8 OPC UA EventTypes8.1 MaintenanceRequestedConditionType ObjectType DefinitionThe MaintenanceRequestedConditionType is sent when the manufacturer wants to inform the operator that the system requires maintenance. The condition is also sent when the maintenance is no longer required. It is formally defined in Table 83 .
Table 83 – MaintenanceRequestedConditionType Definition
Attribute
Value
BrowseName MaintenanceRequestedConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the AcknowledgeableConditionType defined in OPC 10000-9 0:HasProperty Variable Requested 0:Boolean 0:PropertyType M,R
The property Requested reflects the value of the MaintenanceRequested property of the object from which the event originates at the time the event was sent.
8.2 MaintenanceSwitchConditionType ObjectType DefinitionThe MaintenanceSwitchConditionType is sent when the physical maintenance switch is toggled. It is formally defined in Table 84 .
Table 84 – MaintenanceSwitchConditionType Definition
Attribute
Value
BrowseName MaintenanceSwitchConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the ConditionType defined in OPC 10000-9 0:HasProperty Variable SwitchOn 0:Boolean 0:PropertyType M,R
The property SwitchOn reflects the value of the MaintenanceSwitchOn property of the object from which the event originates at the time the event was sent.
8.3 MalfunctionAlarmType ObjectType DefinitionThe MalfunctionAlarmType is sent when the component has an error that may prevent it from operating. The type of the error depends on the specific component that emits the alarm. This specification does not specify the details of the error in a standardized way. It is formally defined in Table 85 .
Table 85 – MalfunctionAlarmType Definition
Attribute
Value
BrowseName MalfunctionAlarmType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the OffNormalAlarmType defined in OPC 10000-9
8.4 DischargeContainerInstalledConditionType ObjectType DefinitionThe DischargeSystemType sends an event of type DischargeContainerInstalledConditionType when the container is installed or removed. It is formally defined in Table 86 .
Table 86 – DischargeContainerInstalledConditionType Definition
Attribute
Value
BrowseName DischargeContainerInstalledConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the ConditionType defined in OPC 10000-9 0:HasProperty Variable Installed 0:Boolean 0:PropertyType M,R
The property Installed reflects the value of the DischargeContainerInstalled property of the DischargeSystemType at the time the event was sent.
8.5 WashingAgentInflowOpenConditionType ObjectType DefinitionThe WashingAgentInflowOpenConditionType is triggered when the washing agent inflow valve is opened or closed. It is formally defined in Table 87 .
Table 87 – WashingAgentInflowOpenConditionType Definition
Attribute
Value
BrowseName WashingAgentInflowOpenConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the ConditionType defined in OPC 10000-9 0:HasProperty Variable Open 0:Boolean 0:PropertyType M,R
The property Open reflects the value of the WashingAgentInflowOpen property of the WetSeparatorType at the time the event was sent.
8.6 WashingAgentInflowMalfunctionAlarmType ObjectType DefinitionThe WashingAgentInflowMalfunctionAlarmType event is triggered when an error occurs on the washing agent inflow. It is formally defined in Table 88 .
Table 88 – WashingAgentInflowMalfunctionAlarmType Definition
Attribute
Value
BrowseName WashingAgentInflowMalfunctionAlarmType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the OffNormalAlarmType defined in OPC 10000-9
8.7 WashingAgentDrainOpenConditionType ObjectType DefinitionThe WashingAgentDrainOpenConditionType is triggered when the washing agent drain valve is opened or closed. It is formally defined in Table 89 .
Table 89 – WashingAgentDrainOpenConditionType Definition
Attribute
Value
BrowseName WashingAgentDrainOpenConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the ConditionType defined in OPC 10000-9 0:HasProperty Variable Open 0:Boolean 0:PropertyType M,R
The property Open reflects the value of the WashingAgentDrainOpen property of the WetSeparatorType at the time the event was sent.
8.8 WashingAgentDrainMalfunctionAlarmType ObjectType DefinitionThe WashingAgentDrainMalfunctionAlarmType is triggered when an error occurs on the washing agent drain. It is formally defined in Table 90 .
Table 90 – WashingAgentDrainMalfunctionAlarmType Definition
Attribute
Value
BrowseName WashingAgentDrainMalfunctionAlarmType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the OffNormalAlarmType defined in OPC 10000-9
8.9 EndOfFilterRollAlarmType ObjectType DefinitionThe EndOfFilterRollAlarmType is triggered when the automatic roll filter reaches the end of the filter roll. It is formally defined in Table 91 .
