7.1 PA-DIM Interfaces

7.1.1 IAdministrationType

The IAdministrationType provides the interface to administration variables and methods of the device and is formally defined in Table 16.

Table 16 – IAdministrationType definition
Attribute Value
BrowseNameIAdministrationType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableDisplayLanguage0:LocaleId0:BaseDataVariableTypeO
0:HasComponentVariableDateOfLastChange0:DateTime0:BaseDataVariableTypeO
0:HasComponentMethodFactoryResetDefined in 9.1 O
Conformance Units
PA-DIM IAdmin DisplayLanguage
PA-DIM IAdmin DateOfChange
PA-DIM IAdmin FactoryReset

DisplayLanguage: is the language used for the local display of the device. ABN597#004 defines language or languages set on the display.

DateOfLastChange: ABN604#001 defines parameter indicating the date and time at which one of the device parameters was changed the last time.

FactoryReset: ABN609#002 property the value of which indicates the kind of reset function to be executed. Note: Properties can be variables or methods according IEC 61987 CDD.

The components of IAdministrationType have additional references which are defined in Table 17.

Table 17 – IAdministrationType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
DisplayLanguage0:HasDictionaryEntryTrue 3:0112/2///61987#ABN597#004
DateOfLastChange0:HasDictionaryEntryTrue 3:0112/2///61987#ABN604#001
FactoryReset0:HasDictionaryEntryTrue 3:0112/2///61987#ABN609#002

The child Nodes of the IAdministrationType have additional Attribute values defined in Table 18.

Table 18 – IAdministrationType Attribute values for child Nodes
BrowsePath Value Attribute
DisplayLanguageen
DateOfLastChange1/1/1601 12:00:00 AM

7.1.2 ISignalSetType

The ISignalSetType provides the interface to process variables of the device and is formally defined in Table 19.

Table 19 – ISignalSetType definition
Attribute Value
BrowseNameISignalSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentObjectSignalSetSignalSetTypeO
Conformance Units
PA-DIM ISignal

SignalSet is a container object for the process variables of the device.

7.1.3 ICalibrationType

The ICalibrationType provides the interface to calibration variables of the sensor resp. signal and is formally defined in Table 20.

Table 20 – ICalibrationType definition
Attribute Value
BrowseNameICalibrationType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableCalibrationTimestamp0:DateTime0:PropertyTypeO
0:HasComponentVariableTypeOfCalibration0:UInt320:MultiStateDictionaryEntryDiscreteTypeO
0:HasComponentObjectCalibrationPointSetCalibrationPointSetTypeO
Conformance Units
PA-DIM ICalibration
PA-DIM ICalibration CalibrationTimestamp
PA-DIM ICalibration TypeOfCalibration
PA-DIM ICalibration CalibrationPointSet

The components of ICalibrationType have additional references which are defined in Table 21.

Table 21 – ICalibrationType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
CalibrationTimestamp0:HasDictionaryEntryTrue 3:0112/2///61987#ABP544#001
TypeOfCalibration0:HasDictionaryEntryTrue 3:0112/2///61987#ABH609#002

The child Nodes of the ICalibrationType have additional Attribute values defined in Table 22.

Table 22 – ICalibrationType Attribute values for child Nodes
BrowsePath Value Attribute
CalibrationTimestamp1/1/1601 12:00:00 AM
TypeOfCalibration0
ns=3;s=0112/2///61987#ABP732#001
adjustment

7.1.4 IConductivityCalibrationType

The IConductivityCalibrationType provides the interface to conductivity measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 23.

Table 23 – IConductivityCalibrationType definition
Attribute Value
BrowseNameIConductivityCalibrationType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableConductivityCellConstant0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM PhSignalType

The components of IConductivityCalibrationType have additional references which are defined in Table 24.

Table 24 – IConductivityCalibrationType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
ConductivityCellConstant0:HasDictionaryEntryTrue 3:0112/2///61987#ABF161#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004

The child Nodes of the IConductivityCalibrationType have additional Attribute values defined in Table 25.

Table 25 – IConductivityCalibrationType Attribute values for child Nodes
BrowsePath Value Attribute
ConductivityCellConstant0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705744658
DisplayName: cm⁻¹
Description: reciprocal centimetre

7.1.5 IAmperometricCalibrationType

The IAmperometricCalibrationType provides the interface to amperometric measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 26.

Table 26 – IAmperometricCalibrationType definition
Attribute Value
BrowseNameIAmperometricCalibrationType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableAmperometricSensorSlope0:Float0:AnalogUnitTypeO
0:HasComponentVariableAmperometricSensorZeroPoint0:Float0:AnalogUnitTypeO
0:HasComponentVariableAbsoluteAirPressure0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorT900:Float0:PropertyTypeO
Conformance Units
PA-DIM AmperometricSignalType
PA-DIM IAmperometricCalibration AbsoluteAirPressure
PA-DIM IAmperometricCalibration SensorT90

The components of IAmperometricCalibrationType have additional references which are defined in Table 27.

Table 27 – IAmperometricCalibrationType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
AmperometricSensorSlope0:HasDictionaryEntryTrue 3:0112/2///61987#ABP572#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
AmperometricSensorZeroPoint0:HasDictionaryEntryTrue 3:0112/2///61987#ABP573#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
AbsoluteAirPressure0:HasDictionaryEntryTrue 3:0112/2///61987#ABP574#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorT900:HasDictionaryEntryTrue 3:0112/2///61987#ABP569#001

The child Nodes of the IAmperometricCalibrationType have additional Attribute values defined in Table 28.

Table 28 – IAmperometricCalibrationType Attribute values for child Nodes
BrowsePath Value Attribute
AmperometricSensorZeroPoint0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705750616
DisplayName: pA
Description: picoampere
AbsoluteAirPressure0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705746519
DisplayName: hPa
Description: hectopascal
SensorT900.0

7.1.6 IOpticalFluorescenseQuenchingCalibrationType

The IOpticalFluorescenseQuenchingCalibrationType provides the interface to optical fluorescence quenching measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 29.

Table 29 – IOpticalFluorescenseQuenchingCalibrationType definition
Attribute Value
BrowseNameIOpticalFluorescenseQuenchingCalibrationType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableOpticalFluorescenseQuenchingSensorSlope0:Float0:AnalogUnitTypeO
0:HasComponentVariableOpticalFluorescenseQuenchingSensorZeroPoint0:Float0:AnalogUnitTypeO
0:HasComponentVariableAbsoluteAirPressure0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorT900:Float0:PropertyTypeO
Conformance Units
PA-DIM OpticalFluorescenseQuenchingSignalType
PA-DIM IOpticalFluorescenseQuenchingCalibration AbsoluteAirPressure
PA-DIM IOpticalFluorescenseQuenchingCalibration SensorT90

The components of IOpticalFluorescenseQuenchingCalibrationType have additional references which are defined in Table 30.

