The SupervisionAuxiliaryDeviceType provides Variables used for monitoring the Pump auxiliary devices. It is formally defined in Table 41. For the generation of events, the SupervisionAuxiliaryDeviceType has references to the four Namur NE 107 statuses defined in OPC 10000-100. The InputNode Property of the Alarm shall contain the NodeId of the Component.
Subtype of the 2:FunctionalGroupType defined in OPC 10000-100, i.e. inheriting the InstanceDeclarations of that Node.
0:HasComponent
Variable
ActuatorElement
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
AmbientTemperature
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
AuxiliaryDeviceFault
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
AuxiliaryMediumAbsence
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
AuxiliaryMediumInsufficiency
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
AuxiliaryPowerPole
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
AuxiliaryPowerRange
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
CommunicationError
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Corrosion
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Deviation
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
ElectromagneticInterference
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
ElectronicFault
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
EnergySupply
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
EvaluationElectronics
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
ExciterError
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Fouling
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
HumidityElectronics
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Installation
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Interruption
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
LineLength
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
MaterialElectronics
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
MeasuredMaterialElectronics
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
MechanicalDamage
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
OperatingConditions
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Other
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Overloading
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
ParameterSetting
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Peripheral
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
ProcessInfluence
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SensorElement
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
StartUp
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
TemperatureShock
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
Vibration
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
WearReserveOperation
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
WearReserveWear
0:Boolean
0:TwoStateDiscreteType
O, RO
0:GeneratesEvent
ObjectType
2:CheckFunctionAlarmType
Defined in OPC 10000-100
0:GeneratesEvent
ObjectType
2:FailureAlarmType
Defined in OPC 10000-100
0:GeneratesEvent
ObjectType
2:MaintenanceRequiredAlarmType
Defined in OPC 10000-100
0:GeneratesEvent
ObjectType
2:OffSpecAlarmType
Defined in OPC 10000-100
The InstanceDeclarations of the SupervisionAuxiliaryDeviceType have additional Attributes defined in Table 42. The Variables and the associated Descriptions are based on the standard VDMA 24223-1.
Table 42 – SupervisionAuxiliaryDeviceType Attribute values for child Nodes
BrowsePath
Description Attribute
ActuatorElement
This property indicates a fault in an actuator element.
AmbientTemperature
This property indicates an abnormal ambient temperature.
AuxiliaryDeviceFault
This property indicates a generic failure of an auxiliary device.
AuxiliaryMediumAbsence
This property indicates an absence of or wrong auxiliary medium.
AuxiliaryMediumInsufficiency
This property indicates an insufficiency of auxiliary medium.
AuxiliaryPowerPole
This property indicates an auxiliary power supply wrongly poled.
AuxiliaryPowerRange
This property indicates an off-spec of the auxiliary power range.
CommunicationError
This property indicates a communication error.
Corrosion
This property indicates corrosion/abrasion in parts in contact with medium.
Deviation
This property indicates an inadmissible deviation from measurement.
ElectromagneticInterference
This property indicates an abnormal electromagnetic interference.
ElectronicFault
This property indicates a fault in the device electronics.
EnergySupply
This property indicates an error in internal energy supply.
EvaluationElectronics
This property indicates an error in evaluation electronics.
ExciterError
This property indicates an error in the exciter of the sensor element.
Fouling
This property indicates a fouling on sensor element.
HumidityElectronics
This property indicates an abnormal amount of humidity in electronics area.
Installation
This property indicates an installation fault.
Interruption
This property indicates an interruption of signal path or short circuit.
LineLength
This property indicates that the maximum line length is exceeded.
MaterialElectronics
This property indicates a foreign material in electronics area.
MeasuredMaterialElectronics
This property indicates measured material in electronics area.
MechanicalDamage
This property indicates a mechanical damage.
OperatingConditions
This property indicates a fault due to non-compliance with specified operating conditions.
Other
This property indicates other faults.
Overloading
This property indicates an overloading.
ParameterSetting
This property indicates a parameter setting error.
Peripheral
This property indicates an error in peripherals.
ProcessInfluence
This property indicates a fault due to process influence.
SensorElement
This property indicates a fault in a sensor element.
StartUp
This property indicate an installation fault or fault during start-up.
TemperatureShock
This property indicates an excessive temperature shock.
Vibration
This property indicates an excessive vibration or impact load.
WearReserveOperation
This property indicates that the wear reserve is used up by operation.
WearReserveWear