8.1.1.2 SwitchToEnergySavingMode Method
This Method initiates a switch to a certain Energy Saving Mode.
Signature
SwitchToEnergySavingMode (
[in] 0:Byte ModeID
[out] 0:Byte EffectiveModeID
[out] 0:Duration CurrentTimeToDestination
[out] 0:Duration RegularTimeToOperate
[out] 0:Duration TimeMinLengthOfStay
[out] 0:Byte ReturnCode
);
| Argument | Description |
| ModeID | ID of the requested Energy Saving Mode. |
| EffectiveModeID | ID of the effectively chosen Energy Saving Mode if successful, otherwise ID of current mode. |
| CurrentTimeToDestination | Time needed to reach the destination Energy Saving Mode if successful, otherwise 0. |
| RegularTimeToOperate | Time needed to reach “Ready to operate” again if the destination Energy Saving Mode will be regularly terminated if successful, otherwise 0. |
| TimeMinLengthOfStay | Time of minimum stay in the destination Energy Saving Mode if successful, otherwise 0. |
| ReturnCode | Return code. See table Table 16. |
The Method Result Codes (defined in Call Service) are defined in Table 15.