Table 30 – IOpticalFluorescenseQuenchingCalibrationType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
OpticalFluorescenseQuenchingSensorSlope0:HasDictionaryEntryTrue 3:0112/2///61987#ABP586#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
OpticalFluorescenseQuenchingSensorZeroPoint0:HasDictionaryEntryTrue 3:0112/2///61987#ABP587#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
AbsoluteAirPressure0:HasDictionaryEntryTrue 3:0112/2///61987#ABP574#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorT900:HasDictionaryEntryTrue 3:0112/2///61987#ABP569#001

The child Nodes of the IOpticalFluorescenseQuenchingCalibrationType have additional Attribute values defined in Table 31.

Table 31 – IOpticalFluorescenseQuenchingCalibrationType Attribute values for child Nodes
BrowsePath Value Attribute
OpticalFluorescenseQuenchingSensorZeroPoint0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741621
DisplayName: µs
Description: microsecond
AbsoluteAirPressure0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705746519
DisplayName: hPa
Description: hectopascal
SensorT900.0

7.1.7 IGasChromatographCalibrationType

The IGasChromatographCalibrationType provides the interface to gaschromatograph measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 32.

Table 32 – IGasChromatographCalibrationTypedefinition
Attribute Value
BrowseNameIGasChromatographCalibrationType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableCalibrationRange1ResponseFactor0:Float0:PropertyTypeO
0:HasComponentVariableCalibrationRange1LowerRangeValue0:Float0:AnalogUnitTypeO
0:HasComponentVariableCalibrationRange1UpperRangeValue0:Float0:AnalogUnitTypeO
0:HasPropertyVariableCalibrationRange2ResponseFactor0:Float0:PropertyTypeO
0:HasComponentVariableCalibrationRange2LowerRangeValue0:Float0:AnalogUnitTypeO
0:HasComponentVariableCalibrationRange2UpperRangeValue0:Float0:AnalogUnitTypeO
0:HasPropertyVariableCalibrationRange3ResponseFactor0:Float0:PropertyTypeO
0:HasComponentVariableCalibrationRange3LowerRangeValue0:Float0:AnalogUnitTypeO
0:HasComponentVariableCalibrationRange3UpperRangeValue0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM GasChromatograph CalibrationRange1
PA-DIM GasChromatograph CalibrationRange2
PA-DIM GasChromatograph CalibrationRange3

CalibrationRange1ResponseFactor is defined by IRDI as ABQ024#001 which states "ratio between the concentration of a compound being analysed and the response of the detector to that compound for the calibration range 1".

CalibrationRange1LowerRangeValue is defined by IRDI as ABQ025#001 which states "volume concentration value assigned to the lower range end-value of calibration range 1".

CalibrationRange1UpperRangeValue is defined by IRDI as ABQ026#001 which states "volume concentration value assigned to the upper range end-value of calibration range 1".

CalibrationRange2ResponseFactor is defined by IRDI as ABQ027#001 which states "ratio between the concentration of a compound being analysed and the response of the detector to that compound for the calibration range 2".

CalibrationRange2LowerRangeValue is defined by IRDI as ABQ028#001 which states "volume concentration value assigned to the lower range end-value of calibration range 2".

CalibrationRange2UpperRangeValue is defined by IRDI as ABQ029#001 which states "volume concentration value assigned to the upper range end-value of calibration range 2".

CalibrationRange3ResponseFactor is defined by IRDI as ABQ030#001 which states "ratio between the concentration of a compound being analysed and the response of the detector to that compound for the calibration range 3".

CalibrationRange3LowerRangeValue is defined by IRDI as ABQ031#001 which states "volume concentration value assigned to the lower range end-value of calibration range 3".

CalibrationRange3UpperRangeValue is defined by IRDI as ABQ032#001 which states "volume concentration value assigned to the upper range end-value of calibration range 3".

The components of IGasChromatographCalibrationType have additional references which are defined in Table 33.

Table 33 – IGasChromatographCalibrationType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
CalibrationRange1ResponseFactor0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ024#001
CalibrationRange1LowerRangeValue0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ025#001
CalibrationRange1UpperRangeValue0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ026#001
CalibrationRange2ResponseFactor0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ027#001
CalibrationRange2LowerRangeValue0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ028#001
CalibrationRange2UpperRangeValue0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ029#001
CalibrationRange3ResponseFactor0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ030#001
CalibrationRange3LowerRangeValue0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ031#001
CalibrationRange3UpperRangeValue0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ032#001

The child Nodes of the IGasChromatographCalibrationType have additional Attribute values defined in Table 34.

Table 34 – IGasChromatographCalibrationType Attribute values for child Nodes
BrowsePath Value Attribute
CalibrationRange1ResponseFactor1.0
CalibrationRange1LowerRangeValue0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange1UpperRangeValue100.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange2ResponseFactor1.0
CalibrationRange2LowerRangeValue0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange2UpperRangeValue100.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange3ResponseFactor1.0
CalibrationRange3LowerRangeValue0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

CalibrationRange3UpperRangeValue100.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705848917

DisplayName: ppm

Description: parts per million

7.1.8 IPhCalibrationType

The IPhCalibrationType provides the interface to pH measurement specific calibration variables of the sensor resp. signal and is formally defined in Error! Reference source not found..

Table 35 – IPhCalibrationType definition
Attribute Value
BrowseNameIPhCalibrationType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensorSlope0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorAsymmetryPotential0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorT900:Float0:PropertyTypeO
Conformance Units
PA-DIM PhSignalType
PA-DIM IPhCalibration SensorT90

The components of IPhCalibrationType have additional references which are defined in Table 36.

Table 36 – IPhCalibrationType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SensorSlope0:HasDictionaryEntryTrue 3:0112/2///61987#ABP567#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorAsymmetryPotential0:HasDictionaryEntryTrue 3:0112/2///61987#ABP568#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorT900:HasDictionaryEntryTrue 3:0112/2///61987#ABP569#001

The child Nodes of the IPhCalibrationType have additional Attribute values defined in Table 37.

Table 37 – IPhCalibrationType Attribute values for child Nodes
BrowsePath Value Attribute
SensorSlope0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749524
DisplayName: mV

Description: millivolt

SensorAsymmetryPotential0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749524

DisplayName: mV

Description: millivolt

SensorT900.0

7.1.9 IGeneralDeviceConditionSetType

The IGeneralDeviceConditionSetType provides the interface to condition variables of the device and its components and is formally defined in Table 38.

