9.1 Conformance Units
This chapter defines the corresponding Conformance Units for the OPC UA Information Model for Pumps and Vacuum Pumps.
| Category | Title | Description |
| Server | Base System | The PumpType is implemented by the server. |
| Server | Historizing | The Historizing Attribute and the HistoryRead Attribute is True for at least one Quantity. |
| Server | Limit Alarm Status | The ObjectTypes MeasurementsType, DriveMeasurementsType, InletConnectionMeasurementsType and OutletConnectionMeasurementsType have a 0:GeneratesEvent reference targeting one of the subtypes of the 0:LimitAlarmType. |
| Server | PumpClass Data | The PumpClass Property of the Design FunctionalGroup is instantiated for all instantiated Pumps and carries a legal value. |
| Server | Pump Connection Port | At least one of the InletConnectionPortType or the OutletConnectionPortType is implemented by the Server. |
| Server | Pump Control | At least one of ControlType, ActuationType or one of subtypes of ActuationType is implemented by the Server. |
| Server | Pump Drive Port | The DrivePortType is implemented by the server. |
| Server | Pump Identification | Supports the PumpIdentificationType with all its mandatory InstanceDeclarations, and optionally the optional InstanceDeclarations with read access. |
| Server | Pump PumpType Mandatory Nodes | All nodes declared as mandatory in the PumpType are available in the AdressSpace. |
| Server | Supervision Health Status | Every instance of a variable of type 0:TwoStateDiscreteType in the subtypes of SupervisionType has a GeneratesEvent reference targeting one of the subtypes of the 2:DeviceHealthDiagnosticAlarmType. |