
PA-DIM ICalibration CalibrationPointSet

CalibrationTimestamp is defined by IRDI as ABP544#001 which states "point in time when a measurement channel of a device was calibrated".

TypeOfCalibration is defined by IRDI as ABH609#002 which states "classification of a calibration according to its intended use".

CalibrationPointSet is a container object for calibration points of the sensor resp. signal.

The components of ICalibrationType have additional references which are defined in Table 21.

Table 21 - ICalibrationType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
CalibrationTimestamp0:HasDictionaryEntryTrue3:0112/2///61987#ABP544#001
TypeOfCalibration0:HasDictionaryEntryTrue3:0112/2///61987#ABH609#002

The child Nodes of the ICalibrationType have additional Attribute values defined in Table 22.

Table 22 - ICalibrationType Attribute values for child Nodes
BrowsePathValue Attribute
CalibrationTimestamp1/1/1601 12:00:00 AM
TypeOfCalibration0
TypeOfCalibration
0:ValueAsDictionaryEntries

ns=3;s=0112/2///61987#ABP732#001
TypeOfCalibration
0:ValueAsText

adjustment

7.1.4 IConductivityCalibrationType

The IConductivityCalibrationType provides the interface to conductivity measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 23.

Table 23 - IConductivityCalibrationType definition
AttributeValue
BrowseNameIConductivityCalibrationType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableConductivityCellConstant0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM PhSignalType

ConductivityCellConstant is defined by IRDI as ABF161#001 which states "ratio of the distance between the electrodes to the electrode area".

The components of IConductivityCalibrationType have additional references which are defined in Table 24.

Table 24 - IConductivityCalibrationType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
ConductivityCellConstant0:HasDictionaryEntryTrue3:0112/2///61987#ABF161#001
ConductivityCellConstant
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004

The child Nodes of the IConductivityCalibrationType have additional Attribute values defined in Table 25.

Table 25 - IConductivityCalibrationType Attribute values for child Nodes
BrowsePathValue Attribute
ConductivityCellConstant0.0
ConductivityCellConstant
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705744658
DisplayName: cm⁻¹
Description: reciprocal centimetre

7.1.5 IAmperometricCalibrationType

The IAmperometricCalibrationType provides the interface to amperometric measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 26.

Table 26 - IAmperometricCalibrationType definition
AttributeValue
BrowseNameIAmperometricCalibrationType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableAmperometricSensorSlope0:Float0:AnalogUnitTypeO
0:HasComponentVariableAmperometricSensorZeroPoint0:Float0:AnalogUnitTypeO
0:HasComponentVariableAbsoluteAirPressure0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorT900:Float0:PropertyTypeO
Conformance Units
PA-DIM AmperometricSignalType
PA-DIM IAmperometricCalibration AbsoluteAirPressure
PA-DIM IAmperometricCalibration SensorT90

AmperometricSensorSlope is defined by IRDI as ABP572#001 which states "slope of an amperometric sensing element characteristic determined by the last calibration".

AmperometricSensorZeroPoint is defined by IRDI as ABP573#001 which states "zero point of an amperometric sensing element characteristic determined by the last calibration".

AbsoluteAirPressure is defined by IRDI as ABP574#001 which states "absolute air pressure under which the last calibration was performed".

SensorT90 is defined by IRDI as ABP569#001 which states "t90 settling time determined by the last calibration".

The components of IAmperometricCalibrationType have additional references which are defined in Table 27.

Table 27 - IAmperometricCalibrationType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
AmperometricSensorSlope0:HasDictionaryEntryTrue3:0112/2///61987#ABP572#001
AmperometricSensorSlope
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
AmperometricSensorZeroPoint0:HasDictionaryEntryTrue3:0112/2///61987#ABP573#001
AmperometricSensorZeroPoint
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
AbsoluteAirPressure0:HasDictionaryEntryTrue3:0112/2///61987#ABP574#001
AbsoluteAirPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorT900:HasDictionaryEntryTrue3:0112/2///61987#ABP569#001

The child Nodes of the IAmperometricCalibrationType have additional Attribute values defined in Table 28.

Table 28 - IAmperometricCalibrationType Attribute values for child Nodes
BrowsePathValue Attribute
AmperometricSensorZeroPoint0.0
AmperometricSensorZeroPoint
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705750616
DisplayName: pA
Description: picoampere
AbsoluteAirPressure0.0
AbsoluteAirPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705746519
DisplayName: hPa
Description: hectopascal
SensorT900.0

7.1.6 IOpticalFluorescenseQuenchingCalibrationType

The IOpticalFluorescenseQuenchingCalibrationType provides the interface to optical fluorescence quenching measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 29.

Table 29 - IOpticalFluorescenseQuenchingCalibrationType definition
AttributeValue
BrowseNameIOpticalFluorescenseQuenchingCalibrationType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableOpticalFluorescenseQuenchingSensorSlope0:Float0:AnalogUnitTypeO
0:HasComponentVariableOpticalFluorescenseQuenchingSensorZeroPoint0:Float0:AnalogUnitTypeO
0:HasComponentVariableAbsoluteAirPressure0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorT900:Float0:PropertyTypeO
Conformance Units
PA-DIM OpticalFluorescenseQuenchingSignalType
PA-DIM IOpticalFluorescenseQuenchingCalibration AbsoluteAirPressure
PA-DIM IOpticalFluorescenseQuenchingCalibration SensorT90

OpticalFluorescenseQuenchingSensorSlope is defined by IRDI as ABP586#001 which states "slope of an optical fluorescence quenching sensing element characteristic determined by the last calibration".

OpticalFluorescenseQuenchingSensorZeroPoint is defined by IRDI as ABP587#001 which states "zero point of an optical fluorescence quenching sensing element characteristic determined by the last calibration".

AbsoluteAirPressure is defined by IRDI as ABP574#001 which states "absolute air pressure under which the last calibration was performed".

SensorT90 is defined by IRDI as ABP569#001 which states "t90 settling time determined by the last calibration".

The components of IOpticalFluorescenseQuenchingCalibrationType have additional references which are defined in Table 30.

Table 30 - IOpticalFluorescenseQuenchingCalibrationType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
OpticalFluorescenseQuenchingSensorSlope0:HasDictionaryEntryTrue3:0112/2///61987#ABP586#001
OpticalFluorescenseQuenchingSensorSlope
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
OpticalFluorescenseQuenchingSensorZeroPoint0:HasDictionaryEntryTrue3:0112/2///61987#ABP587#001
OpticalFluorescenseQuenchingSensorZeroPoint
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
AbsoluteAirPressure0:HasDictionaryEntryTrue3:0112/2///61987#ABP574#001
AbsoluteAirPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorT900:HasDictionaryEntryTrue3:0112/2///61987#ABP569#001

The child Nodes of the IOpticalFluorescenseQuenchingCalibrationType have additional Attribute values defined in Table 31.

Table 31 - IOpticalFluorescenseQuenchingCalibrationType Attribute values for child Nodes
BrowsePathValue Attribute
OpticalFluorescenseQuenchingSensorZeroPoint0.0
OpticalFluorescenseQuenchingSensorZeroPoint
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741621
DisplayName: µs
Description: microsecond
AbsoluteAirPressure0.0
AbsoluteAirPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705746519
DisplayName: hPa
Description: hectopascal
SensorT900.0

7.1.7 IGasChromatographCalibrationType

The IGasChromatographCalibrationType provides the interface to gaschromatograph measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 32.

Table 32 - IGasChromatographCalibrationTypedefinition
AttributeValue
BrowseNameIGasChromatographCalibrationType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableCalibrationRange1ResponseFactor0:Float0:PropertyTypeO
0:HasComponentVariableCalibrationRange1LowerRangeValue0:Float0:AnalogUnitTypeO
0:HasComponentVariableCalibrationRange1UpperRangeValue0:Float0:AnalogUnitTypeO
0:HasPropertyVariableCalibrationRange2ResponseFactor0:Float0:PropertyTypeO
0:HasComponentVariableCalibrationRange2LowerRangeValue0:Float0:AnalogUnitTypeO
0:HasComponentVariableCalibrationRange2UpperRangeValue0:Float0:AnalogUnitTypeO
0:HasPropertyVariableCalibrationRange3ResponseFactor0:Float0:PropertyTypeO
0:HasComponentVariableCalibrationRange3LowerRangeValue0:Float0:AnalogUnitTypeO
0:HasComponentVariableCalibrationRange3UpperRangeValue0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM GasChromatograph CalibrationRange1
PA-DIM GasChromatograph CalibrationRange2
PA-DIM GasChromatograph CalibrationRange3

CalibrationRange1ResponseFactor is defined by IRDI as ABQ024#001 which states "ratio between the concentration of a compound being analysed and the response of the detector to that compound for the calibration range 1".

CalibrationRange1LowerRangeValue is defined by IRDI as ABQ025#001 which states "volume concentration value assigned to the lower range end-value of calibration range 1".

CalibrationRange1UpperRangeValue is defined by IRDI as ABQ026#001 which states "volume concentration value assigned to the upper range end-value of calibration range 1".