Table 38 – IGeneralDeviceConditionSetType definition
Attribute Value
BrowseNameIGeneralDeviceConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentObjectGeneralDeviceConditionsGeneralDeviceConditionSetTypeO
0:HasComponentObjectDeviceComponentConditions0:BaseObjectTypeO
Conformance Units
PA-DIM IGeneralDeviceConditionSet
PA-DIM IGeneralDeviceConditionSet DeviceComponentConditions
Table 39 – IGeneralDeviceConditionSetType additional subcomponents
BrowsePath References NodeClass BrowseName DataType TypeDefinition Other
DeviceComponentConditions0:HasComponentObject<DeviceComponentIdentifier>GeneralDeviceConditionSetTypeOP

<DeviceComponentIdentifier> is an optional placeholder for an object containing the condition variables related to a specific device component.

7.1.10 ITocDeviceConditionSetType

The ITocDeviceConditionSetType provides the interface to TOC device specific condition variables and is formally defined in Table 40.

Table 40 – ITocDeviceConditionSetType definition
Attribute Value
BrowseNameITocDeviceConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableCarrierGasVolumeFlow0:Float0:AnalogUnitTypeO
0:HasComponentVariableCarrierGasGaugePressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableReactorTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleWaterVolumeFlow0:Float0:AnalogUnitTypeO
0:HasComponentVariableReferenceInjectionVolume0:Float0:AnalogUnitTypeO
0:HasComponentVariableActualInjectedVolume0:Float0:AnalogUnitTypeO
0:HasComponentVariableCoolerTemperature0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM TocAnalyserType
PA-DIM TocAnalyserType CarrierGasGaugePressure
PA-DIM TocAnalyserType SampleWaterVolumeFlow
PA-DIM TocAnalyserType ActualInjectedVolume

The components of ITocDeviceConditionSetType have additional references which are defined in Table 41.

Table 41 – ITocDeviceConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
CarrierGasVolumeFlow0:HasDictionaryEntryTrue 3:0112/2///61987#ABP558#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
CarrierGasGaugePressure0:HasDictionaryEntryTrue 3:0112/2///61987#ABP559#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
ReactorTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP554#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SampleWaterVolumeFlow0:HasDictionaryEntryTrue 3:0112/2///61987#ABP561#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
ReferenceInjectionVolume0:HasDictionaryEntryTrue 3:0112/2///61987#ABP563#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
ActualInjectedVolume0:HasDictionaryEntryTrue 3:0112/2///61987#ABP564#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
CoolerTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP555#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004

The child Nodes of the ITocDeviceConditionSetType have additional Attribute values defined in Table 42.

Table 42 – ITocDeviceConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
CarrierGasVolumeFlow0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705747637
DisplayName: l/h
Description: litre per hour
CarrierGasGaugePressure0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
ReactorTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SampleWaterVolumeFlow0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749685
DisplayName: ml/min

Description: millilitre per minute

ReferenceInjectionVolume0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705749652
DisplayName: ml

Description: millilitre

ActualInjectedVolume0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705749652
DisplayName: ml

Description: millilitre

CoolerTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius

7.1.11 IFlameIonisationDeviceConditionSetType

The IFlameIonisationDeviceConditionSetType provides the interface to FID specific condition variables and is formally defined in Table 43.

Table 43 – IFlameIonisationDeviceConditionSetType definition
Attribute Value
BrowseNameIFlameIonisationDeviceConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableCatalystTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableFuelGasPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableCombustionAirPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableBlockTemperature0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM FlameIonisationDetectorType CatalystTemperature
PA-DIM FlameIonisationDetectorType FuelGasPressure
PA-DIM FlameIonisationDetectorType CombustionAirPressure
PA-DIM FlameIonisationDetectorType BlockTemperature

The components of IFlameIonisationDeviceConditionSetType have additional references which are defined in Table 44.

Table 44 – IFlameIonisationDeviceConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
CatalystTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP576#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
FuelGasPressure0:HasDictionaryEntryTrue 3:0112/2///61987#ABP578#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
CombustionAirPressure0:HasDictionaryEntryTrue 3:0112/2///61987#ABP579#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
BlockTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP577#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004

The child Nodes of the IFlameIonisationDeviceConditionSetType have additional Attribute values defined in Table 45.

Table 45 – IFlameIonisationDeviceConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
CatalystTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
FuelGasPressure0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
CombustionAirPressure0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
BlockTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius

7.1.12 IGasChromatographDeviceConditionSetType

The IGasChromatographDeviceConditionSetType provides the interface to gas chromatograph device specific condition variables and is formally defined in Table 46

Table 46 – IGasChromatographDeviceConditionSetType definition
Attribute Value
BrowseNameIGasChromatographDeviceConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableValveName0:LocalizedText[]0:PropertyTypeO
0:HasPropertyVariableValveSwitchingCyclesCounter0:UInt32[]0:PropertyTypeO
0:HasComponentVariableTotalAreaMeasuredPeaks0:Float0:AnalogUnitTypeO
0:HasComponentVariableBaselineNoise0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM GasChromatographType
PA-DIM GasChromatographType Valve
PA-DIM GasChromatographType TotalAreaMeasuredPeaks
PA-DIM GasChromatographType BaselineNoise

The components of IGasChromatographDeviceConditionSetType have additional references which are defined in Table 48.

Table 47 – IGasChromatographDeviceConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
ValveName0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ046#001
ValveSwitchingCyclesCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ007#001
TotalAreaMeasuredPeaks0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ043#001
BaselineNoise0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ036#001

The child Nodes of the IGasChromatographDeviceConditionSetType have additional Attribute values defined in Table 48.

Table 48 – IGasChromatographDeviceConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
TotalAreaMeasuredPeaks0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

BaselineNoise0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749524

DisplayName: mV
Description: millivolt

7.1.13 IFtnirOrFtirDeviceConditionSetType

The IFtnirOrFtirDeviceConditionSetType provides the interface to Fourier Transform Near-Infrared Spectroscopy or Fourier Transform Infrared Spectroscopy device specific condition variables and is formally defined in Table 49.

Table 49 – IFtnirOrFtirDeviceConditionSetType definition
Attribute Value
BrowseNameIFtnirOrFtirDeviceConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableWatchdog0:Boolean0:PropertyTypeO
0:HasPropertyVariableRemainingDataStorageCapacity0:Float0:PropertyTypeO
Conformance Units
PA-DIM FtnirOrFtirSpectrometerType
PA-DIM FtnirOrFtirSpectrometerType Watchdog
PA-DIM FtnirOrFtirSpectrometerType RemainingDataStorageCapacity

The components of IFtnirOrFtirDeviceConditionSetType have additional references which are defined in Table 50.

Table 50 – IFtnirOrFtirDeviceConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
Watchdog0:HasDictionaryEntryTrue 3:0112/2///61987#ABP996#002
RemainingDataStorageCapacity0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ039#001

The child Nodes of the IFtnirOrFtirDeviceConditionSetType have additional Attribute values defined in Table 51.

Table 51 – IFtnirOrFtirDeviceConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
RemainingDataStorageCapacity0.0

7.1.14 IDiodeArrayDeviceConditionSetType

The IDiodeArrayDeviceConditionSetType provides the interface to Diode array spectrometer device specific condition variables and is formally defined in Table 52.

Table 52 – IDiodeArrayDeviceConditionSetType definition
Attribute Value
BrowseNameIDiodeArrayDeviceConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableWatchdog0:Boolean0:PropertyTypeO
0:HasPropertyVariableRemainingDataStorageCapacity0:Float0:PropertyTypeO
Conformance Units
PA-DIM DiodeArraySpectrometerType
PA-DIM DiodeArraySpectrometerType Watchdog
PA-DIM DiodeArraySpectrometerType RemainingDataStorageCapacity

The components of IDiodeArrayDeviceConditionSetType have additional references which are defined in Table 53.

Table 53 – IDiodeArrayDeviceConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
Watchdog0:HasDictionaryEntryTrue 3:0112/2///61987#ABP996#002
RemainingDataStorageCapacity0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ039#001

The child Nodes of the IDiodeArrayDeviceConditionSetType have additional Attribute values defined in Table 54.

Table 54 – IDiodeArrayDeviceConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
RemainingDataStorageCapacity0.0

7.1.15 IRamanDeviceConditionSetType

The IRamanDeviceConditionSetType provides the interface to Raman spectrometer device specific condition variables and is formally defined in Table 55.

Table 55 – IRamanDeviceConditionSetType definition
Attribute Value
BrowseNameIRamanDeviceConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableWatchdog0:Boolean0:PropertyTypeO
0:HasPropertyVariableRemainingDataStorageCapacity0:Float0:PropertyTypeO
Conformance Units
PA-DIM RamanSpectrometerType
PA-DIM RamanSpectrometerType Watchdog
PA-DIM RamanSpectrometerType RemainingDataStorageCapacity

The components of IRamanDeviceConditionSetType have additional references which are defined in Table 56.

Table 56 – IRamanDeviceConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
Watchdog0:HasDictionaryEntryTrue 3:0112/2///61987#ABP996#002
RemainingDataStorageCapacity0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ039#001

The child Nodes of the IRamanDeviceConditionSetType have additional Attribute values defined in Table 57.

Table 57 – IRamanDeviceConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
RemainingDataStorageCapacity0.0

7.1.16 INonDispersiveInfraredSignalConditionSetType

The INonDispersiveInfraredSignalConditionSetType provides the interface to NDIR measurement signal specific condition variables and is formally defined in Table 58.

Table 58 – INonDispersiveInfraredSignalConditionSetType definition
Attribute Value
BrowseNameINonDispersiveInfraredSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableChopperFrequencyDeviation0:Float0:BaseAnalogTypeO
0:HasComponentVariableAbsoluteSampleGasPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleCellTemperature0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
Conformance Units
PA-DIM NonDispersiveInfraredSignalType ChopperFrequencyDeviation
PA-DIM NonDispersiveInfraredSignalType
PA-DIM NonDispersiveInfraredSignalType AbsoluteSampleGasPressure

The components of INonDispersiveInfraredSignalConditionSetType have additional references which are defined in Table 59.

Table 59 – INonDispersiveInfraredSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
ChopperFrequencyDeviation0:HasDictionaryEntryTrue 3:0112/2///61987#ABP553#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
AbsoluteSampleGasPressure0:HasDictionaryEntryTrue 3:0112/2///61987#ABP560#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SampleCellTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP556#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SourceResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABP552#001

The child Nodes of the INonDispersiveInfraredSignalConditionSetType have additional Attribute values defined in Table 60.

Table 60 – INonDispersiveInfraredSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
ChopperFrequencyDeviation0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

AbsoluteSampleGasPressure0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
SampleCellTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SourceResidualLife1.0

7.1.17 ITocSignalConditionSetType

The ITocSignalConditionSetType provides the interface to TOC measurement signal specific condition variables and is formally defined in Table 61.

Table 61 – ITocSignalConditionSetType definition
Attribute Value
BrowseNameITocSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableChopperFrequencyDeviation0:Float0:BaseAnalogTypeO
0:HasComponentVariableRelativeReagentLevel0:Float{Any}0:AnalogUnitTypeO
0:HasComponentVariableSampleCellTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableDetectorZeroSignal0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
0:HasComponentVariableAbsoluteSampleGasPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleGasVolumeFlow0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM TocSignalType
PA-DIM TocSignalType ChopperFrequencyDeviation
PA-DIM TocSignalType RelativeReagentLevel
PA-DIM TocSignalType AbsoluteSampleGasPressure
PA-DIM TocSignalType SampleGasVolumeFlow

The components of ITocSignalConditionSetType have additional references which are defined in Table 62.

Table 62 – ITocSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
ChopperFrequencyDeviation0:HasDictionaryEntryTrue 3:0112/2///61987#ABP553#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
RelativeReagentLevel0:HasDictionaryEntryTrue 3:0112/2///61987#ABP557#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SampleCellTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP556#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
DetectorZeroSignal0:HasDictionaryEntryTrue 3:0112/2///61987#ABP551#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SourceResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABP552#001
AbsoluteSampleGasPressure0:HasDictionaryEntryTrue 3:0112/2///61987#ABP560#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SampleGasVolumeFlow0:HasDictionaryEntryTrue 3:0112/2///61987#ABP562#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004

The child Nodes of the ITocSignalConditionSetType have additional Attribute values defined in Table 63.

Table 63 – ITocSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
ChopperFrequencyDeviation0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

RelativeReagentLevel0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

SampleCellTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
DetectorZeroSignal0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705848917

DisplayName: ppm

Description: parts per million

SourceResidualLife1.0
AbsoluteSampleGasPressure0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
SampleGasVolumeFlow0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705747637

DisplayName: l/h

Description: litre per hour

7.1.18 IParamagneticSignalConditionSetType

The IParamagneticSignalConditionSetType provides the interface to paramagnetic measurement signal specific condition variables and is formally defined in Table 64.

Table 64 – IParamagneticSignalConditionSetType definition
Attribute Value
BrowseNameIParamagneticSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSampleTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM ParamagneticSignalType

The components of IParamagneticSignalConditionSetType have additional references which are defined in Table 65.

Table 65 – IParamagneticSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SampleTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP575#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004

The child Nodes of the IParamagneticSignalConditionSetType have additional Attribute values defined in Table 66.

