9.11 IOLinkMasterAlarmType
The IOLinkMasterAlarmType is the base EventType for alarms generated from an IO-Link Master. It is formally defined in Table 57.
| Attribute | Value | ||||
| BrowseName | IOLinkMasterAlarmType | ||||
| IsAbstract | False | ||||
| References | Node Class | BrowseName | DataType | TypeDefinition | Modelling Rule |
|---|---|---|---|---|---|
| Subtype of IOLinkAlarmType | |||||
The following rules for the inherited Properties apply.
The mandatory Property SourceNode shall be the NodeId of the object representing the IO-Link Master the event originates from.
The mandatory Property SourceName shall be the string part of the BrowseName of the Object representing the IO-Link Master the Event originates from.
The mandatory Property Time shall be the time the Event occurred on the IO-Link Master.
The mandatory Property ReceiveTime shall be set to the time the OPC UA Server receives the event. In case the OPC UA Server runs on the IO-Link Master, this might be the same value as the value of Property Time.
The Properties IOLinkEventCode and the Message are vendor-specific. Vendors may also create subtypes of this EventType to add vendor-specific Properties or to categorize the alarms generated by the IO-Link Master.