7.2.2 Behaviour

7.2.2.1 General

The two SCL services SafetyProvider and SafetyConsumer are specified using state diagrams.

7.2.2.2 SafetyProvider and SafetyConsumer Sequence diagram

Figure 13 and Figure 14 show sequences of requests and responses with SafetyData for this document using OPC UA Client/Server and PubSub communication mechanisms, respectively. The figures show selected scenarios only and are therefore informative.

Figure 13 (informative) – Sequence diagram for requests and responses (Client/Server)

[RQ7.10] In the case of Client/Server communication, a SafetyConsumer’s OPC UA Mapper may call a SafetyProvider (either the state machine implementation itself or the SafetyProvider’s OPC UA Mapper) with an identical RequestSPDU multiple times in a row. In that case, the SafetyProvider (state machine or OPC UA Mapper) shall answer all requests. The returned ResponseSPDUs may contain different values (e.g. currently available process values) or contain the initially returned values.

[RQ7.11] For each SafetyProvider, the implemented choice of behaviour according to RQ7.10 (i.e. whether currently available process values or initially returned values will be used) shall be documented in the corresponding safety manual.

The SafetyConsumerTimeout is the watchdog time checked in the SafetyConsumer. The watchdog is restarted immediately before a new RequestSPDU is generated (transitions T14 and T28 of the SafetyConsumer in Table 35). If an appropriate ResponseSPDU is received in time, and the checks for data integrity, authenticity, and timeliness are all valid, the timer will not expire before it is restarted.

Otherwise, the watchdog timer expires, and the SafetyConsumer triggers a safe reaction. To duly check its timer, the SafetyConsumer is executed cyclically, with period ConsumerCycleTime. ConsumerCycleTime is expected to be smaller than SafetyConsumerTimeout.

The ConsumerCycleTime is the maximum time for the cyclic update of the SafetyConsumer. It is the timeframe from one execution of the SafetyConsumer to the next execution of the SafetyConsumer. The implementation of the monitoring of the ConsumerCycleTime and the reaction in case of exceeding the ConsumerCycleTime are not part of this document; these are vendor-specific.

[RQ7.12] The ConsumerCycleTime shall be monitored in a safety-related way.

[RQ7.26] A change of the SafetyConsumerTimeout parameter value shall take immediate effect on the ConsumerTimer.

7.2.2.3 Duration of demand

In case it is necessary to ensure that a given SafetyData (e.g. a safety demand or a command value) that originates in the SafetyProvider’s safety application is being received by a SafetyConsumer and forwarded to the SafetyConsumer’s safety application, i.e. if no SafetyData in a series of SafetyData is to be missed, the following two cases shall be considered.

In case A, repeated identical RequestSPDUs are being answered by the SafetyProvider with ResponseSPDUs which contain the initially returned value. This is the case for PubSub communication and is a choice for Client/Server communication, see RQ7.11. In this case, the SafetyProvider’s safety application shall provide the respective SafetyData at the SafetyProvider’s SAPI until at least one change of the MNR is detected.

In case B, repeated identical RequestSPDUs are being answered by the SafetyProvider with the currently available SafetyData. This is a choice for Client/Server communication, see RQ7.11. In this case, the SafetyProvider’s safety application shall provide the respective SafetyData at the SafetyProvider’s SAPI until at least two changes of the MNR have been detected.

Figure 15 and Figure 16 show examples justifying case B by depicting two sequences of ResponseSPDUs as sent by a SafetyProvider. Due to the cycles of SafetyProvider and SafetyConsumer not being synchronized, a SafetyConsumer can evaluate any one of a given number of ResponseSPDUs for a given RequestSPDU.

In the examples, the SafetyData is made up of two components: the “respective safety data”, i.e. a safety demand that is not to be missed (one of the values “A”, “B” or “C”) and non-demand numerical measurement values for which it does not matter whether some are not received by the SafetyConsumer.

The worst-case time to make sure that the respective safety data from the SafetyProvider is made available to the SafetyConsumer is two times the SafetyConsumerTimeout. This worst-case time occurs when the two transmissions of a RequestSPDU and its corresponding ResponseSPDU, which are necessary according to the descriptions above, each take a time of just slightly under one SafetyConsumerTimeout.