Table 66 – IParamagneticSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SampleTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SensingElementTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius

7.1.19 IThermalConductivitySignalConditionSetType

The IThermalConductivitySignalConditionSetType provides the interface to thermal conductivity measurement signal specific condition variables and is formally defined in Table 67.

Table 67 – IThermalConductivitySignalConditionSetType definition
Attribute Value
BrowseNameIThermalConductivitySignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSampleTemperature0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM ThermalConductivitySignalType

The components of IThermalConductivitySignalConditionSetType have additional references which are defined in Table 68.

Table 68 – IThermalConductivitySignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SampleTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP575#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004

The child Nodes of the IThermalConductivitySignalConditionSetType have additional Attribute values defined in Table 69.

Table 69 – IThermalConductivitySignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SampleTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius

7.1.20 ITunableDiodeLaserSignalConditionSetType

The ITunableDiodeLaserSignalConditionSetType provides the interface to TDL measurement signal specific condition variables and is formally defined in Table 70.

Table 70 – ITunableDiodeLaserSignalConditionSetType definition
Attribute Value
BrowseNameITunableDiodeLaserSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableAbsoluteSampleGasPressure0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableTransmissionRatio0:Float0:DataItemTypeO
0:HasComponentVariableSignalNoiseRatio0:Float0:DataItemTypeO
0:HasComponentVariableLaserTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSignalFitQuality0:Float0:DataItemTypeO
Conformance Units
PA-DIM TunableDiodeLaserSignalType
PA-DIM TunableDiodeLaserSignalType SignalFitQuality
PA-DIM TunableDiodeLaserSignalType SignalNoiseRatio
PA-DIM TunableDiodeLaserSignalType TransmissionRatio
PA-DIM TunableDiodeLaserSignalType LaserTemperature
PA-DIM TunableDiodeLaserSignalType AbsoluteSampleGasPressure

The components of ITunableDiodeLaserSignalConditionSetType have additional references which are defined in Table 71.

Table 71 – ITunableDiodeLaserSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
AbsoluteSampleGasPressure0:HasDictionaryEntryTrue 3:0112/2///61987#ABP560#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SampleTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP575#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
TransmissionRatio0:HasDictionaryEntryTrue 3:0112/2///61987#ABP582#001
SignalNoiseRatio0:HasDictionaryEntryTrue 3:0112/2///61987#ABP581#001
LaserTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP583#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SignalFitQuality0:HasDictionaryEntryTrue 3:0112/2///61987#ABP580#001

The child Nodes of the ITunableDiodeLaserSignalConditionSetType have additional Attribute values defined in Table 72.

Table 72 – ITunableDiodeLaserSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
AbsoluteSampleGasPressure0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705749552
DisplayName: mbar
Description: millibar
SampleTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
TransmissionRatio0.0
SignalNoiseRatio0.0
LaserTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SignalFitQuality0.0

7.1.21 IZirconiumDioxideSignalConditionSetType

The IZirconiumDioxideSignalConditionSetType provides the interface to Zirconium dioxide measurement signal specific condition variables and is formally defined in Table 73.

Table 73 – IZirconiumDioxideSignalConditionSetType definition
Attribute Value
BrowseNameIZirconiumDioxideSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableRelativeHeatOutput0:Float0:AnalogUnitTypeO
0:HasComponentVariableCellResistance0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensingElementResidualLife0:Float0:PropertyTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSampleGasVolumeFlow0:Float0:AnalogUnitTypeO
Conformance Units
PA-DIM ZirconiumDioxideSignalType
PA-DIM ZirconiumDioxideSignalType RelativeHeatOutput
PA-DIM ZirconiumDioxideSignalType CellResistance
PA-DIM ZirconiumDioxideSignalType SensingElementResidualLife
PA-DIM ZirconiumDioxideSignalType SampleGasVolumeFlow

The components of IZirconiumDioxideSignalConditionSetType have additional references which are defined in Table 74.

Table 74 – IZirconiumDioxideSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
RelativeHeatOutput0:HasDictionaryEntryTrue 3:0112/2///61987#ABP585#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
CellResistance0:HasDictionaryEntryTrue 3:0112/2///61987#ABP596#001
SensingElementResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABP584#001
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SampleGasVolumeFlow0:HasDictionaryEntryTrue 3:0112/2///61987#ABP562#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004

The child Nodes of the IZirconiumDioxideSignalConditionSetType have additional Attribute values defined in Table 75.

Table 75 – IZirconiumDioxideSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
RelativeHeatOutput0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741328

DisplayName: %

Description: percent

CellResistance0.0
SensingElementResidualLife1.0
SensingElementTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
SampleGasVolumeFlow0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705747637
DisplayName: l/h
Description: litre per hour

7.1.22 IPhSignalConditionSetType

The IPhSignalConditionSetType provides the interface to pH measurement signal specific condition variables and is formally defined in Table 76.

Table 76 – IPhSignalConditionSetType definition
Attribute Value
BrowseNameIPhSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariablePhMeasuringMethod0:UInt320:MultiStateDictionaryEntryDiscreteTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorNextCalibration0:UInt320:AnalogUnitTypeO
0:HasComponentVariableSensingElementImpedance0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorReferenceImpedance0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorCleaningsCounter0:UInt320:PropertyTypeO
0:HasPropertyVariableSensorSterilisationsCounter0:UInt320:PropertyTypeO
Conformance Units
PA-DIM PhSignalType
PA-DIM PhSignalType SensorNextCalibration
PA-DIM PhSignalType SensingElementImpedance
PA-DIM PhSignalType SensorReferenceImpedance
PA-DIM PhSignalType SensorCleaningsCounter
PA-DIM PhSignalType SensorSterilisationsCounter

The components of IPhSignalConditionSetType have additional references which are defined in Table 77.

Table 77 – IPhSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
PhMeasuringMethod0:HasDictionaryEntryTrue 3:0112/2///61987#ABP640#002
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorNextCalibration0:HasDictionaryEntryTrue 3:0112/2///61987#ABP566#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensingElementImpedance0:HasDictionaryEntryTrue 3:0112/2///61987#ABP570#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorReferenceImpedance0:HasDictionaryEntryTrue 3:0112/2///61987#ABP571#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorCleaningsCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABP546#001
SensorSterilisationsCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABP547#001

The child Nodes of the IPhSignalConditionSetType have additional Attribute values defined in Table 78.

Table 78 – IPhSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
PhMeasuringMethod0
ns=3;s=0112/2///61987#ABP718#001
glass electrode
SensingElementTemperature0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C

Description: degree Celsius

SensorNextCalibration0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705745431

DisplayName: d

Description: day

SensingElementImpedance0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741367

DisplayName: Ω

Description: ohm

SensorReferenceImpedance0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720

UnitId: 705741367

DisplayName: Ω

Description: ohm

SensorCleaningsCounter0
SensorSterilisationsCounter0

7.1.23 IConductivitySignalConditionSetType

The IConductivitySignalConditionSetType provides the interface to conductivity measurement signal specific condition variables and is formally defined in Table 79.