Table 91 – EndOfFilterRollAlarmType Definition
Attribute
Value
BrowseName EndOfFilterRollAlarmType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the OffNormalAlarmType defined in OPC 10000-9
8.10 HighVoltageUnitSupplyActiveEventType ObjectType DefinitionThe HighVoltageUnitSupplyActiveEventType is triggered when the high voltage unit supply is activated or deactivated. it is formally defined in Table 92 .
Table 92 – HighVoltageUnitSupplyActiveEventType Definition
Attribute
Value
BrowseName HighVoltageUnitSupplyActiveEventType IsAbstract True
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the BaseEventType defined in OPC 10000-9 0:HasProperty Variable Active 0:Boolean 0:PropertyType M,R
The property Active reflects the value of the SupplyActive property of the HighVoltageUnitType at the time the event was triggered.
8.11 ContainerOpenConditionType ObjectType DefinitionThe ContainerNotClosedConditionType is triggered when the filter aid reservoir is opened or closed. It is formally defined in Table 93 .
Table 93 – ContainerOpenConditionType Definition
Attribute
Value
BrowseName ContainerOpenConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the ConditionType defined in OPC 10000-9 0:HasProperty Variable Open 0:Boolean 0:PropertyType M,R
The property Open reflects the value of the ContainerOpen property of the FilterAidDeviceType at the time the condition was triggered.
8.12 CompressedAirSupplyInterruptedAlarmType ObjectType DefinitionThe CompressedAirSupplyInterruptedAlarmType is triggered when the compressed air supply is interrupted. It is formally defined in Table 94 .
Table 94 – CompressedAirSupplyInterruptedAlarmType Definition
Attribute
Value
BrowseName CompressedAirSupplyInterruptedAlarmType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the OffNormalAlarmType defined in OPC 10000-9
8.13 FilterAidDeviceStatusChangedConditionType ObjectType DefinitionThe FilterAidDeviceStatusChangedConditionType is triggered when the FilterAidDeviceStatus of the FilterAidDeviceType changes. It is formally defined in Table 95 .
Table 95 – FilterAidDeviceStatusChangedConditionType Definition
Attribute
Value
BrowseName FilterAidDeviceStatusChangedConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the ConditionType defined in OPC 10000-9 0:HasProperty Variable Status FilterAidDeviceStatusEnum 0:PropertyType M,R
The property Status reflects the value of the FilterAidDeviceStatus property at the time the condition was triggered.
8.14 CleaningUnitActiveConditionType ObjectType DefinitionThe CleaningUnitActiveConditionType is triggered when a cleaning cycle is started or stopped. It is formally defined in Table 96 .
Table 96 – CleaningUnitActiveConditionType Definition
Attribute
Value
BrowseName CleaningUnitActiveConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the ConditionType defined in OPC 10000-9 0:HasProperty Variable Active 0:Boolean 0:PropertyType M,R
The property Active reflects the value of the CleaningActive property of the CleaningUnitType at the time the condition was triggered.
8.15 CleaningRecommendedConditionType ObjectType DefinitionThe CleaningRecommendedConditionType is triggered by the cleaning unit when cleaning of the separator is recommended. It is formally defined in Table 97 .
Table 97 – CleaningRecommendedConditionType Definition
Attribute
Value
BrowseName CleaningRecommendedConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the AcknowledgeableConditionType defined in OPC 10000-9 0:HasProperty Variable Recommended 0:Boolean 0:PropertyType M,R
The Recommended property reflects the value of the property CleaningRecommended of the CleaningUnitType .
8.16 AirConnectionStatusChangedConditionType ObjectType DefinitionThe AirConnectionStatusChangedConditionType is triggered when the ConnectionOpen variable of the AirConnectionType changes. It is formally defined in Table 98 .
Table 98 – AirConnectionStatusChangedConditionType Definition
Attribute
Value
BrowseName AirConnectionStatusChangedConditionType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the ConditionType defined in OPC 10000-9 0:HasProperty Variable Status AirConnectionOpenEnum 0:PropertyType M,R
The Status property reflects the value of the ConnectionOpen property at the time the event is triggered.
8.17 SafetySystemTriggeredAlarmType ObjectType DefinitionThe SafetySystemTriggeredAlarmType is sent when the safety system is triggered. It is formally defined in Table 99 .
Table 99 – SafetySystemTriggeredAlarmType Definition
Attribute
Value
BrowseName SafetySystemTriggeredAlarmType IsAbstract False
References
Node Class
BrowseName
DataType
TypeDefinition
Other
Subtype of the OffNormalAlarmType defined in OPC 10000-9