7.1.18 IParamagneticSignalConditionSetType
The IParamagneticSignalConditionSetType provides the interface to paramagnetic measurement signal specific condition variables and is formally defined in Table 64.
| Attribute | Value | ||||
| BrowseName | IParamagneticSignalConditionSetType | ||||
| IsAbstract | True | ||||
| References | NodeClass | BrowseName | DataType | TypeDefinition | Other |
|---|---|---|---|---|---|
| Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node | |||||
| 0:HasComponent | Variable | SampleTemperature | 0:Float | 0:AnalogUnitType | O |
| 0:HasComponent | Variable | SensingElementTemperature | 0:Float | 0:AnalogUnitType | O |
| Conformance Units | |||||
|---|---|---|---|---|---|
| PA-DIM ParamagneticSignalType |
The components of IParamagneticSignalConditionSetType have additional references which are defined in Table 65.
| SourceBrowsePath | Reference Type | Is Forward | TargetBrowsePath |
| SampleTemperature | 0:HasDictionaryEntry | True | 3:0112/2///61987#ABP575#001 |
| 0:HasDictionaryEntry | True | 3:0112/2///61987#ABA968#004 | |
| SensingElementTemperature | 0:HasDictionaryEntry | True | 3:0112/2///61987#ABP565#001 |
| 0:HasDictionaryEntry | True | 3:0112/2///61987#ABA968#004 |
The child Nodes of the IParamagneticSignalConditionSetType have additional Attribute values defined in Table 66.
| BrowsePath | Value Attribute |
| SampleTemperature | 0.0 |
| NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720 UnitId: 705741427 DisplayName: °C Description: degree Celsius | |
| SensingElementTemperature | 0.0 |
| NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720 UnitId: 705741427 DisplayName: °C Description: degree Celsius |