Table 79 – IConductivitySignalConditionSetType definition
Attribute Value
BrowseNameIConductivitySignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableConductivityMeasuringMethod0:UInt320:MultiStateDictionaryEntryDiscreteTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableTemperatureCompensationStyle0:UInt320:MultiStateDictionaryEntryDiscreteTypeO
0:HasPropertyVariableSensorCleaningsCounter0:UInt320:PropertyTypeO
0:HasPropertyVariableSensorSterilisationsCounter0:UInt320:PropertyTypeO
Conformance Units
PA-DIM PhSignalType
PA-DIM ConductivitySignalType SensorCleaningsCounter
PA-DIM ConductivitySignalType SensorSterilisationsCounter

The components of IConductivitySignalConditionSetType have additional references which are defined in Table 80.

Table 80 – IConductivitySignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
ConductivityMeasuringMethod0:HasDictionaryEntryTrue 3:0112/2///61987#ABP641#002
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
TemperatureCompensationStyle0:HasDictionaryEntryTrue 3:0112/2///61987#ABP642#002
SensorCleaningsCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABP546#001
SensorSterilisationsCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABP547#001

The child Nodes of the IConductivitySignalConditionSetType have additional Attribute values defined in Table 81.

Table 81 – IConductivitySignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
ConductivityMeasuringMethod0
ns=3;s=0112/2///61987#ABP721#001
inductive
SensingElementTemperature0.0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C
Description: degree Celsius
TemperatureCompensationStyle0
ns=3;s=0112/2///61987#ABP724#001
no temperature compensation
SensorCleaningsCounter0
SensorSterilisationsCounter0

7.1.24 IAmperometricSignalConditionSetType

The IAmperometricSignalConditionSetType provides the interface to amperometric measurement signal specific condition variables and is formally defined in Table 82.

Table 82 – IAmperometricSignalConditionSetType definition
Attribute Value
BrowseNameIAmperometricSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorNextCalibration0:UInt320:AnalogUnitTypeO
0:HasPropertyVariableSensorCleaningsCounter0:UInt320:PropertyTypeO
0:HasPropertyVariableSensorSterilisationsCounter0:UInt320:PropertyTypeO
Conformance Units
PA-DIM AmperometricSignalType
PA-DIM AmperometricSignalType SensorNextCalibration
PA-DIM AmperometricSignalType SensorCleaningsCounter
PA-DIM AmperometricSignalType SensorSterilisationsCounter

The components of IAmperometricSignalConditionSetType have additional references which are defined in Table 83.

Table 83 – IAmperometricSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorNextCalibration0:HasDictionaryEntryTrue 3:0112/2///61987#ABP566#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorCleaningsCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABP546#001
SensorSterilisationsCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABP547#001

The child Nodes of the IAmperometricSignalConditionSetType have additional Attribute values defined in Table 84.

Table 84 – IAmperometricSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SensingElementTemperature0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C

Description: degree Celsius

SensorNextCalibration0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705745431
DisplayName: d
Description: day
SensorCleaningsCounter0
SensorSterilisationsCounter0

7.1.25 IAmperometricGasDetectorSignalConditionSetType

The IAmperometricGasDetectorSignalConditionSetType provides the interface to Amperometric Electrochemical signal specific condition variables and is formally defined in Table 85

Table 85 – IAmperometricGasDetectorSignalConditionSetType definition
Attribute Value
BrowseNameIAmperometricGasDetectorSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature 0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorNextCalibrationFixed0:Float0:PropertyTypeO
0:HasPropertyVariableSensorNextCalibrationDynamic0:Float0:PropertyTypeO
0:HasPropertyVariablePowerOnDurationSensor0:Duration0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualLife0:Float0:PropertyTypeO
0:HasPropertyVariableRelativeGasFlowRate0:Float0:PropertyTypeO
0:HasPropertyVariableConsumedSensorCapacity0:Float0:PropertyTypeO
0:HasPropertyVariableRangeExceedancePeakValue0:Float0:PropertyTypeO
0:HasPropertyVariableRangeExceedanceDuration0: Duration0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualSensitivity0:Float0:PropertyTypeO
Conformance Units
PA-DIM AmperometricGasDetectorSignalType
PA-DIM AmperometricGasDetectorSignalType SensorNextCalibrationFixed
PA-DIM AmperometricGasDetectorSignalType SensorNextCalibrationDynamic
PA-DIM AmperometricGasDetectorSignalType PowerOnDurationSensor
PA-DIM AmperometricGasDetectorSignalType SensingElementResidualLife
PA-DIM AmperometricGasDetectorSignalType RelativeGasFlowRate
PA-DIM AmperometricGasDetectorSignalType ConsumedSensorCapacity
PA-DIM AmperometricGasDetectorSignalType RangeExceedance
PA-DIM AmperometricGasDetectorSignalType SensingElementResidualSensitivity

The components of IAmperometricGasDetectorSignalConditionSetType have additional references which are defined in Table 86.

Table 86 – IAmperometricGasDetectorSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SensingElementTemperature 0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
SensorNextCalibrationFixed0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ016#001
SensorNextCalibrationDynamic0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ017#001
PowerOnDurationSensor0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ010#001
SensingElementResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABP584#001
RelativeGasFlowRate0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ011#001
ConsumedSensorCapacity0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ018#001
RangeExceedancePeakValue0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ019#001
RangeExceedanceDuration0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ020#001
SensingElementResidualSensitivity0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ040#001

The child Nodes of the IAmperometricGasDetectorSignalConditionSetType have additional Attribute values defined in Table 87.

Table 87 – IAmperometricGasDetectorSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SensingElementTemperature 0
SensorNextCalibrationFixed0
SensorNextCalibrationDynamic0
PowerOnDurationSensor0
SensingElementResidualLife1
RelativeGasFlowRate0
ConsumedSensorCapacity0
RangeExceedancePeakValue0
RangeExceedanceDuration0
SensingElementResidualSensitivity1

7.1.26 IOpticalFluorescenseQuenchingSignalConditionSetType

The IOpticalFluorescenseQuenchingSignalConditionSetType provides the interface to optical fluorescence quenching measurement signal specific condition variables and is formally defined in Table 88.

