10.1 Channel Configuration DataTypes

10.1.1 RioPaDigitalInputConfigDataType

The RioPaDigitalInputConfigDataType represents the configuration of a digital RIO Input Channel according to RIO PA.

Table 77 – RioPaDigitalInputConfigDataType Structure
NameTypeDescription
RioPaDigitalInputConfigDataTypestructure
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
InversionEnabled0:BooleanTrue if the digital signal is inverted in the Function Block, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValue0:BooleanSubstitute value for the Process Value.

Its representation in the AddressSpace is defined in Table 78.

Table 78 – RioPaDigitalInputConfigDataType Definition
Attribute Value
BrowseNameRioPaDigitalInputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects

10.1.2 RioFaDigitalInputConfigDataType

The RioFaDigitalInputConfigDataType represents the configuration of a digital RIO Input Channel according to RIO FA.

Table 79 – RioFaDigitalInputConfigDataType Structure
NameTypeDescription
RioFaDigitalInputConfigDataTypestructure
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
SupplyVoltageCheckEnabled0:BooleanTrue if supply voltage check is active for the channel, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValue0:BooleanSubstitute value for the Process Value.

Its representation in the AddressSpace is defined in Table 80.

Table 80 – RioFaDigitalInputConfigDataType Definition
Attribute Value
BrowseNameRioFaDigitalInputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects

10.1.3 RioPaDigitalOutputConfigDataType

The RioPaDigitalOutputConfigDataType represents the configuration of a digital RIO Output Channel according to RIO PA.

Table 81 – RioPaDigitalOutputConfigDataType Structure
NameTypeDescription
RioPaDigitalOutputConfigDataTypestructure
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
InversionEnabled0:BooleanTrue if the digital signal is inverted in the Function Block, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValue0:BooleanSubstitute value for the Process Value.
SubstituteTime0:FloatTime in seconds from the detection of a failure to the application of the SubstitutePolicy.

Its representation in the AddressSpace is defined in Table 82.

Table 82 – RioPaDigitalOutputConfigDataType Definition
Attribute Value
BrowseNameRioPaDigitalOutputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects

10.1.4 RioFaDigitalOutputConfigDataType

The RioFaDigitalOutputConfigDataType represents the configuration of a digital RIO Output Channel according to RIO FA.

Table 83 – RioFaDigitalOutputConfigDataType Structure
NameTypeDescription
RioFaDigitalOutputConfigDataTypestructure
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
SupplyVoltageCheckEnabled0:BooleanTrue if supply voltage check is active for the channel, otherwise False.
LoadVoltageCheckEnabled0:BooleanTrue if load voltage check is active for the channel, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValue0:BooleanSubstitute value for the Process Value.
SubstituteTime0:FloatTime in seconds from the detection of a failure to the application of the SubstitutePolicy.

Its representation in the AddressSpace is defined in Table 84.

Table 84 – RioFaDigitalOutputConfigDataType Definition
Attribute Value
BrowseNameRioFaDigitalOutputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects

10.1.5 RioPaAnalogInputConfigDataType

The RioPaAnalogInputConfigDataType represents the configuration of an analog RIO Input Channel according to RIO PA.

Table 85 – RioPaAnalogInputConfigDataType Structure
NameTypeDescription
RioPaAnalogInputConfigDataTypestructure
Damping0:FloatDamping time (T63) in seconds applied to an analog signal in the Function Block.
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValueRioAnalogDataTypeSubstitute value for the Process Value.
HighLimitRioAnalogDataTypeUpper limit of an analog signal.
LowLimitRioAnalogDataTypeLower limit of an analog signal.

Its representation in the AddressSpace is defined in Table 86.

Table 86 – RioPaAnalogInputConfigDataType Definition
Attribute Value
BrowseNameRioPaAnalogInputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects

10.1.6 RioFaAnalogInputConfigDataType

The RioFaAnalogInputConfigDataType represents the configuration of an analog RIO Input Channel according to RIO FA.

Table 87 – RioFaAnalogInputConfigDataType Structure
NameTypeDescription
RioFaAnalogInputConfigDataTypestructureDamping time (T63) in seconds applied to an analog signal in the Function Block.
Damping0:FloatDamping time (T63) in seconds applied to an analog signal in the Function Block.
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
SupplyVoltageCheckEnabled0:BooleanTrue if supply voltage check is active for the channel, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValueRioAnalogDataTypeSubstitute value for the Process Value.

Its representation in the AddressSpace is defined in Table 88.

Table 88 – RioFaAnalogInputConfigDataType Definition
Attribute Value
BrowseNameRioFaAnalogInputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects

10.1.7 RioPaAnalogOutputConfigDataType

The RioPaAnalogOutputConfigDataType represents the configuration of an analog RIO Output Channel according to RIO PA.

Table 89 – RioPaAnalogOutputConfigDataType Structure
NameTypeDescription
RioPaAnalogOutputConfigDataTypestructure
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValueRioAnalogDataTypeSubstitute value for the Process Value.
SubstituteTime0:FloatTime in seconds from the detection of a failure to the application of the SubstitutePolicy.

Its representation in the AddressSpace is defined in Table 90.

Table 90 – RioPaAnalogOutputConfigDataType Definition
Attribute Value
BrowseNameRioPaAnalogOutputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects

10.1.8 RioFaAnalogOutputConfigDataType

The RioFaAnalogOutputConfigDataType represents the configuration of an analog RIO Output Channel according to RIO FA.

Table 91 – RioFaAnalogOutputConfigDataType Structure
NameTypeDescription
RioFaAnalogOutputConfigDataTypestructure
SignalTypeRioSignalTypeEnumerationSignal Type.
WireCheckEnabled0:BooleanTrue if wire check is active for the channel, otherwise False.
SupplyVoltageCheckEnabled0:BooleanTrue if supply voltage check is active for the channel, otherwise False.
LoadVoltageCheckEnabled0:BooleanTrue if load voltage check is active for the channel, otherwise False.
SubstitutePolicyRioSubstitutePolicyEnumerationSubstitute value setting of the channel.
SubstituteValueRioAnalogDataTypeSubstitute value for the Process Value.
SubstituteTime0:FloatTime in seconds from the detection of a failure to the application of the SubstitutePolicy.

Its representation in the AddressSpace is defined in Table 92.

Table 92 – RioFaAnalogOutputConfigDataType Definition
Attribute Value
BrowseNameRioFaAnalogOutputConfigDataType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:Structure type defined in OPC 10000-3
Conformance Units
PNRIO Channel Objects