If the SafetyConsumer’s SafetyConsumerTimeout is known at the SafetyProvider, the SafetyProvider may alternatively provide the respective safety data for at least two times the SafetyConsumerTimeout to ensure that the respective safety data reaches the SafetyConsumer.

Since NonSafetyData is consistently transmitted with SafetyData, the same considerations apply for NonSafetyData.

Figure 15 – Duration of demand example for missed demand value in case of currently available SafetyData not being provided until second change of MNR
Figure 16 – Duration of demand example for received demand value in case of currently available SafetyData being provided
7.2.2.4 SafetyProvider state diagram

[RQ7.13] Figure 17 shows a simplified representation of the state diagram of the SafetyProvider. The exact behaviour is described in Table 30, Table 31, and Table 32. The SafetyProvider shall implement that behaviour. It is not required to literally follow the entries given in the tables, if the externally observable behaviour does not change.

Figure 17 – Simplified representation of the state diagram for the SafetyProvider

Table 29 shows the symbols used for state machines.

Table 29 – Symbols used for state machines
Graphical representationTypeDescription
Activity stateWithin these interruptible activity states the SafetyProvider waits for new input.
Action stateWithin these non-interruptible action states events like new requests are deferred until the next activity state is reached, see [1].

The transitions are fired in case of an event. “Event” in this context means either a Method call in the case of Client/Server communication or the detection of a changed RequestSPDU by the OPC UA Mapper in the case of PubSub communication.

In case of several possible transitions, so-called guard conditions (refer to […] in UML diagrams) define which transition to fire.

The diagram consists of activity and action states. Activity states are surrounded by bold lines, action states are surrounded by thin lines. While activity states can be interruptible by new events, action states are not. External events occurring while the state machine is in an action state, are deferred until the next activity state is reached.

If input is available, it starts executing action states until its time-slice is up or until the next activity state is reached.

Table 30 shows the internal items of a SafetyProvider instance.

Table 30 – SafetyProvider instance internal items
Internal itemsTypeDefinition
RequestSPDU_iVariableLocal memory for RequestSPDU (required to react on changes).
SPDU_ID_1_iUInt32Local variable to store SPDU_ID_1.
SPDU_ID_2_iUInt32Local variable to store SPDU_ID_2.
SPDU_ID_3_iUInt32Local variable to store SPDU_ID_3.
BaseID_iGuidLocal variable containing the BaseID (taken either from the SPI or SAPI).
ProviderID_iUInt32Local variable containing the ProviderID (taken either from the SPI or SAPI).
<Get RequestSPDU>MacroInstruction to take the whole RequestSPDU from the OPC UA Mapper.
<Set ResponseSPDU>MacroInstruction to transfer the whole ResponseSPDU to the OPC UA Mapper.
<Calc SPDU_ID_i>Macro

const uint32 SafetyProviderLevel_ID:= … // see 7.2.3.4

If(SAPI.SafetyBaseID == 0) then
BaseID_i:= SPI.SafetyBaseIDConfigured
Else
BaseID_i:= SAPI.SafetyBaseID

Endif
If(SAPI.SafetyProviderID == 0) then
ProviderID_i:= SPI.SafetyProviderIDConfigured
Else
ProviderID_i:= SAPI.SafetyProviderID

Endif

SPDU_ID_1_i:= BaseID_i (octets 0…3)
XOR SafetyProviderLevel_ID

SPDU_ID_2_i:= BaseID_i (octets 4…7)
XOR SPI.SafetyStructureSignature

SPDU_ID_3_i:= BaseID_i (octets 8…11)
XOR BaseID_i (octets 12…15)
XOR ProviderID_i

// see 7.2.3.2 for clarification

<build ResponseSPDU>Macro

Take the MNR and the SafetyConsumerID of the received RequestSPDU. Add the SPDU_ID_1_i, SPDU_ID_2_i, SPDU_ID_3_i, Flags, the SafetyData and the NonSafetyData, as well as the calculated CRC.

See 7.2.3.1

Table 31 shows the states of a SafetyProvider instance. The SafetyProvider does not check for correct configuration. It will reply to requests even if it is incorrectly configured (e.g. its SafetyProviderID is zero). However, SafetyConsumers will never try to communicate with SafetyProviders having incorrect parameters, see Transitions T13 and T27 in Table 35 and the macro <ParametersOK?> in Table 33.

