7.21 SystemRequirementsType ObjectType Definition

The SystemRequirementsType provides static Variables for parameters of the process in which the Pump is to be used and is formally defined in Table 49.

Table 49 – SystemRequirementsType Definition
Attribute Value
BrowseNameSystemRequirementsType
IsAbstractFalse
References Node Class BrowseName DataType TypeDefinition Other
Subtype of the 2:FunctionalGroupType defined in OPC 10000-100, i.e. inheriting the InstanceDeclarations of that Node.
0:HasComponentVariableCompressionRatio0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableExplosionZoneExplosionZoneOptionSet0:DataItemTypeO, RW
0:HasComponentVariableFieldbusFieldbusEnum0:DataItemTypeO, RW
0:HasComponentVariableFluid0:String0:DataItemTypeO, RW
0:HasComponentVariableGasContent0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableHeightOfTheInletSideOfTheInstallation0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableHeightOfTheOutletSideOfTheInstallation0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableHeightOfThePump0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMaximumAmbientTemperature0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMaximumFlow0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMaximumHead0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMaximumInletPressure0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMaximumOutletPressure0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMaximumRelativeHumidity0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMaximumTemperature0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMeanTimeBetweenFailures0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMinimumAmbientTemperature0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMinimumFlow0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMinimumHead0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMinimumInletPressure0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMinimumOutletPressure0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMinimumRelativeHumidity0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMinimumTemperature0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableMulti_Phase0:Boolean0:TwoStateDiscreteTypeO, RW
0:HasComponentVariableNetPositiveInletPressureAvailable0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableNormalFlow0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableNpshDatumPlane0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableOperatingModeOperatingModeEnum0:DataItemTypeO, RW
0:HasComponentVariableRatedInletPressureOfTheInstallation0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableRatedPumpUnitTotalHead0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableReferencePlane0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableRequiredControlModeControlModeEnum0:DataItemTypeO, RW
0:HasComponentVariableRequiredTime0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableSolidContent0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableThroughput0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableUltimatePressureOfAVacuumPump0:Double0:BaseAnalogTypeO, RW
0:HasComponentVariableWorkingTemperature0:Double0:BaseAnalogTypeO, RW

The InstanceDeclarations of the SystemRequirementsType have additional Attributes defined in Table 50. The Variables and the associated Descriptions are based on the standards DIN EN ISO 17769-1, DIN ISO 21360-1, ISO 3529-2, DIN 28400-2, DIN EN 13306 and VDI 3805-4.

Table 50 – SystemRequirementsType Attribute values for child Nodes
BrowsePath Value Attribute Description Attribute
CompressionRatioRatio of the backing pressure, p3, to the inlet pressure, p1, of the vacuum pump without throughput
ExplosionZoneCategories of explosion zones for devices according to 2014/34/EU (ATEX).
FieldbusSelected fieldbus for the product
FluidFluid that is handled by the pump at specified operating conditions
GasContentProportion of gaseous substance in the liquid to be pumped, either as a contaminant or as vapor from the main body of liquid

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 20529

DisplayName: %

Description: percent

HeightOfTheInletSideOfTheInstallationHeight of the fluid level on the inlet side of the installation, or in the center of the inlet manifold

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067858

DisplayName: m

Description: metre

HeightOfTheOutletSideOfTheInstallationHeight of the fluid level on the outlet side of the installation or in the center of the outlet manifold

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067858

DisplayName: m

Description: metre

HeightOfThePumpHeight of the center of the pump

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067858

DisplayName: m

Description: metre

MaximumAmbientTemperatureHighest ambient temperature to be expected under normal circumstances

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4932940

DisplayName: K

Description: kelvin

MaximumFlowGreatest rate of flow which is expected at operating conditions

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067091

DisplayName: m³/s

Description: cubic metre per second

MaximumHeadHighest total head developed by a pump at any rate of flow

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067858

DisplayName: m

Description: metre

MaximumInletPressureHighest inlet pressure to which the pump is subjected during operation

