The SupervisionElectronicsType provides Variables used for monitoring the Pump electronics. It is formally defined in Table 43. For the generation of events, the SupervisionElectronicsType has references to the four Namur NE 107 statuses defined in OPC 10000-100. The InputNode Property of the Alarm shall contain the NodeId of the Component.
Table 43 – SupervisionElectronicsType Definition
Attribute
Value
BrowseName
SupervisionElectronicsType
IsAbstract
false
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the 2:FunctionalGroupType defined in OPC 10000-100, i.e. inheriting the InstanceDeclarations of that Node.
0:HasComponent
Variable
ArmatureCircuit
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
CurrentInsideDevice
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
ElectricalFault
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
FieldCircuit
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
InstallationFault
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
InsulationResistance
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
PhaseFailure
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
ShortCircuit
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
ShortToEarth
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyCurrent
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyCurrentHigh
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyCurrentLow
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyFrequency
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyFrequencyHigh
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyFrequencyLow
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyVoltage
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyVoltageHigh
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
SupplyVoltageLow
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
VoltageInsideDevice
0:Boolean
0:TwoStateDiscreteType
O, RO
0:HasComponent
Variable
WindingTemperature
0:Boolean
0:TwoStateDiscreteType
O, RO
0:GeneratesEvent
ObjectType
2:CheckFunctionAlarmType
Defined in OPC 10000-100
0:GeneratesEvent
ObjectType
2:FailureAlarmType
Defined in OPC 10000-100
0:GeneratesEvent
ObjectType
2:MaintenanceRequiredAlarmType
Defined in OPC 10000-100
0:GeneratesEvent
ObjectType
2:OffSpecAlarmType
Defined in OPC 10000-100
The InstanceDeclarations of the SupervisionElectronicsType have additional Attributes defined in Table 44. The Variables and the associated Descriptions are based on the standard VDMA 24223-1.
Table 44 – SupervisionElectronicsType Attribute values for child Nodes
BrowsePath
Description Attribute
ArmatureCircuit
This property indicates a failure in armature circuit.
CurrentInsideDevice
This property indicates unacceptable current inside the device.
ElectricalFault
This property indicates a generic electrical fault.
FieldCircuit
This property indicates a failure in field circuit.
InstallationFault
This property indicates an unacceptable electrical installation, e.g. mixed up phases.
InsulationResistance
This property indicates an unacceptable low winding resistance.
PhaseFailure
This property indicates a phase failure.
ShortCircuit
This property indicates a short circuit.
ShortToEarth
This property indicates a short to earth.
SupplyCurrent
This property indicates a failure of supply current.
SupplyCurrentHigh
This property indicates too high supply current.
SupplyCurrentLow
This property indicates too low supply current.
SupplyFrequency
This property indicates unacceptable supply frequency.
SupplyFrequencyHigh
This property indicates too high supply frequency.
SupplyFrequencyLow
This property indicates too low supply frequency.
SupplyVoltage
This property indicates a failure of supply voltage.
SupplyVoltageHigh
This property indicates too high supply voltage.
SupplyVoltageLow
This property indicates too low supply voltage.
VoltageInsideDevice
This property indicates unacceptable voltage inside the device.
WindingTemperature
This property indicates an unacceptable winding temperature.