Table 31 – States of SafetyProvider instance
State nameState description
Initialization

// Initial state

SAPI.SafetyData:= 0

SAPI.NonSafetyData:= 0
SAPI.MonitoringNumber:= 0
SAPI.SafetyConsumerID:= 0

SAPI.OperatorAckRequested:= 0

RequestSPDU_i:= 0

S1_WaitForRequest

// waiting on next RequestSPDU from SafetyConsumer

<Get RequestSPDU>

S2_PrepareSPDU

ResponseSPDU.Flags.ActivateFSV:= SAPI.ActivateFSV
ResponseSPDU.Flags.OperatorAckProvider:= SAPI.OperatorAckProvider
ResponseSPDU.Flags.TestModeActivated:= SAPI.EnableTestMode

<Calc SPDU_ID_i>

<build ResponseSPDU> // see 7.2.3.1

Table 32 shows the transitions of the SafetyProvider.

Table 32 – SafetyProvider transitions
TransitionSource stateTarget stateGuard conditionActivity
T1InitS1
T2S1S2

// RequestSPDU received1

-

// Process request

RequestSPDU_i:= RequestSPDU

SAPI.MonitoringNumber:= RequestSPDU.MonitoringNumber

SAPI.SafetyConsumerID:= RequestSPDU.SafetyConsumerID

SAPI.OperatorAckRequested:= RequestSPDU.Flags.OperatorAckRequested

T3S2S1

// SPDU is prepared

-

<Set ResponseSPDU>
1 See the preceding explanation in 7.2.2.4 of what constitutes events which trigger this transition.
7.2.2.5 SafetyConsumer state diagram

[RQ7.14] Figure 18 shows a simplified representation of the state diagram of the SafetyConsumer. The exact behaviour is described in Table 33, Table 34, and Table 35. The SafetyConsumer shall implement this behaviour. It is not required to literally follow the entries given in the tables, if the externally observable behaviour does not change.

To avoid unnecessary spurious trips requiring operator acknowledgment, it is recommended that a SafetyConsumer is started after an OPC UA connection to a running SafetyProvider has been established, or that the setting of input SAPI.Enable to “1” is delayed until the SafetyProvider is running.

Figure 18 – Principle state diagram for SafetyConsumer

Table 33 shows the internal items of a SafetyConsumer. A macro is a shorthand representation for operations described in the according definition.

Table 33 – SafetyConsumer internal items
Internal itemsTypeDefinition
Constants
MNR_min:= 0x100UInt32

// 0x100 is the start value for MNR, also used after wrap-around

// The values 0…0xFF are reserved for future use

Variables
FaultReqOA_iBooleanLocal memory for errors which request operator acknowledgment
OperatorAckConsumerAllowed_iBooleanAuxiliary flag indicating that operator acknowledgment is allowed. It is true if the input SAPI.OperatorAckConsumer has been ‘false’ since FaultReqOA_i was set
MNR_iUInt32Local MonitoringNumber (MNR)
prevMNR_iUInt32Local memory for previous MNR
ConsumerID_iUInt32Local memory for SafetyConsumerID in use
CRCCheck_iBooleanLocal variable used to store the result of the CRC check
SPDUCheck_iBooleanLocal variable used to store the result of the additional SPDU checks
SPDU_ID_1_iUInt32Local variable to store the expected SPDU_ID_1
SPDU_ID_2_iUInt32Local variable to store the expected SPDU_ID_2
SPDU_ID_3_iUInt32Local variable to store the expected SPDU_ID_3
SPI_SafetyConsumerID_iUInt32Local variable to store the parameter SafetyConsumerID
SPI_SafetyProviderID_iUInt32Local variable to store the parameter SafetyProviderID
SPI_SafetyBaseID_iUInt128Local variable to store the parameter SafetyBaseID
SPI_SafetyStructureSignature_iUInt32Local variable to store the parameter SafetyStructureSignature
SPI_SafetyOperatorAckNecessary_iBooleanLocal variable to store the parameter SafetyOperatorAckNecessary
SPI_SafetyErrorIntervalLimit_iUInt16Local variable to store the parameter SafetyErrorIntervalLimit
MNR_re_sync_iBooleanLocal variable used to support re-synchronization of MNR after detected error
Timers
ConsumerTimerTimer

This timer is used to check whether the next valid ResponseSPDU has arrived on time. It is initialized using the parameter SPI.SafetyConsumerTimeout.