CalibrationRange2ResponseFactor is defined by IRDI as ABQ027#001 which states "ratio between the concentration of a compound being analysed and the response of the detector to that compound for the calibration range 2".

CalibrationRange2LowerRangeValue is defined by IRDI as ABQ028#001 which states "volume concentration value assigned to the lower range end-value of calibration range 2".

CalibrationRange2UpperRangeValue is defined by IRDI as ABQ029#001 which states "volume concentration value assigned to the upper range end-value of calibration range 2".

CalibrationRange3ResponseFactor is defined by IRDI as ABQ030#001 which states "ratio between the concentration of a compound being analysed and the response of the detector to that compound for the calibration range 3".

CalibrationRange3LowerRangeValue is defined by IRDI as ABQ031#001 which states "volume concentration value assigned to the lower range end-value of calibration range 3".

CalibrationRange3UpperRangeValue is defined by IRDI as ABQ032#001 which states "volume concentration value assigned to the upper range end-value of calibration range 3".

The components of IGasChromatographCalibrationType have additional references which are defined in Table 33.

Table 33 - IGasChromatographCalibrationType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
CalibrationRange1ResponseFactor0:HasDictionaryEntryTrue3:0112/2///61987#ABQ024#001
CalibrationRange1LowerRangeValue0:HasDictionaryEntryTrue3:0112/2///61987#ABQ025#001
CalibrationRange1UpperRangeValue0:HasDictionaryEntryTrue3:0112/2///61987#ABQ026#001
CalibrationRange2ResponseFactor0:HasDictionaryEntryTrue3:0112/2///61987#ABQ027#001
CalibrationRange2LowerRangeValue0:HasDictionaryEntryTrue3:0112/2///61987#ABQ028#001
CalibrationRange2UpperRangeValue0:HasDictionaryEntryTrue3:0112/2///61987#ABQ029#001
CalibrationRange3ResponseFactor0:HasDictionaryEntryTrue3:0112/2///61987#ABQ030#001
CalibrationRange3LowerRangeValue0:HasDictionaryEntryTrue3:0112/2///61987#ABQ031#001
CalibrationRange3UpperRangeValue0:HasDictionaryEntryTrue3:0112/2///61987#ABQ032#001

The child Nodes of the IGasChromatographCalibrationType have additional Attribute values defined in Table 34.

Table 34 - IGasChromatographCalibrationType Attribute values for child Nodes
BrowsePathValue Attribute
CalibrationRange1ResponseFactor1.0
CalibrationRange1LowerRangeValue0.0
CalibrationRange1LowerRangeValue
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange1UpperRangeValue100.0
CalibrationRange1UpperRangeValue
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange2ResponseFactor1.0
CalibrationRange2LowerRangeValue0.0
CalibrationRange2LowerRangeValue
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange2UpperRangeValue100.0
CalibrationRange2UpperRangeValue
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange3ResponseFactor1.0
CalibrationRange3LowerRangeValue0.0
CalibrationRange3LowerRangeValue
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange3UpperRangeValue100.0
CalibrationRange3UpperRangeValue
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

7.1.8 IPhCalibrationType

The IPhCalibrationType provides the interface to pH measurement specific calibration variables of the sensor resp. signal and is formally defined in .

Table 35 - IPhCalibrationType definition
AttributeValue
BrowseNameIPhCalibrationType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensorSlope0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorAsymmetryPotential0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorT900:Float0:PropertyTypeO
Conformance Units
PA-DIM PhSignalType
PA-DIM IPhCalibration SensorT90

SensorSlope is defined by IRDI as ABP567#001 which states "slope of a pH sensing element characteristic, expressed as the voltage change of the pH sensor per pH value, determined by the last calibration".

SensorAsymmetryPotential is defined by IRDI as ABP568#001 which states "asymmetry potential of a pH sensing element characteristic determined by the last calibration".

SensorT90is defined by IRDI as ABP569#001 which states "t90 settling time determined by the last calibration".

The components of IPhCalibrationType have additional references which are defined in Table 36.

Table 36 - IPhCalibrationType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SensorSlope0:HasDictionaryEntryTrue3:0112/2///61987#ABP567#001
SensorSlope
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorAsymmetryPotential0:HasDictionaryEntryTrue3:0112/2///61987#ABP568#001
SensorAsymmetryPotential
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorT900:HasDictionaryEntryTrue3:0112/2///61987#ABP569#001

The child Nodes of the IPhCalibrationType have additional Attribute values defined in Table 37.

Table 37 - IPhCalibrationType Attribute values for child Nodes
BrowsePathValue Attribute
SensorSlope0.0
SensorSlope
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749524
DisplayName: mV

Description: millivolt

SensorAsymmetryPotential0.0
SensorAsymmetryPotential
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749524

DisplayName: mV

Description: millivolt

SensorT900.0

7.1.9 IGeneralDeviceConditionSetType

The IGeneralDeviceConditionSetType provides the interface to condition variables of the device and its components and is formally defined in Table 38.

Table 38 - IGeneralDeviceConditionSetType definition
AttributeValue
BrowseNameIGeneralDeviceConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentObjectGeneralDeviceConditionsGeneralDeviceConditionSetTypeO
0:HasComponentObjectDeviceComponentConditions0:BaseObjectTypeO
Conformance Units
PA-DIM IGeneralDeviceConditionSet
PA-DIM IGeneralDeviceConditionSet DeviceComponentConditions

GeneralDeviceConditions is a container object for general condition variables of the device.

DeviceComponentConditions is a container object for condition variables of the device components.

Table 39 - IGeneralDeviceConditionSetType additional subcomponents
BrowsePathReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
DeviceComponentConditions0:HasComponentObject<DeviceComponentIdentifier>GeneralDeviceConditionSetTypeOP

<DeviceComponentIdentifier> is an optional placeholder for an object containing the condition variables related to a specific device component.

7.1.10 ITocDeviceConditionSetType

The ITocDeviceConditionSetType provides the interface to TOC device specific condition variables and is formally defined in Table 40.

Table 40 - ITocDeviceConditionSetType definition
AttributeValue
BrowseNameITocDeviceConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableCarrierGasVolumeFlow0:Float0:AnalogUnitTypeO
0:HasComponentVariableCarrierGasGaugePressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableReactorTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleWaterVolumeFlow0:Float0:AnalogUnitTypeO
0:HasComponentVariableReferenceInjectionVolume0:Float0:AnalogUnitTypeO
0:HasComponentVariableActualInjectedVolume0:Float0:AnalogUnitTypeO
0:HasComponentVariableCoolerTemperature0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM TocAnalyserType
PA-DIM TocAnalyserType CarrierGasGaugePressure
PA-DIM TocAnalyserType SampleWaterVolumeFlow
PA-DIM TocAnalyserType ActualInjectedVolume

CarrierGasVolumeFlow is defined by IRDI as ABP558#001 which states "volume flow of the auxiliary (compressed air) gas supply".

CarrierGasGaugePressure is defined by IRDI as ABP559#001 which states "overpressure of the auxiliary (compressed air) gas supply in the system due to flow resistance within the complete analytical system".

ReactorTemperature is defined by IRDI as ABP554#001 which states "measured temperature of a high temperature combustion system".

SampleWaterVolumeFlow is defined by IRDI as ABP561#001 which states "volume flow of a liquid sample inside the device".

ReferenceInjectionVolume is defined by IRDI as ABP563#001 which states "volume of liquid that should be injected by the injection system".

ActualInjectedVolume is defined by IRDI as ABP564#001 which states "volume of liquid that has been injected by the injection system".

CoolerTemperature is defined by IRDI as ABP555#001 which states "measured temperature of the gas cooler".

The components of ITocDeviceConditionSetType have additional references which are defined in Table 41.

Table 41 - ITocDeviceConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
CarrierGasVolumeFlow0:HasDictionaryEntryTrue3:0112/2///61987#ABP558#001
CarrierGasVolumeFlow
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
CarrierGasGaugePressure0:HasDictionaryEntryTrue3:0112/2///61987#ABP559#001
CarrierGasGaugePressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
ReactorTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP554#001
ReactorTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SampleWaterVolumeFlow0:HasDictionaryEntryTrue3:0112/2///61987#ABP561#001
SampleWaterVolumeFlow
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
ReferenceInjectionVolume0:HasDictionaryEntryTrue3:0112/2///61987#ABP563#001
ReferenceInjectionVolume
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
ActualInjectedVolume0:HasDictionaryEntryTrue3:0112/2///61987#ABP564#001
ActualInjectedVolume
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
CoolerTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP555#001
CoolerTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004

The child Nodes of the ITocDeviceConditionSetType have additional Attribute values defined in Table 42.

Table 42 - ITocDeviceConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
CarrierGasVolumeFlow0.0
CarrierGasVolumeFlow
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705747637
DisplayName: l/h
Description: litre per hour
CarrierGasGaugePressure0.0
CarrierGasGaugePressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
ReactorTemperature0.0
ReactorTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SampleWaterVolumeFlow0.0
SampleWaterVolumeFlow
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749685
DisplayName: ml/min

Description: millilitre per minute

ReferenceInjectionVolume0.0
ReferenceInjectionVolume
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705749652
DisplayName: ml

Description: millilitre

ActualInjectedVolume0.0
ActualInjectedVolume
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705749652
DisplayName: ml

Description: millilitre

CoolerTemperature0.0
CoolerTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius

7.1.11 IFlameIonisationDeviceConditionSetType

The IFlameIonisationDeviceConditionSetType provides the interface to FID specific condition variables and is formally defined in Table 43.

