9.1 Conformance Units

This chapter defines the corresponding Conformance Units for the OPC UA Information Model for Pumps and Vacuum Pumps.

Table 152 – Conformance Units for OPC UA for Pumps and Vacuum Pumps
Category Title Description
ServerBase SystemThe PumpType is implemented by the server.
ServerHistorizingThe Historizing Attribute and the HistoryRead Attribute is True for at least one Quantity.
ServerLimit Alarm StatusThe ObjectTypes MeasurementsType, DriveMeasurementsType, InletConnectionMeasurementsType and OutletConnectionMeasurementsType have a 0:GeneratesEvent reference targeting one of the subtypes of the 0:LimitAlarmType.
ServerPumpClass DataThe PumpClass Property of the Design FunctionalGroup is instantiated for all instantiated Pumps and carries a legal value.
ServerPump Connection PortAt least one of the InletConnectionPortType or the OutletConnectionPortType is implemented by the Server.
ServerPump ControlAt least one of ControlType, ActuationType or one of subtypes of ActuationType is implemented by the Server.
ServerPump Drive PortThe DrivePortType is implemented by the server.
ServerPump Identification

Supports the PumpIdentificationType with all its mandatory

InstanceDeclarations, and optionally the optional InstanceDeclarations with read access.

ServerPump
PumpType
Mandatory Nodes
All nodes declared as mandatory in the PumpType are available in the AdressSpace.
ServerSupervision Health StatusEvery instance of a variable of type 0:TwoStateDiscreteType in the subtypes of SupervisionType has a GeneratesEvent reference targeting one of the subtypes of the 2:DeviceHealthDiagnosticAlarmType.