7.2.3.6 RioFaAnalogOutputChannelType

The RioFaAnalogOutputChannelType provides access to the data of an analog RIO Output Channel according to RIOforFA.

Table 43 – RioFaAnalogOutputChannelType
Attribute Value
BrowseNameRioFaAnalogOutputChannelType
IsAbstractFalse
References Node Class BrowseName DataType TypeDefinition Other
Subtype of the RioChannelType.
0:HasComponentVariableProcessValueRioFaAnalogProcessValueDataTypeRioFaAnalogProcessValueVariableTypeM, RO
0:HasComponentVariableProcessValueReadbackRioFaAnalogProcessValueDataTypeRioFaAnalogProcessValueVariableTypeO, RO
0:HasComponentVariableSignalValue0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableSignalValueReadback0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableConfigRioFaAnalogOutputConfigDataTypeRioFaAnalogOutputConfigVariableTypeM, RO
Conformance Units
PNRIO Channel Objects

The ProcessValue Variable contains the current analog Output value for an automated process.

The ProcessValueReadback Variable contains the readback value obtained by reading the output signal back through the Transducer and the Function Block.

The SignalValue Variable contains the output signal value fed to the signal coupling in the Transducer.

The SignalValueReadback Variable contains the output signal read back through the signal coupling in the Transducer.

The Config Variable contains the configuration properties available for the RIO Channel. See the definition of the RioFaAnalogOutputConfigVariableType (see chapter 9.4.8).