NOTE As opposed to other parameters, a modification of the parameter value SafetyConsumerTimeout takes effect immediately, i.e. not only when state S11 is visited, see RQ7.26.

ErrorIntervalTimerTimer

This timer is used to check the elapsed time between errors. If the elapsed time between two consecutive errors is smaller than the value SafetyErrorIntervalLimit, FSV will be activated. Otherwise, the ResponseSPDU is discarded and the SafetyConsumer waits for the next ResponseSPDU.

This timer is initialized using the local variable SPI_SafetyErrorIntervalLimit_i.

See Table 26, 6.3.4.3, and 9.4 for more information.

NOTE The local variable SPI_SafetyErrorIntervalLimit_i is not to be confused with the parameter SPI.SafetyErrorIntervalLimit. The local variable is copied from the parameter in state S11 (restart). Hence, if the parameter value changes during runtime, the new value will only be used after the connection has been restarted.

Macros <...><...>
<risingEdge x>Macro

// detection of a rising edge:

If x==true && tmp==false
Then
result:= true
Else
result:= false
Endif

tmp:= x

<Get ResponseSPDU>MacroInstruction to take the whole ResponseSPDU from the OPC UA Mapper.
<Use FSV> Macro

SAPI.SafetyData is set to binary 0

If [<ConsumerTimer expired || SAPI.Enable==0 ?>]
Then
SAPI.NonSafetyData is set to binary 0

Else
SAPI.NonSafetyData is set to ResponseSPDU.NonSafetyData

Endif

SAPI.FSV_Activated:= 1

RequestSPDU.Flags.FSV_Activated:= 1

NOTE 1 If a safety application prefers fail-safe values other than binary 0, this can be implemented in the safety application by querying SAPI.FSV_Activated.

NOTE 2 The NonSafetyData is always updated if data is available. In case of a timeout, no data is available, which is indicated using binary zero. If it is necessary for an application to distinguish between “no data available” and “binary zero received”, it can add a Boolean variable to the NonSafetyData. This value is set to ”1” during normal operation, and to ”0” for indicating that no data is available.

<Use PV>Macro

SAPI.SafetyData is set to ResponseSPDU.SafetyData

SAPI.NonSafetyData is set to ResponseSPDU.NonSafetyData

SAPI.FSV_Activated:= 0

RequestSPDU.Flags.FSV_Activated:= 0

RequestSPDU.Flags.CommunicationError:= 0

<Set RequestSPDU>MacroInstruction to transfer the whole RequestSPDU to the OPC UA Mapper.
<(Re)Start ConsumerTimer>MacroRestarts the ConsumerTimer.
<(Re)Start ErrorIntervalTimer>MacroRestarts the ErrorIntervalTimer.
<ConsumerTimer expired?>MacroYields “true” if the timer is running longer than SPI.SafetyConsumerTimeout since last restart, “false” otherwise.
<ErrorIntervalTimer expired?>MacroYields “true” if the timer is running longer than SPI.SafetyErrorIntervalLimit since last restart, “false” otherwise.
<Assign ConsumerID>Macro

If SAPI.SafetyConsumerID != 0

Then

ConsumerID_i:= SAPI.SafetyConsumerID

Else

ConsumerID_i:= SPI_SafetyConsumerID_i

Endif
RequestSPDU.SafetyConsumerID:= ConsumerID_i

<Calc SPDU_ID_i>Macro

uint128 BaseID

uint32 ProviderID

const uint32 SafetyProviderLevel_ID:= … // see 7.2.3.4

If(SAPI.SafetyBaseID == 0)

Then
BaseID:= SPI_SafetyBaseID_i
Else
BaseID:= SAPI.SafetyBaseID

Endif
If(SAPI.SafetyProviderID == 0)