Table 88 – IOpticalFluorescenseQuenchingSignalConditionSetType definition
Attribute Value
BrowseNameIOpticalFluorescenseQuenchingSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasComponentVariableSensorNextCalibration0:UInt320:AnalogUnitTypeO
0:HasPropertyVariableSensorCleaningsCounter0:UInt320:PropertyTypeO
0:HasPropertyVariableSensorSterilisationsCounter0:UInt320:PropertyTypeO
Conformance Units
PA-DIM OpticalFluorescenseQuenchingSignalType
PA-DIM OpticalFluorescenseQuenchingSignalType SensorNextCalibration
PA-DIM OpticalFluorescenseQuenchingSignalType SensorCleaningsCounter
PA-DIM OpticalFluorescenseQuenchingSignalType SensorSterilisationsCounter

The components of IOpticalFluorescenseQuenchingSignalConditionSetType have additional references which are defined in Table 89.

Table 89 – IOpticalFluorescenseQuenchingSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorNextCalibration0:HasDictionaryEntryTrue 3:0112/2///61987#ABP566#001
0:HasDictionaryEntryTrue 3:0112/2///61987#ABA968#004
SensorCleaningsCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABP546#001
SensorSterilisationsCounter0:HasDictionaryEntryTrue 3:0112/2///61987#ABP547#001

The child Nodes of the IOpticalFluorescenseQuenchingSignalConditionSetType have additional Attribute values defined in Table 90.

Table 90 – IOpticalFluorescenseQuenchingSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SensingElementTemperature0.0

NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705741427
DisplayName: °C

Description: degree Celsius

SensorNextCalibration0
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720
UnitId: 705745431
DisplayName: d
Description: day
SensorCleaningsCounter0
SensorSterilisationsCounter0

7.1.27 IGasChromatographSignalConditionSetType

The IGasChromatographSignalConditionSetType provides the interface to gaschromatograph measurement signal specific condition variables and is formally defined in Table 91

Table 91 – IGasChromatographSignalConditionSetType definition
Attribute Value
BrowseNameIGasChromatographSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariablePeakWidth0:Float0:AnalogUnitTypeO
0:HasComponentVariablePeakHeight0:Float0:AnalogUnitTypeO
0:HasComponentVariablePeakArea0:Float0:AnalogUnitTypeO
0:HasPropertyVariableTailingFactor0:Float0:PropertyTypeO
0:HasComponentVariableExpectedRetentionTime0:Float0:AnalogUnitTypeO
0:HasComponentVariableActualRetentionTime0:Float0:AnalogUnitTypeO
0:HasPropertyVariableInjectionTime0:DateTime0:PropertyTypeO
0:HasPropertyVariableComponentName0:String0:PropertyTypeO
Conformance Units
PA-DIM GasChromatographSignalType
PA-DIM GasChromatographSignalType Peak
PA-DIM GasChromatographSignalType RetentionTime
PA-DIM GasChromatographSignalType InjectionTime
PA-DIM GasChromatographSignalType ComponentName

The components of IGasChromatographSignalConditionSetType have additional references which are defined in Table 92.

Table 92 – IGasChromatographSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
PeakWidth0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ022#001
PeakHeight0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ023#001
PeakArea0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ042#001
TailingFactor0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ033#001
ExpectedRetentionTime0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ034#001
ActualRetentionTime0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ035#001
InjectionTime0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ006#001
ComponentName0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ045#001

The child Nodes of the IGasChromatographSignalConditionSetType have additional Attribute values defined in Table 93.

Table 93 – IGasChromatographSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
PeakWidth0
PeakHeight0
PeakArea0
TailingFactor1.0
ExpectedRetentionTime0
ActualRetentionTime0
InjectionTime1/1/1601 12:00:00 AM
ComponentName

7.1.28 IFtnirOrFtirSignalConditionSetType

The IFtnirOrFtirSignalConditionSetTypeprovides the interface to FT NIR or FT IR signal specific condition variables and is formally defined in Table 94

Table 94 – IFtnirOrFtirSignalConditionSetType definition
Attribute Value
BrowseNameIFtnirOrFtirSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableTransmissionRatio0:Float0:DataItemTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasPropertyVariableMahalanobisDistance0:Float0:PropertyTypeO
0:HasPropertyVariableSpectralResidual0:Float0:PropertyTypeO
0:HasPropertyVariableElectronicsReadNoise0:Float0:PropertyTypeO
0:HasPropertyVariableLaserResidualLife0:Float0:PropertyTypeO
Conformance Units
PA-DIM FtnirOrFtirSignalType
PA-DIM FtnirOrFtirSignalType TransmissionRatio
PA-DIM FtnirOrFtirSignalType MahalanobisDistance
PA-DIM FtnirOrFtirSignalType SpectralResidual
PA-DIM FtnirOrFtirSignalType ElectronicsReadNoise
PA-DIM FtnirOrFtirSignalType LaserResidualLife

The components of IFtnirOrFtirSignalConditionSetType have additional references which are defined in Table 95.

Table 95 – IFtnirOrFtirSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
TransmissionRatio0:HasDictionaryEntryTrue 3:0112/2///61987#ABP582#001
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
MahalanobisDistance0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ037#001
SpectralResidual0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ038#001
ElectronicsReadNoise0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ057#001
LaserResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ044#001

The child Nodes of the IFtnirOrFtirSignalConditionSetType have additional Attribute values defined in Table 96.

Table 96 – IFtnirOrFtirSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
TransmissionRatio0.0
SensingElementTemperature0.0
MahalanobisDistance0.0
SpectralResidual0.0
ElectronicsReadNoise0.0
LaserResidualLife1.0

7.1.29 IDiodeArraySignalConditionSetType

The IDiodeArraySignalConditionSetType provides the interface to Diode Array signal specific condition variables and is formally defined in Table 97

Table 97 – IDiodeArraySignalConditionSetType definition
Attribute Value
BrowseNameIDiodeArraySignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasPropertyVariableMahalanobisDistance0:Float0:PropertyTypeO
0:HasPropertyVariableSpectralResidual0:Float0:PropertyTypeO
0:HasPropertyVariableElectronicsReadNoise0:Float0:PropertyTypeO
Conformance Units
PA-DIM DiodeArraySignalType
PA-DIM DiodeArraySignalType SourceResidualLife
PA-DIM DiodeArraySignalType MahalanobisDistance
PA-DIM DiodeArraySignalType SpectralResidual
PA-DIM DiodeArraySignalType ElectronicsReadNoise

The components of IDiodeArraySignalConditionSetType have additional references which are defined in Table 98.

Table 98 – IDiodeArraySignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SourceResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABP552#001
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
MahalanobisDistance0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ037#001
SpectralResidual0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ038#001
ElectronicsReadNoise0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ057#001

The child Nodes of the IFtnirOrFtirSignalConditionSetType have additional Attribute values defined in Table 99.