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5259596

DisplayName: Pa

Description: pascal

MaximumOutletPressureMaximum possible pressure at outlet, due either to internal energy increase (rotodynamic pumps) or external downstream restrictions (volumetric pumps)

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5259596

DisplayName: Pa

Description: pascal

MaximumRelativeHumidityHighest relative humidity that can be expected under normal circumstances.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 20529

DisplayName: %

Description: percent

MaximumTemperatureHighest fluid temperature to be expected under operating conditions

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4932940

DisplayName: K

Description: kelvin

MeanTimeBetweenFailuresAverage of the times between failures

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4740434

DisplayName: h

Description: hour

MinimumAmbientTemperatureLowest ambient temperature to be expected under normal circumstances

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4932940

DisplayName: K

Description: kelvin

MinimumFlowSmallest rate of flow which is expected at operating conditions

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067091

DisplayName: m³/s

Description: cubic metre per second

MinimumHeadSmallest total head developed by a pump at any rate of flow

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067858

DisplayName: m

Description: metre

MinimumInletPressureLowest inlet pressure that can occur during operation for the pump

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5259596

DisplayName: Pa

Description: pascal

MinimumOutletPressureLowest outlet pressure that can occur during operation for the pump

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5259596

DisplayName: Pa

Description: pascal

MinimumRelativeHumidityLowest relative humidity to be expected under normal circumstances.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 20529

DisplayName: %

Description: percent

MinimumTemperatureLowest fluid temperature to be expected under operating conditions

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4932940

DisplayName: K

Description: kelvin

Multi_PhaseComprising a fluid together with substances in solid or gaseous states, whether due to deliberate addition or a change of state caused by a change in conditions. A "True" status means that there is a possibility of multi-phase-fluid and a "False" status means that there is no possibility of multi-phase-fluid.
NetPositiveInletPressureAvailableTotal pressure (including velocity pressure) at the pump inlet connection less the liquid vapor pressure at the present temperature of the liquid

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5259596

DisplayName: Pa

Description: pascal

NormalFlowRate of flow at which usual operation is expected

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067091

DisplayName: m³/s

Description: cubic metre per second

NpshDatumPlaneHorizontal plane through the center of the circle described by the external points of the entrance edges of the impeller blades, in the first stage in the case of multi-stage pumps

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067858

DisplayName: m

Description: metre

OperatingModeSpecifies whether the pump is to be operated in single, parallel or series connection.
RatedInletPressureOfTheInstallationInlet pressure of the installation for the working conditions

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5259596

DisplayName: Pa

Description: pascal

RatedPumpUnitTotalHeadDifference of the total head, at the outlet side of the pump unit from the total head at the inlet side of the pump unit, at which usual operation is expected

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067858

DisplayName: m

Description: metre

ReferencePlaneAny horizontal plane for use as the datum for height measurement

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5067858

DisplayName: m

Description: metre

RequiredControlModeSpecifies which control mode is to be used for the use case.
RequiredTimeTime interval throughout which an item is required to be in an up state

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4740434

DisplayName: h

Description: hour

SolidContentProportion of solids contained in the fluid to be pumped, either as a contaminant or as a deliberate useful burden or suspension

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 20529

DisplayName: %

Description: percent

ThroughputAmount of fluid flowing through a duct

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4665393

DisplayName: Pa·m³/s

Description: pascal cubic metre per second

UltimatePressureOfAVacuumPumpThe ultimate pressure is the value to which the pressure in a standardized test dome approaches asymptotically during normal operation of the vacuum pump and without gas inlet. A difference can be made between the final pressure caused by gases and the final pressure caused by gases and vapors.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5259596

DisplayName: Pa

Description: pascal

WorkingTemperatureTemperature determined by the given application and fluid.

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4932940

DisplayName: K

Description: kelvin