The EnergyMeasurementType contains References to MeasurementValueType Objects.

Table 20 – EnergyMeasurementType Definition

Attribute

Value

BrowseName

EnergyMeasurementType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType

0:HasProperty

Variable

PeObjectNumber

0:UInt16

0:PropertyType

M, RO

0:HasComponent

Variable

<MeasurementValue>

0:Number

MeasurementValueType

MP, RO

0:HasComponent

Method

ResetEnergyCounter

O

The PeObjectNumber Variable shall contain the Object number of the related PROFIenergy measurement Object.

The MeasurementValue Variable contains one actual measurement value. For each measurement value of a Metering Point one MeasurementValueType Variable shall exist.

If one of the MeasurementValueType Variables is used as energy counter, the ResetEnergyCounter Method can be used to set the value of this Variable to 0. See section 9.1, ”MeasurementValueType” for further details.

A RepresentedBy Reference may connect the Object to the representing PROFIenergy service access point Object (see PeServiceAccessPointType). The BrowseName of the Reference shall be “PESAP”. If the PESAP is not part of the Information Model, the RepresentedBy Reference in the EnergyMeasurementType Object is omitted.

Mapping to PROFIenergy properties:

BrowseName

PE Service

PE Service Data Response Field

PeObjectNumber

Get_Measurement_List_with_Object_Number

Object_Number