Table 99 – IDiodeArraySignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SourceResidualLife1.0
SensingElementTemperature0
MahalanobisDistance0
SpectralResidual0
ElectronicsReadNoise0

7.1.30 IRamanSignalConditionSetType

The IRamanSignalConditionSetTypeprovides the interface to Raman signal specific condition variables and is formally defined in Table 100

Table 100 – IRamanSignalConditionSetType definition
Attribute Value
BrowseNameIRamanSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
0:HasComponentVariableSensingElementTemperature0:Float0:AnalogUnitTypeO
0:HasPropertyVariableMahalanobisDistance0:Float0:PropertyTypeO
0:HasPropertyVariableSpectralResidual0:Float0:PropertyTypeO
0:HasPropertyVariableElectronicsReadNoise0:Float0:PropertyTypeO
Conformance Units
PA-DIM RamanSignalType
PA-DIM RamanSignalType SourceResidualLife
PA-DIM RamanSignalType SensingElementTemperature
PA-DIM RamanSignalType MahalanobisDistance
PA-DIM RamanSignalType SpectralResidual
PA-DIM RamanSignalType ElectronicsReadNoise

The components of IRamanSignalConditionSetType have additional references which are defined in Table 101.

Table 101 – IRamanSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SourceResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABP552#001
SensingElementTemperature0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
MahalanobisDistance0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ037#001
SpectralResidual0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ038#001
ElectronicsReadNoise0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ057#001

The child Nodes of the IFtnirOrFtirSignalConditionSetType have additional Attribute values defined in Table 102.

Table 102 – IRamanSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SourceResidualLife1.0
SensingElementTemperature0.0
MahalanobisDistance0.0
SpectralResidual0.0
ElectronicsReadNoise0.0

7.1.31 IInfraredSignalConditionSetType

The IInfraredSignalConditionSetType provides the interface to Infrared signal specific condition variables and is formally defined in Table 103

Table 103 – IInfraredSignalConditionSetType definition
Attribute Value
BrowseNameIInfraredSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature 0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSourceResidualLife0:Float0:PropertyTypeO
0:HasPropertyVariableTransmissionRatio0:Float0:PropertyTypeO
0:HasPropertyVariableSensorNextCalibrationFixed0:Float0:PropertyTypeO
0:HasPropertyVariableSensorNextCalibrationDynamic0:Float0:PropertyTypeO
0:HasPropertyVariablePowerOnDurationSensor0: Duration0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualLife0:Float0:PropertyTypeO
0:HasPropertyVariableRelativeGasFlowRate0:Float0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualSensitivity0:Float0:PropertyTypeO
Conformance Units
PA-DIM InfraredSignalType
PA-DIM InfraredSignalType SourceResidualLife
PA-DIM InfraredSignalType TransmissionRatio
PA-DIM InfraredSignalType SensorNextCalibrationFixed
PA-DIM InfraredSignalType SensorNextCalibrationDynamic
PA-DIM InfraredSignalType PowerOnDurationSensor
PA-DIM InfraredSignalType SensingElementResidualLife

The components of IInfraredSignalConditionSetType have additional references which are defined in Table 104.

Table 104 – IInfraredSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SensingElementTemperature 0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
SourceResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ041#001
TransmissionRatio0:HasDictionaryEntryTrue 3:0112/2///61987#ABP582#001
SensorNextCalibrationFixed0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ016#001
SensorNextCalibrationDynamic0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ017#001
PowerOnDurationSensor0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ010#001
SensingElementResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABP584#001
RelativeGasFlowRate0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ011#001
SensingElementResidualSensitivity0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ040#001

The child Nodes of the IInfraredSignalConditionSetType have additional Attribute values defined in Table 105.

Table 105 – IInfraredSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SensingElementTemperature 0
SourceResidualLife1.0
TransmissionRatio0
SensorNextCalibrationFixed0
SensorNextCalibrationDynamic0
PowerOnDurationSensor0
SensingElementResidualLife1.0
RelativeGasFlowRate0
SensingElementResidualSensitivity1.0

7.1.32 ICatalyticBeadSignalConditionSetType

The I CatalyticBeadSignalConditionSetType provides the interface to Catalytic Bead signal specific condition variables and is formally defined in Table 106

Table 106 – ICatalyticBeadSignalConditionSetType definition
Attribute Value
BrowseNameICatalyticBeadSignalConditionSetType
IsAbstractTrue
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node
0:HasComponentVariableSensingElementTemperature 0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensorNextCalibrationFixed0:Float0:PropertyTypeO
0:HasPropertyVariableSensorNextCalibrationDynamic0:Float0:PropertyTypeO
0:HasPropertyVariablePowerOnDurationSensor0:Duration0:PropertyTypeO
0:HasPropertyVariableSensingElementResidualLife0:Float0:PropertyTypeO
0:HasPropertyVariableRelativeGasFlowRate0:Float0:PropertyTypeO
0:HasComponentVariableSensorValue0:Float0:AnalogUnitTypeO
0:HasPropertyVariableSensingElementResidualSensitivity0:Float0:PropertyTypeO
Conformance Units
PA-DIM CatalyticBeadSignalType
PA-DIM CatalyticBeadSignalType SensorNextCalibrationFixed
PA-DIM CatalyticBeadSignalType SensorNextCalibrationDynamic
PA-DIM CatalyticBeadSignalType PowerOnDurationSensor
PA-DIM CatalyticBeadSignalType SensingElementResidualLife
PA-DIM CatalyticBeadSignalType RelativeGasFlowRate
PA-DIM CatalyticBeadSignalType SensorValue
PA-DIM CatalyticBeadSignalType SensingElementResidualSensitivity

The components of ICatalyticBeadSignalType SignalConditionSetType have additional references which are defined in Table 107.

Table 107 – ICatalyticBeadSignalConditionSetType additional References
SourceBrowsePath Reference Type Is Forward TargetBrowsePath
SensingElementTemperature 0:HasDictionaryEntryTrue 3:0112/2///61987#ABP565#001
SensorNextCalibrationFixed0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ016#001
SensorNextCalibrationDynamic0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ017#001
PowerOnDurationSensor0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ010#001
SensingElementResidualLife0:HasDictionaryEntryTrue 3:0112/2///61987#ABP584#001
RelativeGasFlowRate0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ011#001
SensorValue0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ021#001
SensingElementResidualSensitivity0:HasDictionaryEntryTrue 3:0112/2///61987#ABQ040#001

The child Nodes of the IAmperometricGasDetectorSignalConditionSetType have additional Attribute values defined in Table 108.

Table 108 – ICatalyticBeadSignalConditionSetType Attribute values for child Nodes
BrowsePath Value Attribute
SensingElementTemperature 0
SensorNextCalibrationFixed0
SensorNextCalibrationDynamic0
PowerOnDurationSensor0
SensingElementResidualLife1
RelativeGasFlowRate0
SensorValue0
SensingElementResidualSensitivity1