6.3.1.8.1.1 SetTags Method
This optional method writes the I&M1 fields IM_TagFunction and IM_Tag_Location remanent to the PROFINET device and sets the TagFunction and TagLocation variables accordingly.
Signature
SetTags (
[in] IMTagSelectorEnumeration Tag_Selector,
[in] String Tag_Function,
[in] String Tag_Location
);
| Argument | Description |
| Tag_Selector | If FUNCTION, Tag_Function shall be written, If LOCATION, Tag_Location shall be written, if BOTH both. |
| Tag_Function | String containing the new I&M1 | IM_Tag_Function to be written remanent to the device. |
| Tag_Location | String containing the new I&M1 | IM_Tag_Location to be written remanent to the device. |
Method Result Codes
| ResultCode | Description |
| Bad_InvalidArgument | The Server is not able to apply an argument. The argument may be too long or may contain invalid characters. |
| Bad_UnexpectedError | The Server is not able to apply the name because an unexpected error occurred. The device might be temporarily unavailable or unreachable due to network failure. |