Then
ProviderID:= SPI_SafetyProviderID_i
Else
ProviderID:= SAPI.SafetyProviderID

Endif

SPDU_ID_1_i:= BaseID (octets 0…3)
XOR SafetyProviderLevel_ID

SPDU_ID_2_i:= BaseID (octets 4…7)
XOR SPI_SafetyStructureSignature_i

SPDU_ID_3_i:= BaseID (octets 8…11)
XOR BaseID (octets 12…15)
XOR ProviderID

// see 7.2.3.2 for clarification

<ParametersOK?>Macro

Boolean result:= true
If(SAPI.SafetyBaseID == 0 && SPI_SafetyBaseID_i==0)
Then
result:= false
Else
Endif

If(SAPI.SafetyProviderID == 0 && SPI_SafetyProviderID_i==0)
Then
result:= false
Else
Endif

If(SAPI.SafetyConsumerID == 0 && SPI_SafetyConsumerID_i==0)
Then
result:= false
Else
Endif

If(SPI_SafetyStructureSignature_i==0)
Then
result:= false
Else
Endif

yield result

<Set Diag(ID,

Boolean isPermanent)>

Macro

// ID is the identifier for the type of diagnostic output, see Table 28.
// Parameter isPermanent is used to indicate a permanent error.
// Only one diagnostic message is created for multiple permanent
// errors in sequence

If(RequestSPDU.Flags.CommunicationError == 0)
Then
<do vendor-specific function for diagnostic output using ID>
Else
//do nothing
Endif

RequestSPDU.Flags.CommunicationError:= isPermanent
// NOTE See Table 28 for possible values for “ID” and their codes.

<ResponseSPDU
ready for checks>
Macro

Boolean result:= false

If MNR_re_sync_i == false

Then
If ResponseSPDU.MNR <> prevMNR_i

Then result:= true

Else
//do nothing
Endif

Else

If ResponseSPDU.MNR == MNR_i

Then result:= true

Else
//do nothing
Endif

Endif

yield result

<Handle WDTimeout>Macro

<Set Diag(CommErrTO,isPermanent:=true)>
<Use FSV>

If SPI_SafetyOperatorAckNecessary_i == 1
Then
FaultReqOA_i:= 1
SAPI.OperatorAckRequested:= 0
RequestSPDU.Flags.OperatorAckRequested:= 0
Else
// do nothing
Endif

External event
Restart cycleEventThe external call of SafetyConsumer can be interpreted as event “restart cycle”

Table 34 shows the states of the SafetyConsumer. The SafetyConsumer parameters are accessed only in state S11. In this state, a copy is made, and in all other states and transitions the copied values are used. This ensures that a change of one of these parameters takes effect only when a new safety connection is established. The only exception from this rule is the parameter SafetyConsumerTimeout. A change of this parameter becomes effective immediately (see RQ7.26). If this is not the desired behaviour, i.e. if parameters should be changeable during runtime, this can be accomplished by establishing a second safety connection according to this document with the new parameters, and then switching between these two safety connections at runtime.

Table 34 – SafetyConsumer states
State nameState description
Initialization

// Initial state of the SafetyConsumer instance.

<Use FSV>

SAPI.OperatorAckRequested:= 0
RequestSPDU.Flags.OperatorAckRequested:= 0
SAPI.OperatorAckProvider:= 0

FaultReqOA_i:= 0
OperatorAckConsumerAllowed_i:= 0
SAPI.TestModeActivated:= 0

RequestSPDU.Flags.CommunicationError:= 0

MNR_re_sync_i:= false

S11_Wait for (Re)Start

// Safety layer is waiting for (Re)Start

// Changes to these parameters are only considered in this state

// Exception: a change of SafetyConsumerTimeout is possible during operation

// Read parameters from the SPI and store them in local variables:

SPI_SafetyConsumerID_i:= SPI.SafetyConsumerID

SPI_SafetyProviderID_i:= SPI.SafetyProviderIDConfigured

SPI_SafetyBaseID_i:= SPI.SafetyBaseIDConfigured

SPI_SafetyStructureSignature_i:= SPI.SafetyStructureSignature

SPI_SafetyOperatorAckNecessary_i:= SPI.SafetyOperatorAckNecessary

SPI_SafetyErrorIntervalLimit_i:= SPI_SafetyErrorIntervalLimit

S12_initialize MNR

// Use previous MNR if known
// or random MNR within the allowed range (e.g. after cold start), see 9.2.