Table 43 - IFlameIonisationDeviceConditionSetType definition
AttributeValue
BrowseNameIFlameIonisationDeviceConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableCatalystTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableFuelGasPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableCombustionAirPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableBlockTemperature0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM FlameIonisationDetectorType CatalystTemperature
PA-DIM FlameIonisationDetectorType FuelGasPressure
PA-DIM FlameIonisationDetectorType CombustionAirPressure
PA-DIM FlameIonisationDetectorType BlockTemperature

CatalystTemperature is defined by IRDI as ABP576#001 which states "measured temperature of a catalyst".

FuelGasPressure is defined by IRDI as ABP578#001 which states "measured absolute pressure of the fuel gas".

CombustionAirPressure is defined by IRDI as ABP579#001 which states "measured absolute pressure of the combustion air".

BlockTemperature is defined by IRDI as ABP577#001 which states "measured temperature of a flame ionisation detector block".

The components of IFlameIonisationDeviceConditionSetType have additional references which are defined in Table 44.

Table 44 - IFlameIonisationDeviceConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
CatalystTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP576#001
CatalystTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
FuelGasPressure0:HasDictionaryEntryTrue3:0112/2///61987#ABP578#001
FuelGasPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
CombustionAirPressure0:HasDictionaryEntryTrue3:0112/2///61987#ABP579#001
CombustionAirPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
BlockTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP577#001
BlockTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004

The child Nodes of the IFlameIonisationDeviceConditionSetType have additional Attribute values defined in Table 45.

Table 45 - IFlameIonisationDeviceConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
CatalystTemperature0.0
CatalystTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
FuelGasPressure0.0
FuelGasPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
CombustionAirPressure0.0
CombustionAirPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
BlockTemperature0.0
BlockTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius

7.1.12 IGasChromatographDeviceConditionSetType

The IGasChromatographDeviceConditionSetType provides the interface to gas chromatograph device specific condition variables and is formally defined in Table 46

Table 46 - IGasChromatographDeviceConditionSetType definition
AttributeValue
BrowseNameIGasChromatographDeviceConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableValveName0:LocalizedText[]0:PropertyTypeO
0:HasPropertyVariableValveSwitchingCyclesCounter0:UInt32[]0:PropertyTypeO
0:HasComponentVariableTotalAreaMeasuredPeaks0:Float0:AnalogUnitTypeO
0:HasComponentVariableBaselineNoise0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM GasChromatographType
PA-DIM GasChromatographType Valve
PA-DIM GasChromatographType TotalAreaMeasuredPeaks
PA-DIM GasChromatographType BaselineNoise

ValveName is defined by IRDI as ABQ046#001 which states "name of the valve".

ValveSwitchingCyclesCounter is defined by IRDI as ABQ007#001 which states "number of opening or closing operations of a valve".

TotalAreaMeasuredPeaks is defined by IRDI as ABQ043#001 which states "integral of the area under the output peaks of all chromatogram substance signals in units defined by the manufacturer".

BaselineNoise is defined by IRDI as ABQ036#001 which states "short-term variation of the baseline from a straight line caused by electric signal fluctuations from the detector".

The components of IGasChromatographDeviceConditionSetType have additional references which are defined in Table 48.

Table 47 - IGasChromatographDeviceConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
ValveName0:HasDictionaryEntryTrue3:0112/2///61987#ABQ046#001
ValveSwitchingCyclesCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABQ007#001
TotalAreaMeasuredPeaks0:HasDictionaryEntryTrue3:0112/2///61987#ABQ043#001
BaselineNoise0:HasDictionaryEntryTrue3:0112/2///61987#ABQ036#001

The child Nodes of the IGasChromatographDeviceConditionSetType have additional Attribute values defined in Table 48.

Table 48 - IGasChromatographDeviceConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
TotalAreaMeasuredPeaks0.0
TotalAreaMeasuredPeaks
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

BaselineNoise0.0
BaselineNoise
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749524

DisplayName: mV
Description: millivolt

7.1.13 IFtnirOrFtirDeviceConditionSetType

The IFtnirOrFtirDeviceConditionSetType provides the interface to Fourier Transform Near-Infrared Spectroscopy or Fourier Transform Infrared Spectroscopy device specific condition variables and is formally defined in Table 49.

Table 49 - IFtnirOrFtirDeviceConditionSetType definition
AttributeValue
BrowseNameIFtnirOrFtirDeviceConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableWatchdog0:Boolean0:PropertyTypeO
0:HasPropertyVariableRemainingDataStorageCapacity0:Float0:PropertyTypeO
Conformance Units
PA-DIM FtnirOrFtirSpectrometerType
PA-DIM FtnirOrFtirSpectrometerType Watchdog
PA-DIM FtnirOrFtirSpectrometerType RemainingDataStorageCapacity

Watchdog is defined by IRDI as ABP996#002 which states "existence of a function for failure detection of installed hardware and software"

RemainingDataStorageCapacity is defined by IRDI as ABQ039#001 which states "amount of memory remaining for storage of device data, measured in terabytes".

The components of IFtnirOrFtirDeviceConditionSetType have additional references which are defined in Table 50.

Table 50 - IFtnirOrFtirDeviceConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
Watchdog0:HasDictionaryEntryTrue3:0112/2///61987#ABP996#002
RemainingDataStorageCapacity0:HasDictionaryEntryTrue3:0112/2///61987#ABQ039#001

The child Nodes of the IFtnirOrFtirDeviceConditionSetType have additional Attribute values defined in Table 51.

Table 51 - IFtnirOrFtirDeviceConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
RemainingDataStorageCapacity0.0

7.1.14 IDiodeArrayDeviceConditionSetType

The IDiodeArrayDeviceConditionSetType provides the interface to Diode array spectrometer device specific condition variables and is formally defined in Table 52.

Table 52 - IDiodeArrayDeviceConditionSetType definition
AttributeValue
BrowseNameIDiodeArrayDeviceConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableWatchdog0:Boolean0:PropertyTypeO
0:HasPropertyVariableRemainingDataStorageCapacity0:Float0:PropertyTypeO
Conformance Units
PA-DIM DiodeArraySpectrometerType
PA-DIM DiodeArraySpectrometerType Watchdog
PA-DIM DiodeArraySpectrometerType RemainingDataStorageCapacity

Watchdog is defined by IRDI as ABP996#002 which states "existence of a function for failure detection of installed hardware and software"

RemainingDataStorageCapacity is defined by IRDI as ABQ039#001 which states "amount of memory remaining for storage of device data, measured in terabytes".

The components of IDiodeArrayDeviceConditionSetType have additional references which are defined in Table 53.

Table 53 - IDiodeArrayDeviceConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
Watchdog0:HasDictionaryEntryTrue3:0112/2///61987#ABP996#002
RemainingDataStorageCapacity0:HasDictionaryEntryTrue3:0112/2///61987#ABQ039#001

The child Nodes of the IDiodeArrayDeviceConditionSetType have additional Attribute values defined in Table 54.

Table 54 - IDiodeArrayDeviceConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
RemainingDataStorageCapacity0.0

7.1.15 IRamanDeviceConditionSetType

The IRamanDeviceConditionSetType provides the interface to Raman spectrometer device specific condition variables and is formally defined in Table 55.

Table 55 - IRamanDeviceConditionSetType definition
AttributeValue
BrowseNameIRamanDeviceConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableWatchdog0:Boolean0:PropertyTypeO
0:HasPropertyVariableRemainingDataStorageCapacity0:Float0:PropertyTypeO
Conformance Units
PA-DIM RamanSpectrometerType
PA-DIM RamanSpectrometerType Watchdog
PA-DIM RamanSpectrometerType RemainingDataStorageCapacity

Watchdog is defined by IRDI as ABP996#002 which states "existence of a function for failure detection of installed hardware and software"

RemainingDataStorageCapacity is defined by IRDI as ABQ039#001 which states "amount of memory remaining for storage of device data, measured in terabytes".

The components of IRamanDeviceConditionSetType have additional references which are defined in Table 56.

Table 56 - IRamanDeviceConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
Watchdog0:HasDictionaryEntryTrue3:0112/2///61987#ABP996#002
RemainingDataStorageCapacity0:HasDictionaryEntryTrue3:0112/2///61987#ABQ039#001

The child Nodes of the IRamanDeviceConditionSetType have additional Attribute values defined in Table 57.

Table 57 - IRamanDeviceConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
RemainingDataStorageCapacity0.0

7.1.16 INonDispersiveInfraredSignalConditionSetType

The INonDispersiveInfraredSignalConditionSetType provides the interface to NDIR measurement signal specific condition variables and is formally defined in Table 58.

