7.43 DriveDesignType ObjectType Definition

The DriveDesignType provides static Variables for Pump drive design properties and is formally defined in Table 94.

Table 94 – DriveDesignType Definition
Attribute Value
BrowseNameDriveDesignType
IsAbstractFalse
References Node Class BrowseName DataType TypeDefinition Other
Subtype of the 2:FunctionalGroupType defined in OPC 10000-100, i.e. inheriting the InstanceDeclarations of that Node.
0:HasComponentVariableEnergyEfficiencyClassOfMotor0:String0:DataItemTypeO, RO
0:HasComponentVariableMaxNominalFrequency0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableMinNominalFrequency0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableMotorEfficiency0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableNominalFrequency0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableNominalPowerConsumption0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableNominalVoltage0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariablePowerFactor0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableProtectionClass0:String0:DataItemTypeO, RO
0:HasComponentVariableRatedCurrent0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableRatedSpeed0:Double0:BaseAnalogTypeO, RO
0:HasComponentVariableTorqueAtNominalSpeedOfDrive0:Double0:BaseAnalogTypeO, RO

The InstanceDeclarations of the DriveDesignType have additional Attributes defined in

Table 95. The Variables and the associated Descriptions are based on the standard DIN EN ISO 17769-1 and ECLASS entries.

Table 95 – DriveDesignType Attribute values for child Nodes
BrowsePath Value Attribute Description Attribute
EnergyEfficiencyClassOfMotorCharacterization of the energy efficiency of electric motors according to international standards.
MaxNominalFrequencyA suitable, maximum (usually rounded) value of a frequency to describe, designate or identify a component, device, resource, facility or equipment.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4740186

DisplayName: Hz

Description: hertz

MinNominalFrequencyA suitable minimum (usually rounded) value of a frequency to describe, designate or identify a component, device, resource, facility or equipment.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4740186

DisplayName: Hz

Description: hertz

MotorEfficiencyProportion of the motor power input P_mot delivered as pump power input P_mot, u.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 20529

DisplayName: %

Description: percent

NominalFrequencyDesign of the object at a certain frequency, which is repeated regularly.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4740186

DisplayName: Hz

Description: hertz

NominalPowerConsumptionIndication of the rated power consumption in watts.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5723220

DisplayName: W

Description: watt

NominalVoltageRated voltage is the value of the electrical voltage in normal operation specified by the manufacturer or supplier.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5655636

DisplayName: V

Description: volt

PowerFactorRatio of the amount of active power to apparent power.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 20529

DisplayName: %

Description: percent

ProtectionClassProtection class of an enclosure, expressed as NEMA or IP rating.
RatedCurrentAppropriate (usually rounded) value of a current to describe, designate or identify a component, device, resource, facility or equipment.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4279632

DisplayName: A

Description: ampere

RatedSpeedSpeed corresponding to the rated data of the motor used.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4405559

DisplayName: s⁻¹

Description: reciprocal second

TorqueAtNominalSpeedOfDriveThe torque transmittable by the equipment.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5129559

DisplayName: N