MNR_i:= (previous MNR_i if known) or (random MNR)

MNR_i:= max(MNR_i, MNR_min)1

S13_PrepareRequest// Build RequestSPDU and send (done in T16)
S14_WaitForChangedSPDU

// Safety Layer is waiting for next ResponseSPDU from SafetyProvider.

// A new ResponseSPDU is characterized by a change in the MNR.

S15_CRCCheckSPDU

// Check CRC

uint32 CRC_calc
CRCCheck_i:= (CRC_calc == ResponseSPDU.CRC)

// see 7.2.3.6 on how to calculate CRC_calc

S16_CheckResponseSPDU

// Check SafetyConsumerID and SPDU_ID and MNR (see T22, T23, T24)

SPDUCheck_i:=
ResponseSPDU.SPDU_ID_1 == SPDU_ID_1_i &&
ResponseSPDU.SPDU_ID_2 == SPDU_ID_2_i && ResponseSPDU.SPDU_ID_3 == SPDU_ID_3_i && ResponseSPDU.SafetyConsumerID == ConsumerID_i &&
ResponseSPDU.MNR == MNR_i

S17_ErrorSAPI.TestModeActivated:= 0
S18_ProvideSafetyData// Provide SafetyData to the application program
S19_SecondWDT_Check

// Second check of WDTimeout

// Prevents restarting of ConsumerTimer if it expired since initial check

1 This ensures that the MNR is greater or equal to MNR_min, in cases the random number generator yielded a smaller value.

Table 35 shows the transitions of the SafetyConsumer.

Table 35 – SafetyConsumer transitions
Tran
sition
Source stateTarget stateGuard conditionActivity
T12InitS11-
T13S11S12

//Start

[SAPI.Enable==1 && <ParametersOK?>]

<(Re)Start ErrorIntervalTimer>
<calc SPDU_ID_i>
// see 7.2.3.2 for clarification
T14S12S13// MNR initialized

<(Re)Start ConsumerTimer>

<Assign ConsumerID>

T15S18S11

// Termination

[SAPI.Enable==0]

<Use FSV>

RequestSPDU.Flags.CommunicationError:= 0

// necessary to make sure that no diagnostic

// message is lost, see macro <Set Diag ...>

// NOTE Depending on its implementation, it could

// be necessary to stop the ConsumerTimer here.

T16S13S14// Build RequestSPDU
// and send it

prevMNR_i:= MNR_i

If MNR_i == 0xFFFFFFFFF
Then
MNR_i:= MNR_min
Else

MNR_i:= MNR_i + 1
Endif

RequestSPDU.MonitoringNumber:= MNR_i

<Set RequestSPDU>

T17S14S15

// Changed ResponseSPDU
// is received1

<Get ResponseSPDU>2

<ResponseSPDU ready for checks>

// A changed ResponseSPDU is characterized by a change in the MNR.
T18S14S17

// WDTimeout

[<ConsumerTimer expired?>]

<Handle WDTimeout>
T19S15S13// When CRC err and ErrorIntervalTimer expired
[(crcCheck_i == 0) && <ErrorIntervalTimer expired?>]

MNR_re_sync_i:= true

<(Re)Start ErrorIntervalTimer>
<Set Diag(CRCerrIgn, isPermanent:=false)>

T20S15S17

// When CRC err and ErrorIntervalTimer not expired

[(crcCheck_i == 0) && not <ErrorIntervalTimer expired?>]

<(Re)Start ErrorIntervalTimer>
<Set Diag(CRCerrOA, isPermanent:=true)>
<Use FSV>

FaultReqOA_i:= 1
SAPI.OperatorAckRequested:= 0
RequestSPDU.Flags.OperatorAckRequested:= 0

T21S15S16

// When CRCCheckOK

[crcCheck_i == 1]

-
T22S16S18

// SPDU OK

[SPDUCheck_i==true]

// For clarification, refer to Figure 19;

MNR_re_sync_i:= false

// indicate OA from provider

SAPI.OperatorAckProvider:= ResponseSPDU.Flags.OperatorAckProvider

// OA requested due to rising edge at ActivateFSV?

