7.6.3 SetAndActivatePressureSetpoint Method

The Method SetAndActivatePressureSetpoint sets a setpoint for the pressure. The value’s unit is the same as the one specified in object Pressure. Since setpoints are mutually exclusive, the method also sets the boolean IsActiveSetpoint of the setpoints for airflow and rotational speed to false. The signature of this Method is specified below.

Table 34 and Table 35 specify the Arguments and AddressSpace representation, respectively.

Signature

	SetAndActivatePressureSetpoint (
		[in]	0:Double	Value)
Table 34 – SetAndActivatePressureSetpoint Method Arguments
Argument Description
ValueNew setpoint value
Table 35 – SetAndActivatePressureSetpoint Method AddressSpace Definition
Attribute Value
BrowseNameSetAndActivatePressureSetpoint
References Node Class BrowseName DataType TypeDefinition ModellingRule
0:HasPropertyVariable0:InputArguments0:Argument[]0:PropertyType0:Mandatory
Conformance Units
PAEFS FilterUnit Pressure Setpoint