Table 58 - INonDispersiveInfraredSignalConditionSetType definition
AttributeValue
BrowseNameINonDispersiveInfraredSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableChopperFrequencyDeviation0:Float0:BaseAnalogTypeO
0:HasComponentVariableAbsoluteSampleGasPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleCellTemperature0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
Conformance Units
PA-DIM NonDispersiveInfraredSignalType ChopperFrequencyDeviation
PA-DIM NonDispersiveInfraredSignalType
PA-DIM NonDispersiveInfraredSignalType AbsoluteSampleGasPressure

ChopperFrequencyDeviation is defined by IRDI as ABP553#001 which states "relative change in the chopper frequency of a detector during a measurement".

AbsoluteSampleGasPressure is defined by IRDI as ABP560#001 which states "absolute pressure of sample gas inside a detection system".

SampleCellTemperature is defined by IRDI as ABP556#001 which states "measured temperature of the sample cell".

SourceResidualLife is defined by IRDI as ABP552#001 which states "degradation of a radiation source expressed as a value between 1 (good) and 0 (bad)".

The components of INonDispersiveInfraredSignalConditionSetType have additional references which are defined in Table 59.

Table 59 - INonDispersiveInfraredSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
ChopperFrequencyDeviation0:HasDictionaryEntryTrue3:0112/2///61987#ABP553#001
ChopperFrequencyDeviation
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
AbsoluteSampleGasPressure0:HasDictionaryEntryTrue3:0112/2///61987#ABP560#001
AbsoluteSampleGasPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SampleCellTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP556#001
SampleCellTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SourceResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABP552#001

The child Nodes of the INonDispersiveInfraredSignalConditionSetType have additional Attribute values defined in Table 60.

Table 60 - INonDispersiveInfraredSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
ChopperFrequencyDeviation0.0
ChopperFrequencyDeviation
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

AbsoluteSampleGasPressure0.0
AbsoluteSampleGasPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
SampleCellTemperature0.0
SampleCellTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SourceResidualLife1.0

7.1.17 ITocSignalConditionSetType

The ITocSignalConditionSetType provides the interface to TOC measurement signal specific condition variables and is formally defined in Table 61.

Table 61 - ITocSignalConditionSetType definition
AttributeValue
BrowseNameITocSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableChopperFrequencyDeviation0:Float0:BaseAnalogTypeO
0:HasComponentVariableRelativeReagentLevel0:Float{Any}0:AnalogUnitTypeO
0:HasComponentVariableSampleCellTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableDetectorZeroSignal0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
0:HasComponentVariableAbsoluteSampleGasPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleGasVolumeFlow0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM TocSignalType
PA-DIM TocSignalType ChopperFrequencyDeviation
PA-DIM TocSignalType RelativeReagentLevel
PA-DIM TocSignalType AbsoluteSampleGasPressure
PA-DIM TocSignalType SampleGasVolumeFlow

ChopperFrequencyDeviation is defined by IRDI as ABP553#001 which states "relative change in the chopper frequency of a detector during a measurement".

RelativeReagentLevel is defined by IRDI as ABP557#001 which states "relative filling level of auxiliary reagent".

SampleCellTemperature is defined by IRDI as ABP556#001 which states "measured temperature of the sample cell".

DetectorZeroSignal is defined by IRDI as ABP551#001 which states "offset signal of the detector prior to the injection of the sample".

SourceResidualLife is defined by IRDI as ABP552#001 which states "degradation of a radiation source expressed as a value between 1 (good) and 0 (bad)".

AbsoluteSampleGasPressure is defined by IRDI as ABP560#001 which states "absolute pressure of sample gas inside a detection system".

SampleGasVolumeFlow is defined by IRDI as ABP562#001 which states "volume flow of a sample gas through a detection system".

The components of ITocSignalConditionSetType have additional references which are defined in Table 62.

Table 62 - ITocSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
ChopperFrequencyDeviation0:HasDictionaryEntryTrue3:0112/2///61987#ABP553#001
ChopperFrequencyDeviation
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
RelativeReagentLevel0:HasDictionaryEntryTrue3:0112/2///61987#ABP557#001
RelativeReagentLevel
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SampleCellTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP556#001
SampleCellTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
DetectorZeroSignal0:HasDictionaryEntryTrue3:0112/2///61987#ABP551#001
DetectorZeroSignal
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SourceResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABP552#001
AbsoluteSampleGasPressure0:HasDictionaryEntryTrue3:0112/2///61987#ABP560#001
AbsoluteSampleGasPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SampleGasVolumeFlow0:HasDictionaryEntryTrue3:0112/2///61987#ABP562#001
SampleGasVolumeFlow
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004

The child Nodes of the ITocSignalConditionSetType have additional Attribute values defined in Table 63.

Table 63 - ITocSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
ChopperFrequencyDeviation0.0
ChopperFrequencyDeviation
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

RelativeReagentLevel0.0
RelativeReagentLevel
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

SampleCellTemperature0.0
SampleCellTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
DetectorZeroSignal0.0
DetectorZeroSignal
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705848917

DisplayName: ppm

Description: parts per million

SourceResidualLife1.0
AbsoluteSampleGasPressure0.0
AbsoluteSampleGasPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
SampleGasVolumeFlow0.0
SampleGasVolumeFlow
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705747637

DisplayName: l/h

Description: litre per hour

7.1.18 IParamagneticSignalConditionSetType

The IParamagneticSignalConditionSetType provides the interface to paramagnetic measurement signal specific condition variables and is formally defined in Table 64.

Table 64 - IParamagneticSignalConditionSetType definition
AttributeValue
BrowseNameIParamagneticSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSampleTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM ParamagneticSignalType

SampleTemperature is defined by IRDI as ABP575#001 which states "temperature of the sample at the point of measurement".

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

The components of IParamagneticSignalConditionSetType have additional references which are defined in Table 65.

Table 65 - IParamagneticSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SampleTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP575#001
SampleTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SensingElementTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004

The child Nodes of the IParamagneticSignalConditionSetType have additional Attribute values defined in Table 66.

Table 66 - IParamagneticSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SampleTemperature0.0
SampleTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SensingElementTemperature0.0
SensingElementTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius

7.1.19 IThermalConductivitySignalConditionSetType

The IThermalConductivitySignalConditionSetType provides the interface to thermal conductivity measurement signal specific condition variables and is formally defined in Table 67.

Table 67 - IThermalConductivitySignalConditionSetType definition
AttributeValue
BrowseNameIThermalConductivitySignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSampleTemperature0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM ThermalConductivitySignalType

SampleTemperature is defined by IRDI as ABP575#001 which states "temperature of the sample at the point of measurement".

The components of IThermalConductivitySignalConditionSetType have additional references which are defined in Table 68.

Table 68 - IThermalConductivitySignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SampleTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP575#001
SampleTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004

The child Nodes of the IThermalConductivitySignalConditionSetType have additional Attribute values defined in Table 69.

Table 69 - IThermalConductivitySignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SampleTemperature0.0
SampleTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius

7.1.20 ITunableDiodeLaserSignalConditionSetType

The ITunableDiodeLaserSignalConditionSetType provides the interface to TDL measurement signal specific condition variables and is formally defined in Table 70.

Table 70 - ITunableDiodeLaserSignalConditionSetType definition
AttributeValue
BrowseNameITunableDiodeLaserSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableAbsoluteSampleGasPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableTransmissionRatio0:Float0:DataItemTypeO
0:HasComponentVariableSignalNoiseRatio0:Float0:DataItemTypeO
0:HasComponentVariableLaserTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSignalFitQuality0:Float0:DataItemTypeO
Conformance Units
PA-DIM TunableDiodeLaserSignalType
PA-DIM TunableDiodeLaserSignalType SignalFitQuality
PA-DIM TunableDiodeLaserSignalType SignalNoiseRatio
PA-DIM TunableDiodeLaserSignalType TransmissionRatio
PA-DIM TunableDiodeLaserSignalType LaserTemperature
PA-DIM TunableDiodeLaserSignalType AbsoluteSampleGasPressure

AbsoluteSampleGasPressure is defined by IRDI as ABP560#001 which states "absolute pressure of sample gas inside a detection system".

SampleTemperature is defined by IRDI as ABP575#001 which states "temperature of the sample at the point of measurement".

TransmissionRatio is defined by IRDI as ABP582#001 which states "ratio of the value of a specified radiation quantity in the centre of a beam of specified radiation quality and under specified geometrical conditions after passage through a material to the value which would be present at the same position without this material in the beam".

SignalNoiseRatio is defined by IRDI as ABP581#001 which states "linear ratio of the signal level to the noise level as measured under specified conditions".

LaserTemperature is defined by IRDI as ABP583#001 which states "measured temperature of the element that defines the wavelength of a laser".

SignalFitQuality is defined by IRDI as ABP580#001 which states "degree of correlation between the calculated and the measured absorption signal".

The components of ITunableDiodeLaserSignalConditionSetType have additional references which are defined in Table 71.

Table 71 - ITunableDiodeLaserSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
AbsoluteSampleGasPressure0:HasDictionaryEntryTrue3:0112/2///61987#ABP560#001
AbsoluteSampleGasPressure
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SampleTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP575#001
SampleTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
TransmissionRatio0:HasDictionaryEntryTrue3:0112/2///61987#ABP582#001
SignalNoiseRatio0:HasDictionaryEntryTrue3:0112/2///61987#ABP581#001
LaserTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP583#001
LaserTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SignalFitQuality0:HasDictionaryEntryTrue3:0112/2///61987#ABP580#001

The child Nodes of the ITunableDiodeLaserSignalConditionSetType have additional Attribute values defined in Table 72.

Table 72 - ITunableDiodeLaserSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
AbsoluteSampleGasPressure0.0
AbsoluteSampleGasPressure
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
SampleTemperature0.0
SampleTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
TransmissionRatio0.0
SignalNoiseRatio0.0
LaserTemperature0.0
LaserTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SignalFitQuality0.0

7.1.21 IZirconiumDioxideSignalConditionSetType

The IZirconiumDioxideSignalConditionSetType provides the interface to Zirconium dioxide measurement signal specific condition variables and is formally defined in Table 73.

Table 73 - IZirconiumDioxideSignalConditionSetType definition
AttributeValue
BrowseNameIZirconiumDioxideSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableRelativeHeatOutput0:Float0:AnalogUnitTypeO
0:HasComponentVariableCellResistance0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensingElementResidualLife0:Float0:PropertyTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleGasVolumeFlow0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM ZirconiumDioxideSignalType
PA-DIM ZirconiumDioxideSignalType RelativeHeatOutput
PA-DIM ZirconiumDioxideSignalType CellResistance
PA-DIM ZirconiumDioxideSignalType SensingElementResidualLife
PA-DIM ZirconiumDioxideSignalType SampleGasVolumeFlow

RelativeHeatOutput is defined by IRDI as ABP585#001 which states "relative heat output referred to the maximum heat output to keep the sensor at its setpoint temperature during operation".

SensingElementResidualLife is defined by IRDI as ABP584#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad)".

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

SampleGasVolumeFlow is defined by IRDI as ABP562#001 which states "volume flow of a sample gas through a detection system".

The components of IZirconiumDioxideSignalConditionSetType have additional references which are defined in Table 74.

Table 74 - IZirconiumDioxideSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
RelativeHeatOutput0:HasDictionaryEntryTrue3:0112/2///61987#ABP585#001
RelativeHeatOutput
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
CellResistance0:HasDictionaryEntryTrue3:0112/2///61987#ABP596#001
SensingElementResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABP584#001
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SensingElementTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SampleGasVolumeFlow0:HasDictionaryEntryTrue3:0112/2///61987#ABP562#001
SampleGasVolumeFlow
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004

The child Nodes of the IZirconiumDioxideSignalConditionSetType have additional Attribute values defined in Table 75.

Table 75 - IZirconiumDioxideSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
RelativeHeatOutput0.0
RelativeHeatOutput
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

CellResistance0.0
SensingElementResidualLife1.0
SensingElementTemperature0.0
SensingElementTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SampleGasVolumeFlow0.0
SampleGasVolumeFlow
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705747637
DisplayName: l/h
Description: litre per hour

7.1.22 IPhSignalConditionSetType

The IPhSignalConditionSetType provides the interface to pH measurement signal specific condition variables and is formally defined in Table 76.

Table 76 - IPhSignalConditionSetType definition
AttributeValue
BrowseNameIPhSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariablePhMeasuringMethod0:UInt320:MultiStateDictionaryEntryDiscreteTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorNextCalibration0:UInt320:AnalogUnitTypeO
0:HasComponentVariableSensingElementImpedance0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorReferenceImpedance0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorCleaningsCounter0:UInt320:PropertyTypeO
0:HasPropertyVariableSensorSterilisationsCounter0:UInt320:PropertyTypeO
Conformance Units
PA-DIM PhSignalType
PA-DIM PhSignalType SensorNextCalibration
PA-DIM PhSignalType SensingElementImpedance
PA-DIM PhSignalType SensorReferenceImpedance
PA-DIM PhSignalType SensorCleaningsCounter
PA-DIM PhSignalType SensorSterilisationsCounter

PhMeasuringMethod is defined by IRDI as ABP640#002 which states "physical measuring method of a pH sensor".

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

SensorNextCalibration is defined by IRDI as ABP566#001 which states "time that can elapse until the next calibration, calculated from the configured calibration interval or estimated by the device".

SensingElementImpedance is defined by IRDI as ABP570#001 which states "absolute value of impedance for a pH sensing element, compensated for a temperature of 25°C".

SensorReferenceImpedance is defined by IRDI as ABP571#001 which states "absolute value of impedance for a pH reference system, compensated for a temperature of 25°C".

SensorCleaningsCounter is defined by IRDI as ABP546#001 which states "number of times a sensor has been cleaned in place".

SensorSterilisationsCounter is defined by IRDI as ABP547#001 which states "number of times a sensor has been sterilized in place".

The components of IPhSignalConditionSetType have additional references which are defined in Table 77.

Table 77 - IPhSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
PhMeasuringMethod0:HasDictionaryEntryTrue3:0112/2///61987#ABP640#002
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SensingElementTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorNextCalibration0:HasDictionaryEntryTrue3:0112/2///61987#ABP566#001
SensorNextCalibration
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensingElementImpedance0:HasDictionaryEntryTrue3:0112/2///61987#ABP570#001
SensingElementImpedance
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorReferenceImpedance0:HasDictionaryEntryTrue3:0112/2///61987#ABP571#001
SensorReferenceImpedance
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorCleaningsCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABP546#001
SensorSterilisationsCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABP547#001

The child Nodes of the IPhSignalConditionSetType have additional Attribute values defined in Table 78.

Table 78 - IPhSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
PhMeasuringMethod0
PhMeasuringMethod
0:ValueAsDictionaryEntries

ns=3;s=0112/2///61987#ABP718#001
PhMeasuringMethod
0:ValueAsText

glass electrode
SensingElementTemperature0.0
SensingElementTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C

Description: degree Celsius

SensorNextCalibration0
SensorNextCalibration
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705745431

DisplayName: d

Description: day

SensingElementImpedance0.0
SensingElementImpedance
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741367

DisplayName: Ω

Description: ohm

SensorReferenceImpedance0.0
SensorReferenceImpedance
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741367

DisplayName: Ω

Description: ohm

SensorCleaningsCounter0
SensorSterilisationsCounter0

7.1.23 IConductivitySignalConditionSetType

The IConductivitySignalConditionSetType provides the interface to conductivity measurement signal specific condition variables and is formally defined in Table 79.

Table 79 - IConductivitySignalConditionSetType definition
AttributeValue
BrowseNameIConductivitySignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableConductivityMeasuringMethod0:UInt320:MultiStateDictionaryEntryDiscreteTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableTemperatureCompensationStyle0:UInt320:MultiStateDictionaryEntryDiscreteTypeO
0:HasPropertyVariableSensorCleaningsCounter0:UInt320:PropertyTypeO
0:HasPropertyVariableSensorSterilisationsCounter0:UInt320:PropertyTypeO
Conformance Units
PA-DIM PhSignalType
PA-DIM ConductivitySignalType SensorCleaningsCounter
PA-DIM ConductivitySignalType SensorSterilisationsCounter

ConductivityMeasuringMethod is defined by IRDI as ABP641#002 which states "physical measuring method of a conductivity sensor".

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

TemperatureCompensationStyle is defined by IRDI as ABP642#002 which states "method of temperature compensation that is offered by the device".

SensorCleaningsCounter is defined by IRDI as ABP546#001 which states "number of times a sensor has been cleaned in place".

SensorSterilisationsCounter is defined by IRDI as ABP547#001 which states "number of times a sensor has been sterilized in place".

The components of IConductivitySignalConditionSetType have additional references which are defined in Table 80.

Table 80 - IConductivitySignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
ConductivityMeasuringMethod0:HasDictionaryEntryTrue3:0112/2///61987#ABP641#002
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SensingElementTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
TemperatureCompensationStyle0:HasDictionaryEntryTrue3:0112/2///61987#ABP642#002
SensorCleaningsCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABP546#001
SensorSterilisationsCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABP547#001

The child Nodes of the IConductivitySignalConditionSetType have additional Attribute values defined in Table 81.

Table 81 - IConductivitySignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
ConductivityMeasuringMethod0
ConductivityMeasuringMethod
0:ValueAsDictionaryEntries

ns=3;s=0112/2///61987#ABP721#001
ConductivityMeasuringMethod
0:ValueAsText

inductive
SensingElementTemperature0.0
SensingElementTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
TemperatureCompensationStyle0
TemperatureCompensationStyle
0:ValueAsDictionaryEntries

ns=3;s=0112/2///61987#ABP724#001
TemperatureCompensationStyle
0:ValueAsText

no temperature compensation
SensorCleaningsCounter0
SensorSterilisationsCounter0

7.1.24 IAmperometricSignalConditionSetType

The IAmperometricSignalConditionSetType provides the interface to amperometric measurement signal specific condition variables and is formally defined in Table 82.

