9.2.2 Server Facets
9.2.2.1 Overview
The following sections specify the Facets available for Servers that implement the OPC UA for Pumps and Vacuum Pumps companion specification. Each section defines and describes a Facet or Profile.
9.2.2.2 Pump Base Server Profile
This Profile defines the elements for a Pump Server which supports basic functionality like the configuration of the Pump, perform various analyses, and provide machine identification.
| Group | Conformance Unit / Profile Title | M / O |
| Profile | 0:Embedded 2017 UA Server Profile http://opcfoundation.org/UA-Profile/Server/EmbeddedUA2017 | M |
| Profile | 0:Data Access Server Facet http://opcfoundation.org/UA-Profile/Server/DataAccess | M |
| Profile | 0:ComplexType 2017 Server Facet http://opcfoundation.org/UA-Profile/Server/ComplexTypes2017 | M |
| Profile | 0:Aggregate Subscription Server Facet http://opcfoundation.org/UA-Profile/Server/AggregateSubscription | M |
| Profile | 3:Machine Identification Writable Server Facet http://opcfoundation.org/UA-Profile/Machinery/Server/MachineIdentificationWritable | M |
| Pump | Pump PumpType Mandatory Nodes | M |
| Pump | Base System | M |
9.2.2.3 Pump Advanced Server Profile
This Profile defines the elements for a Pump Server which supports advanced functionality like the control of the pump, provide health and limit status in the AddressSpace and provide ports.
| Group | Conformance Unit / Profile Title | M / O |
| Profile | 0:Address Space Notifier Server Facet http://opcfoundation.org/UA-Profile/Server/AddressSpaceNotifier | M |
| Profile | 0:A & C Address Space Instance Server Facet http://opcfoundation.org/UA-Profile/Server/ACAddressSpaceInstance | M |
| Profile | 0:A & C Exclusive Alarming Server Facet http://opcfoundation.org/UA-Profile/Server/ACExclusiveAlarming | M |
| Profile | 0:Base Historical Event Server Facet http://opcfoundation.org/UA-Profile/Server/BaseHistoricalEvent | M |
| Profile | 0:Historical Raw Data Server Facet http://opcfoundation.org/UA-Profile/Server/HistoricalRawData | M |
| Profile | 0:Historical Aggregate Server Facet http://opcfoundation.org/UA-Profile/Server/AggregateHistorical | M |
| Profile | Pump Base Server Profile http://opcfoundation.org/UA-Profile/CAS/Server/Base | M |
| Pumps | Historizing | O |
| Pumps | Limit Alarm Status | O |
| Pumps | PumpClass Data | O |
| Pumps | Pump Connection Port | O |
| Pumps | Pump Control | O |
| Pumps | Pump Drive Port | O |
| Pumps | Supervision Health Status | O |