7.7.1 Overview

The AirConnectionType is a non-tangible component representing the state of a connection from the ducting system to a filter unit. The connection can be open or closed. The open state represents a state of the ducting system where air can pass through to the filter unit.

It is formally defined in Table 40.

Table 40 – AirConnectionType Definition
Attribute Value
BrowseNameAirConnectionType
IsAbstractFalse
References Node Class BrowseName DataType TypeDefinition Other
Subtype of the BaseObjectType defined in OPC 10000-5
0:HasComponentObjectHumiditySensorMonitoringTypeO
0:HasComponentObjectTemperatureSensorMonitoringTypeO
0:HasComponentObjectAirflowSensorMonitoringTypeO
0:HasComponentObjectGasQualitySensorMonitoringTypeO
0:HasComponentObjectPressureSensorMonitoringTypeO
0:HasPropertyVariableConnectionOpenAirConnectionOpenEnum0:PropertyTypeO,R
0:HasPropertyVariableMalfunction0:Boolean0:PropertyTypeO,R
0:HasComponentMethodOpenO
0:HasComponentMethodCloseO
0:GeneratesEventObjectTypeMalfunctionAlarmType
0:GeneratesEventObjectTypeAirConnectionStatusChangedConditionType
Conformance Units
PAEFS AirConnectionType Basic
PAEFS AirConnectionType Advanced
PAEFS AirConnectionType Events
PAEFS AirConnectionType Methods
Table 41 – AirConnectionType Attribute values for child nodes
BrowsePath Attribute Description
HumidityValue of the humidity sensor
TemperatureValue of the temperature sensor
AirflowValue of the air flow sensor
GasQualityValue of the gas quality sensor
PressureValue of the pressure sensor
ConnectionOpenIndicates the connections status (open, closed, or a state in between)
MalfunctionIndicates that the AirConnection is malfunctioning, i.e., an error occurs in a component that provides functionality for this abstract component; e.g., an error in the ducting system or a valve. True in case of error.

The Open and Close Methods can be called to open or close the connection. In a complex ducting system that consists of a network of joints and junctions, opening or closing the connection may involve switching multiple valves.

The control logic for switching the state of the ducting system is determined by the server implementation.

The air connection may contain optional sensors for humidity, temperature, air flow, gas quality, and air pressure.

The server sends a MalfunctionAlarmType event when the Malfunction property changes.

The AirConnectionStatusChangedConditionType event is triggered when the ConnectionOpen property changes.