Table 82 - IAmperometricSignalConditionSetType definition
AttributeValue
BrowseNameIAmperometricSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorNextCalibration0:UInt320:AnalogUnitTypeO
0:HasPropertyVariableSensorCleaningsCounter0:UInt320:PropertyTypeO
0:HasPropertyVariableSensorSterilisationsCounter0:UInt320:PropertyTypeO
Conformance Units
PA-DIM AmperometricSignalType
PA-DIM AmperometricSignalType SensorNextCalibration
PA-DIM AmperometricSignalType SensorCleaningsCounter
PA-DIM AmperometricSignalType SensorSterilisationsCounter

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

SensorNextCalibration is defined by IRDI as ABP566#001 which states "time that can elapse until the next calibration, calculated from the configured calibration interval or estimated by the device".

SensorCleaningsCounter is defined by IRDI as ABP546#001 which states "number of times a sensor has been cleaned in place".

SensorSterilisationsCounter is defined by IRDI as ABP547#001 which states "number of times a sensor has been sterilized in place".

The components of IAmperometricSignalConditionSetType have additional references which are defined in Table 83.

Table 83 - IAmperometricSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SensingElementTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorNextCalibration0:HasDictionaryEntryTrue3:0112/2///61987#ABP566#001
SensorNextCalibration
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorCleaningsCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABP546#001
SensorSterilisationsCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABP547#001

The child Nodes of the IAmperometricSignalConditionSetType have additional Attribute values defined in Table 84.

Table 84 - IAmperometricSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SensingElementTemperature0.0
SensingElementTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C

Description: degree Celsius

SensorNextCalibration0
SensorNextCalibration
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705745431
DisplayName: d
Description: day
SensorCleaningsCounter0
SensorSterilisationsCounter0

7.1.25 IAmperometricGasDetectorSignalConditionSetType

The IAmperometricGasDetectorSignalConditionSetType provides the interface to Amperometric Electrochemical signal specific condition variables and is formally defined in Table 85

Table 85 - IAmperometricGasDetectorSignalConditionSetType definition
AttributeValue
BrowseNameIAmperometricGasDetectorSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature 0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorNextCalibrationFixed0:Float0:PropertyTypeO
0:HasPropertyVariableSensorNextCalibrationDynamic0:Float0:PropertyTypeO
0:HasPropertyVariablePowerOnDurationSensor0:Duration0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualLife0:Float0:PropertyTypeO
0:HasPropertyVariableRelativeGasFlowRate0:Float0:PropertyTypeO
0:HasPropertyVariableConsumedSensorCapacity0:Float0:PropertyTypeO
0:HasPropertyVariableRangeExceedancePeakValue0:Float0:PropertyTypeO
0:HasPropertyVariableRangeExceedanceDuration0: Duration0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualSensitivity0:Float0:PropertyTypeO
Conformance Units
PA-DIM AmperometricGasDetectorSignalType
PA-DIM AmperometricGasDetectorSignalType SensorNextCalibrationFixed
PA-DIM AmperometricGasDetectorSignalType SensorNextCalibrationDynamic
PA-DIM AmperometricGasDetectorSignalType PowerOnDurationSensor
PA-DIM AmperometricGasDetectorSignalType SensingElementResidualLife
PA-DIM AmperometricGasDetectorSignalType RelativeGasFlowRate
PA-DIM AmperometricGasDetectorSignalType ConsumedSensorCapacity
PA-DIM AmperometricGasDetectorSignalType RangeExceedance
PA-DIM AmperometricGasDetectorSignalType SensingElementResidualSensitivity

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

SensorNextCalibrationFixed is defined by IRDI as ABQ016#001 which states "time expressed in days that can elapse until the next calibration, calculated from the configured calibration interval".

SensorNextCalibrationDynamic is defined by IRDI as ABQ017#001 which states "time expressed in days that can elapse until the next calibration, estimated from operational or historical information".

PowerOnDurationSensor is defined by IRDI as ABQ010#001 which states "summed duration of time intervals for which the sensor was in an operating powered state".

SensingElementResidualLife is defined by IRDI as ABP584#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad)".

RelativeGasFlowRate is defined by IRDI as ABQ011#001 which states "flow rate of gas expressed as a value between 100 (good) and 0 (bad)".

ConsumedSensorCapacity is defined by IRDI as ABQ018#001 which states "accumulated gas dosage expressed in concentration multiplied by time of exposure".

RangeExceedancePeakValue is defined by IRDI as ABQ019#001 which states "extrapolated maximum gas concentration upon overload".

RangeExceedanceDuration is defined by IRDI as ABQ020#001 which states "accumulated duration of measurement time in overload condition".

SensingElementResidualSensitivity is defined by IRDI as ABQ040#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad) calculated during its calibration".

The components of IAmperometricGasDetectorSignalConditionSetType have additional references which are defined in Table 86.

Table 86 - IAmperometricGasDetectorSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SensingElementTemperature 0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SensorNextCalibrationFixed0:HasDictionaryEntryTrue3:0112/2///61987#ABQ016#001
SensorNextCalibrationDynamic0:HasDictionaryEntryTrue3:0112/2///61987#ABQ017#001
PowerOnDurationSensor0:HasDictionaryEntryTrue3:0112/2///61987#ABQ010#001
SensingElementResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABP584#001
RelativeGasFlowRate0:HasDictionaryEntryTrue3:0112/2///61987#ABQ011#001
ConsumedSensorCapacity0:HasDictionaryEntryTrue3:0112/2///61987#ABQ018#001
RangeExceedancePeakValue0:HasDictionaryEntryTrue3:0112/2///61987#ABQ019#001
RangeExceedanceDuration0:HasDictionaryEntryTrue3:0112/2///61987#ABQ020#001
SensingElementResidualSensitivity0:HasDictionaryEntryTrue3:0112/2///61987#ABQ040#001

The child Nodes of the IAmperometricGasDetectorSignalConditionSetType have additional Attribute values defined in Table 87.

Table 87 - IAmperometricGasDetectorSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SensingElementTemperature 0
SensorNextCalibrationFixed0
SensorNextCalibrationDynamic0
PowerOnDurationSensor0
SensingElementResidualLife1
RelativeGasFlowRate0
ConsumedSensorCapacity0
RangeExceedancePeakValue0
RangeExceedanceDuration0
SensingElementResidualSensitivity1

7.1.26 IOpticalFluorescenseQuenchingSignalConditionSetType

The IOpticalFluorescenseQuenchingSignalConditionSetType provides the interface to optical fluorescence quenching measurement signal specific condition variables and is formally defined in Table 88.

Table 88 - IOpticalFluorescenseQuenchingSignalConditionSetType definition
AttributeValue
BrowseNameIOpticalFluorescenseQuenchingSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorNextCalibration0:UInt320:AnalogUnitTypeO
0:HasPropertyVariableSensorCleaningsCounter0:UInt320:PropertyTypeO
0:HasPropertyVariableSensorSterilisationsCounter0:UInt320:PropertyTypeO
Conformance Units
PA-DIM OpticalFluorescenseQuenchingSignalType
PA-DIM OpticalFluorescenseQuenchingSignalType SensorNextCalibration
PA-DIM OpticalFluorescenseQuenchingSignalType SensorCleaningsCounter
PA-DIM OpticalFluorescenseQuenchingSignalType SensorSterilisationsCounter

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

SensorNextCalibration is defined by IRDI as ABP566#001 which states "time that can elapse until the next calibration, calculated from the configured calibration interval or estimated by the device".

SensorCleaningsCounter is defined by IRDI as ABP546#001 which states "number of times a sensor has been cleaned in place".

SensorSterilisationsCounter is defined by IRDI as ABP547#001 which states "number of times a sensor has been sterilized in place".

The components of IOpticalFluorescenseQuenchingSignalConditionSetType have additional references which are defined in Table 89.

Table 89 - IOpticalFluorescenseQuenchingSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SensingElementTemperature
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorNextCalibration0:HasDictionaryEntryTrue3:0112/2///61987#ABP566#001
SensorNextCalibration
0:EngineeringUnits

0:HasDictionaryEntryTrue3:0112/2///61987#ABA968#004
SensorCleaningsCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABP546#001
SensorSterilisationsCounter0:HasDictionaryEntryTrue3:0112/2///61987#ABP547#001

The child Nodes of the IOpticalFluorescenseQuenchingSignalConditionSetType have additional Attribute values defined in Table 90.

Table 90 - IOpticalFluorescenseQuenchingSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SensingElementTemperature0.0
SensingElementTemperature
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C

Description: degree Celsius

SensorNextCalibration0
SensorNextCalibration
0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705745431
DisplayName: d
Description: day
SensorCleaningsCounter0
SensorSterilisationsCounter0

7.1.27 IGasChromatographSignalConditionSetType

The IGasChromatographSignalConditionSetType provides the interface to gaschromatograph measurement signal specific condition variables and is formally defined in Table 91

Table 91 - IGasChromatographSignalConditionSetType definition
AttributeValue
BrowseNameIGasChromatographSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariablePeakWidth0:Float0:AnalogUnitTypeO
0:HasComponentVariablePeakHeight0:Float0:AnalogUnitTypeO
0:HasComponentVariablePeakArea0:Float0:AnalogUnitTypeO
0:HasPropertyVariableTailingFactor0:Float0:PropertyTypeO
0:HasComponentVariableExpectedRetentionTime0:Float0:AnalogUnitTypeO
0:HasComponentVariableActualRetentionTime0:Float0:AnalogUnitTypeO
0:HasPropertyVariableInjectionTime0:DateTime0:PropertyTypeO
0:HasPropertyVariableComponentName0:String0:PropertyTypeO
Conformance Units
PA-DIM GasChromatographSignalType
PA-DIM GasChromatographSignalType Peak
PA-DIM GasChromatographSignalType RetentionTime
PA-DIM GasChromatographSignalType InjectionTime
PA-DIM GasChromatographSignalType ComponentName

PeakWidth is defined by IRDI as ABQ022#001 which states "width of a chromatogram peak in time units, measured at 10% of peak height".

PeakHeight is defined by IRDI as ABQ023#001 which states "magnitude of a Process GC output signal in units defined by the manufacturer, measured from the peak tip perpendicular to the baseline".

PeakArea is defined by IRDI as ABQ042#001 which states "integral of the area under the output peak of a chromatogram signal in units defined by the manufacturer".

TailingFactor is defined by IRDI as ABQ033#001 which states "asymmetry of a substance peak in a chromatogram expressed as the ratio of the back part to the front part of the peak, referred to the peak maximum, at 10 % peak height above the baseline".

ExpectedRetentionTime is defined by IRDI as ABQ034#001 which states "anticipated time a component needs between injection into the column and detection of the peak".

ActualRetentionTime is defined by IRDI as ABQ035#001 which states "measured time a component needs between injection into the column and detection of the peak".

InjectionTime is defined by IRDI as ABQ006#001 which states "time stamp of sample injection to the chromatograph".

ComponentName is defined by IRDI as ABQ045#001 which states "name of the medium".

The components of IGasChromatographSignalConditionSetType have additional references which are defined in Table 92.

Table 92 - IGasChromatographSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
PeakWidth0:HasDictionaryEntryTrue3:0112/2///61987#ABQ022#001
PeakHeight0:HasDictionaryEntryTrue3:0112/2///61987#ABQ023#001
PeakArea0:HasDictionaryEntryTrue3:0112/2///61987#ABQ042#001
TailingFactor0:HasDictionaryEntryTrue3:0112/2///61987#ABQ033#001
ExpectedRetentionTime0:HasDictionaryEntryTrue3:0112/2///61987#ABQ034#001
ActualRetentionTime0:HasDictionaryEntryTrue3:0112/2///61987#ABQ035#001
InjectionTime0:HasDictionaryEntryTrue3:0112/2///61987#ABQ006#001
ComponentName0:HasDictionaryEntryTrue3:0112/2///61987#ABQ045#001

The child Nodes of the IGasChromatographSignalConditionSetType have additional Attribute values defined in Table 93.

Table 93 - IGasChromatographSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
PeakWidth0
PeakHeight0
PeakArea0
TailingFactor1.0
ExpectedRetentionTime0
ActualRetentionTime0
InjectionTime1/1/1601 12:00:00 AM
ComponentName

7.1.28 IFtnirOrFtirSignalConditionSetType

The IFtnirOrFtirSignalConditionSetTypeprovides the interface to FT NIR or FT IR signal specific condition variables and is formally defined in Table 94

Table 94 - IFtnirOrFtirSignalConditionSetType definition
AttributeValue
BrowseNameIFtnirOrFtirSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableTransmissionRatio0:Float0:DataItemTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasPropertyVariableMahalanobisDistance0:Float0:PropertyTypeO
0:HasPropertyVariableSpectralResidual0:Float0:PropertyTypeO
0:HasPropertyVariableElectronicsReadNoise0:Float0:PropertyTypeO
0:HasPropertyVariableLaserResidualLife0:Float0:PropertyTypeO
Conformance Units
PA-DIM FtnirOrFtirSignalType
PA-DIM FtnirOrFtirSignalType TransmissionRatio
PA-DIM FtnirOrFtirSignalType MahalanobisDistance
PA-DIM FtnirOrFtirSignalType SpectralResidual
PA-DIM FtnirOrFtirSignalType ElectronicsReadNoise
PA-DIM FtnirOrFtirSignalType LaserResidualLife

TransmissionRatio is defined by IRDI as ABP582#001 which states "ratio of the value of a specified radiation quantity in the centre of a beam of specified radiation quality and under specified geometrical conditions after passage through a material to the value which would be present at the same position without this material in the beam".

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

MahalanobisDistance is defined by IRDI as ABQ037#001 which states "measure of the distance between a point P and a distribution D".

SpectralResidual is defined by IRDI as ABQ038#001 which states "difference between the actual data and the data reconstructed by factor decomposition".

ElectronicsReadNoise is defined by IRDI as ABQ057#001 which states "total dark noise of the detector and spectrometer electronics, measured relative to the dynamic range of the spectrometer".

LaserResidualLife is defined by IRDI as ABQ044#001 which states "degradation of a laser expressed as a value between 1 (good) and 0 (bad)".

The components of IFtnirOrFtirSignalConditionSetType have additional references which are defined in Table 95.

Table 95 - IFtnirOrFtirSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
TransmissionRatio0:HasDictionaryEntryTrue3:0112/2///61987#ABP582#001
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
MahalanobisDistance0:HasDictionaryEntryTrue3:0112/2///61987#ABQ037#001
SpectralResidual0:HasDictionaryEntryTrue3:0112/2///61987#ABQ038#001
ElectronicsReadNoise0:HasDictionaryEntryTrue3:0112/2///61987#ABQ057#001
LaserResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABQ044#001

The child Nodes of the IFtnirOrFtirSignalConditionSetType have additional Attribute values defined in Table 96.

Table 96 - IFtnirOrFtirSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
TransmissionRatio0.0
SensingElementTemperature0.0
MahalanobisDistance0.0
SpectralResidual0.0
ElectronicsReadNoise0.0
LaserResidualLife1.0

7.1.29 IDiodeArraySignalConditionSetType

The IDiodeArraySignalConditionSetType provides the interface to Diode Array signal specific condition variables and is formally defined in Table 97

Table 97 - IDiodeArraySignalConditionSetType definition
AttributeValue
BrowseNameIDiodeArraySignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasPropertyVariableMahalanobisDistance0:Float0:PropertyTypeO
0:HasPropertyVariableSpectralResidual0:Float0:PropertyTypeO
0:HasPropertyVariableElectronicsReadNoise0:Float0:PropertyTypeO
Conformance Units
PA-DIM DiodeArraySignalType
PA-DIM DiodeArraySignalType SourceResidualLife
PA-DIM DiodeArraySignalType MahalanobisDistance
PA-DIM DiodeArraySignalType SpectralResidual
PA-DIM DiodeArraySignalType ElectronicsReadNoise

SourceResidualLife is defined by IRDI as ABP552#001 which states "degradation of a radiation source expressed as a value between 1 (good) and 0 (bad)".

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

MahalanobisDistance is defined by IRDI as ABQ037#001 which states "measure of the distance between a point P and a distribution D".

SpectralResidual is defined by IRDI as ABQ038#001 which states "difference between the actual data and the data reconstructed by factor decomposition".

The components of IDiodeArraySignalConditionSetType have additional references which are defined in Table 98.

Table 98 - IDiodeArraySignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SourceResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABP552#001
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
MahalanobisDistance0:HasDictionaryEntryTrue3:0112/2///61987#ABQ037#001
SpectralResidual0:HasDictionaryEntryTrue3:0112/2///61987#ABQ038#001
ElectronicsReadNoise0:HasDictionaryEntryTrue3:0112/2///61987#ABQ057#001

The child Nodes of the IFtnirOrFtirSignalConditionSetType have additional Attribute values defined in Table 99.

Table 99 - IDiodeArraySignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SourceResidualLife1.0
SensingElementTemperature0
MahalanobisDistance0
SpectralResidual0
ElectronicsReadNoise0

7.1.30 IRamanSignalConditionSetType

The IRamanSignalConditionSetTypeprovides the interface to Raman signal specific condition variables and is formally defined in Table 100

Table 100 - IRamanSignalConditionSetType definition
AttributeValue
BrowseNameIRamanSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasPropertyVariableMahalanobisDistance0:Float0:PropertyTypeO
0:HasPropertyVariableSpectralResidual0:Float0:PropertyTypeO
0:HasPropertyVariableElectronicsReadNoise0:Float0:PropertyTypeO
Conformance Units
PA-DIM RamanSignalType
PA-DIM RamanSignalType SourceResidualLife
PA-DIM RamanSignalType SensingElementTemperature
PA-DIM RamanSignalType MahalanobisDistance
PA-DIM RamanSignalType SpectralResidual
PA-DIM RamanSignalType ElectronicsReadNoise

TransmissionRatio is defined by IRDI as ABP582#001 which states "ratio of the value of a specified radiation quantity in the centre of a beam of specified radiation quality and under specified geometrical conditions after passage through a material to the value which would be present at the same position without this material in the beam".

