10.1.7 RioPaAnalogOutputConfigDataType

The RioPaAnalogOutputConfigDataType represents the configuration of an analog RIO Output Channel according to RIO PA.

Table 89 – RioPaAnalogOutputConfigDataType Structure
NameTypeDescription
RioPaAnalogOutputConfigDataTypestructure
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValueRioAnalogDataTypeSubstitute value for the Process Value.
SubstituteTime0:FloatTime in seconds from the detection of a failure to the application of the SubstitutePolicy.

Its representation in the AddressSpace is defined in Table 90.

Table 90 – RioPaAnalogOutputConfigDataType Definition
Attribute Value
BrowseNameRioPaAnalogOutputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects