10.19 PumpControlMode

Description:Defines to which setpoint or function the pump is controlled. The TypeDefinition is MultiStateValueDiscreteType, so the Properties EnumValues and ValueAsText must be filled with the supported values out of Table 9.
Table 9 – Values for PumpControlMode
EnumValue ValueAsText Description
0NORMALNormal Operation: fixed pump rotational speed
1AUTOAutomatic adjustment of the pump rotational speed
2SPEEDSpeed controlled: the pump is controlled according to the specified nominal value PumpSpeed
3FLOWFlow rate controlled: the pump is controlled according to the specified nominal value FlowRate
4TEMP_DIFFTemperature difference controlled: the pump is controlled according to the specified nominal value TemperatureDifference
5PRESS_DIFFPressure difference controlled: the pump is controlled according to the specified nominal value PressureDifference
6BOOSTBoost mode: the pump is operated at the maximum possible rotational pump speed