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

MahalanobisDistance is defined by IRDI as ABQ037#001 which states "measure of the distance between a point P and a distribution D".

SpectralResidual is defined by IRDI as ABQ038#001 which states "difference between the actual data and the data reconstructed by factor decomposition".

ElectronicsReadNoise is defined by IRDI as ABQ057#001 which states "total dark noise of the detector and spectrometer electronics, measured relative to the dynamic range of the spectrometer".

The components of IRamanSignalConditionSetType have additional references which are defined in Table 101.

Table 101 - IRamanSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SourceResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABP552#001
SensingElementTemperature0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
MahalanobisDistance0:HasDictionaryEntryTrue3:0112/2///61987#ABQ037#001
SpectralResidual0:HasDictionaryEntryTrue3:0112/2///61987#ABQ038#001
ElectronicsReadNoise0:HasDictionaryEntryTrue3:0112/2///61987#ABQ057#001

The child Nodes of the IFtnirOrFtirSignalConditionSetType have additional Attribute values defined in Table 102.

Table 102 - IRamanSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SourceResidualLife1.0
SensingElementTemperature0.0
MahalanobisDistance0.0
SpectralResidual0.0
ElectronicsReadNoise0.0

7.1.31 IInfraredSignalConditionSetType

The IInfraredSignalConditionSetType provides the interface to Infrared signal specific condition variables and is formally defined in Table 103

Table 103 - IInfraredSignalConditionSetType definition
AttributeValue
BrowseNameIInfraredSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature 0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
0:HasPropertyVariableTransmissionRatio0:Float0:PropertyTypeO
0:HasPropertyVariableSensorNextCalibrationFixed0:Float0:PropertyTypeO
0:HasPropertyVariableSensorNextCalibrationDynamic0:Float0:PropertyTypeO
0:HasPropertyVariablePowerOnDurationSensor0: Duration0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualLife0:Float0:PropertyTypeO
0:HasPropertyVariableRelativeGasFlowRate0:Float0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualSensitivity0:Float0:PropertyTypeO
Conformance Units
PA-DIM InfraredSignalType
PA-DIM InfraredSignalType SourceResidualLife
PA-DIM InfraredSignalType TransmissionRatio
PA-DIM InfraredSignalType SensorNextCalibrationFixed
PA-DIM InfraredSignalType SensorNextCalibrationDynamic
PA-DIM InfraredSignalType PowerOnDurationSensor
PA-DIM InfraredSignalType SensingElementResidualLife

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

SourceResidualLife is defined by IRDI as ABQ041#001 which states "degradation of an infrared radiation source expressed as a value between 1 (good) and 0 (bad)".

TransmissionRatio is defined by IRDI as ABP582#001 which states "ratio of the value of a specified radiation quantity in the centre of a beam of specified radiation quality and under specified geometrical conditions after passage through a material to the value which would be present at the same position without this material in the beam".

SensorNextCalibrationFixed is defined by IRDI as ABQ016#001 which states "time expressed in days that can elapse until the next calibration, calculated from the configured calibration interval".

SensorNextCalibrationDynamic is defined by IRDI as ABQ017#001 which states "time expressed in days that can elapse until the next calibration, estimated from operational or historical information".

PowerOnDurationSensor is defined by IRDI as ABQ010#001 which states "summed duration of time intervals for which the sensor was in an operating powered state".

SensingElementResidualLife is defined by IRDI as ABQ040#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad) calculated during its calibration".

RelativeGasFlowRate is defined by IRDI as ABQ011#001 which states "flow rate of gas expressed as a value between 100 (good) and 0 (bad)".

SensingElementResidualSensitivity is defined by IRDI as ABQ040#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad) calculated during its calibration".

The components of IInfraredSignalConditionSetType have additional references which are defined in Table 104.

Table 104 - IInfraredSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SensingElementTemperature 0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SourceResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABQ041#001
TransmissionRatio0:HasDictionaryEntryTrue3:0112/2///61987#ABP582#001
SensorNextCalibrationFixed0:HasDictionaryEntryTrue3:0112/2///61987#ABQ016#001
SensorNextCalibrationDynamic0:HasDictionaryEntryTrue3:0112/2///61987#ABQ017#001
PowerOnDurationSensor0:HasDictionaryEntryTrue3:0112/2///61987#ABQ010#001
SensingElementResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABP584#001
RelativeGasFlowRate0:HasDictionaryEntryTrue3:0112/2///61987#ABQ011#001
SensingElementResidualSensitivity0:HasDictionaryEntryTrue3:0112/2///61987#ABQ040#001

The child Nodes of the IInfraredSignalConditionSetType have additional Attribute values defined in Table 105.

Table 105 - IInfraredSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SensingElementTemperature 0
SourceResidualLife1.0
TransmissionRatio0
SensorNextCalibrationFixed0
SensorNextCalibrationDynamic0
PowerOnDurationSensor0
SensingElementResidualLife1.0
RelativeGasFlowRate0
SensingElementResidualSensitivity1.0

7.1.32 ICatalyticBeadSignalConditionSetType

The I CatalyticBeadSignalConditionSetType provides the interface to Catalytic Bead signal specific condition variables and is formally defined in Table 106

Table 106 - ICatalyticBeadSignalConditionSetType definition
AttributeValue
BrowseNameICatalyticBeadSignalConditionSetType
IsAbstractTrue
ReferencesNodeClassBrowseNameDataTypeTypeDefinitionOther
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature 0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorNextCalibrationFixed0:Float0:PropertyTypeO
0:HasPropertyVariableSensorNextCalibrationDynamic0:Float0:PropertyTypeO
0:HasPropertyVariablePowerOnDurationSensor0:Duration0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualLife0:Float0:PropertyTypeO
0:HasPropertyVariableRelativeGasFlowRate0:Float0:PropertyTypeO
0:HasComponentVariableSensorValue0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensingElementResidualSensitivity0:Float0:PropertyTypeO
Conformance Units
PA-DIM CatalyticBeadSignalType
PA-DIM CatalyticBeadSignalType SensorNextCalibrationFixed
PA-DIM CatalyticBeadSignalType SensorNextCalibrationDynamic
PA-DIM CatalyticBeadSignalType PowerOnDurationSensor
PA-DIM CatalyticBeadSignalType SensingElementResidualLife
PA-DIM CatalyticBeadSignalType RelativeGasFlowRate
PA-DIM CatalyticBeadSignalType SensorValue
PA-DIM CatalyticBeadSignalType SensingElementResidualSensitivity

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

SensorNextCalibrationFixed is defined by IRDI as ABQ016#001 which states "time expressed in days that can elapse until the next calibration, calculated from the configured calibration interval".

SensorNextCalibrationDynamic is defined by IRDI as ABQ017#001 which states "time expressed in days that can elapse until the next calibration, estimated from operational or historical information".

PowerOnDurationSensor is defined by IRDI as ABQ010#001 which states "summed duration of time intervals for which the sensor was in an operating powered state".

SensingElementResidualLife is defined by IRDI as ABP584#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad)".

RelativeGasFlowRate is defined by IRDI as ABQ011#001 which states "flow rate of gas expressed as a value between 100 (good) and 0 (bad)".

SensingValue is defined by IRDI as ABQ021#001 which states "measured voltage across the Wheatstone bridge upon calibration".

SensingElementResidualSensitivity is defined by IRDI as ABQ040#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad) calculated during its calibration".

The components of ICatalyticBeadSignalType SignalConditionSetType have additional references which are defined in Table 107.

Table 107 - ICatalyticBeadSignalConditionSetType additional References
SourceBrowsePathReference TypeIs ForwardTargetBrowsePath
SensingElementTemperature 0:HasDictionaryEntryTrue3:0112/2///61987#ABP565#001
SensorNextCalibrationFixed0:HasDictionaryEntryTrue3:0112/2///61987#ABQ016#001
SensorNextCalibrationDynamic0:HasDictionaryEntryTrue3:0112/2///61987#ABQ017#001
PowerOnDurationSensor0:HasDictionaryEntryTrue3:0112/2///61987#ABQ010#001
SensingElementResidualLife0:HasDictionaryEntryTrue3:0112/2///61987#ABP584#001
RelativeGasFlowRate0:HasDictionaryEntryTrue3:0112/2///61987#ABQ011#001
SensorValue0:HasDictionaryEntryTrue3:0112/2///61987#ABQ021#001
SensingElementResidualSensitivity0:HasDictionaryEntryTrue3:0112/2///61987#ABQ040#001

The child Nodes of the IAmperometricGasDetectorSignalConditionSetType have additional Attribute values defined in Table 108.

Table 108 - ICatalyticBeadSignalConditionSetType Attribute values for child Nodes
BrowsePathValue Attribute
SensingElementTemperature 0
SensorNextCalibrationFixed0
SensorNextCalibrationDynamic0
PowerOnDurationSensor0
SensingElementResidualLife1
RelativeGasFlowRate0
SensorValue0
SensingElementResidualSensitivity1