If (<risingEdge ResponseSPDU.Flags.ActivateFSV>&& SPI_SafetyOperatorAckNecessary_i == true)
Then
FaultReqOA_i:= 1;
<Set Diag(FSV_Requested,isPermanent:=true)>
Else
// do nothing

Endif

// Set Flags if OA requested:

If FaultReqOA_i==1
Then
SAPI.OperatorAckRequested:= 1,
RequestSPDU.Flags.OperatorAckRequested:= 1,
OperatorAckConsumerAllowed_i:= 0,
FaultReqOA_i:= 0
Else
//do nothing
Endif

// Wait until OperatorAckConsumer is not active

If SAPI.OperatorAckConsumer==0

Then

OperatorAckConsumerAllowed_i:= 1

Else

//do nothing

Endif

// Reset Flags after OA:

If SAPI.OperatorAckConsumer ==1 && OperatorAckConsumerAllowed_i == 1

Then

SAPI.OperatorAckRequested:= 0, RequestSPDU.Flags.OperatorAckRequested:= 0
Else

// do nothing

Endif

If SAPI.OperatorAckRequested==1 || ResponseSPDU.Flags.ActivateFSV==1
Then <Use FSV>
Else <Use PV>
Endif

// Notify safety application that SafetyProvider is in test mode:

SAPI.TestModeActivated:= ResponseSPDU.Flags.TestModeActivated

T23S16S13// SPDU NOK and ErrorIntervalTimer expired

[SPDUCheck_i == false && <ErrorIntervalTimer expired?>]

<(Re)Start ErrorIntervalTimer>,

MNR_re_sync_i:= true

// Send diagnostic message according to the
// detected error:

If ResponseSPDU.SafetyConsumerID <> ConsumerID_i
Then <Set Diag(CoIDerrIgn, isPermanent:=false)>
Else
If ResponseSPDU.MNR<>MNR_i
Then <Set Diag(MNRerrIgn, isPermanent:=false)>
Else
//do nothing
EndIf
If
ResponseSPDU.SPDU_ID_1<> SPDU_ID_1_i ||
ResponseSPDU.SPDU_ID_2<> SPDU_ID_2_i ||
ResponseSPDU.SPDU_ID_3<> SPDU_ID_3_i
Then
<Set Diag(SD_IDerrIgn,

isPermanent:=false)>3
Else
// do nothing
Endif
Endif

T24S16S17

// SPDU NOK and ErrorIntervalTimer not expired


[SPDUCheck_i == 0 && not <ErrorIntervalTimer expired?>]

<(Re)Start ErrorIntervalTimer>
// Send diagnostic message according to the
// detected error:

If ResponseSPDU.SafetyConsumerID<> ConsumerID_i
Then <Set Diag(CoIDerrOA, isPermanent:=true)>
Else
If ResponseSPDU.MNR<>MNR_i
Then
<Set Diag(MNRerrOA,isPermanent:=true)>
Else
//do nothing
Endif
If ResponseSPDU.SPDU_ID_1<> SPDU_ID_1_i ||
ResponseSPDU.SPDU_ID_2<> SPDU_ID_2_i ||
ResponseSPDU.SPDU_ID_3<> SPDU_ID_3_i
Then <Set Diag(SD_IDerrOA,isPermanent:=true)>
Else
//do nothing
Endif
Endif

FaultReqOA_i:= 1

SAPI.OperatorAckRequested:= 0
RequestSPDU.Flags.OperatorAckRequested:= 0
<Use FSV>

T25S17S18

// SPDU NOK

-

MNR_re_sync_i:= true
T26S18S19

// Restart Cycle

[SAPI.Enable==1]

-
T27S11S11

// Invalid parameters

[SAPI.Enable==1 && not <ParametersOK?>]

<Set Diag(ParametersInvalid, isPermanent:=true)>
T28S19S13// No WDTimeout<(Re)Start ConsumerTimer>
T29S19S17

// WDTimeout

[<ConsumerTimer expired?>]

<Handle WDTimeout>

1 Another event like “Method completion successful” can be used as guard condition of “Changed ResponseSPDU received” as well.

2 SPDUs with all values (incl. CRC signature) being zero shall be ignored, see requirement RQ5.6.

3 See Table 28.

7.2.2.6 SafetyConsumer sequence diagram for operator acknowledgment (informative)

Figure 19 shows the sequence after the detection of an error requiring operator acknowledge until communication returns to delivering process values again.

Figure 19 – Sequence diagram for OA

After the error is gone the sequence follows the logic of T22 in Table 35.