The EnergyStandbyManagementType ObjectTypes provide access to the Standby Management functionality of one Standby Management Entity. Parallel access of Clients to the read only data shall be possible but write operations and Method invocation can be limited to one Client at a time with the Lock Object.
Table 12 – EnergyStandbyManagementType Definition
Attribute |
Value |
||||
BrowseName |
EnergyStandbyManagementType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the BaseObjectType defined in [OPC 10000-5]. |
|||||
0:HasComponent |
Variable |
StandbyManagementStatus |
Byte |
0:MultiStateDiscreteType |
M, RO |
0:HasComponent |
Object |
EnergySavingModeStatus |
|
EnergySavingModeStatusType |
M |
0:HasComponent |
Object |
EnergySavingModes |
|
EnergySavingModesContainerType |
O |
0:HasComponent |
Variable |
PauseTime |
0:Duration |
0:BaseDataVariableType |
M, RW |
0:HasComponent |
Object |
2:Lock |
|
2:LockingServicesType |
O |
0:HasComponent |
Method |
StartPause |
|
O |
|
0:HasComponent |
Method |
EndPause |
|
O |
|
0:HasComponent |
Method |
SwitchToEnergySavingMode |
|
O |
The StandbyManagementStatus Variable shall contain the current state of the Standby Management. The value of this Variable shall be consistent with the content of the EnergySavingModeStatus Object.
The values of the 0:EnumStrings of the StandbyManagementStatus shall follow the definition of Table 13. Each instance shall have the values 0 to 8. Element numbers 9-15 are reserved for future use. If vendors add specific elements, the range 9-15 shall be filled with ‘null’-strings.
Table 13 – Defined elements of EnumStrings array of StandbyManagementStatus Variable
Element number (starting with 0) |
Message (for locale “en”) |
0 |
Energy saving disabled |
1 |
Power Off |
2 |
Ready to operate |
3 |
Moving to Energy Saving Mode |
4 |
Energy saving mode |
5 |
Moving to ready to operate |
6 |
Moving to Sleep mode WOL |
7 |
Sleep mode WOL |
8 |
Wake up WOL |
9-15 |
‘null’-String |
16 – 255 |
Vendor specific |
The Variables of the EnergyStandbyManagementType have additional Attributes defined in Table 14
Table 14 – EnergyStandbyManagementType Attribute values for child Nodes
Source Path |
Value Attribute |
||
|
Energy saving disabled Power Off Ready to operate Moving to Energy Saving Mode Energy saving mode Moving to ready to operate Moving to Sleep mode WOL Sleep mode WOL Wake up WOL |
The EnergySavingModes container Object contains References to EnergySavingModeType Objects representing the supported Energy Saving Modes.
Writing the PauseTime Variable can be used to update the pause time alternatively to the StartPause Method. Setting the PauseTime Variable with a value not equal to 0 shall have the same effect as invoking the StartPause Method passing the PauseTime value. Setting the PauseTime Variable with a value equal to 0 shall have the same effect as invoking the EndPause Method. An additional benefit is that the Variable PauseTime can be used in a PubSub communication scenario where the PauseTime is distributed by a central time management client using a broadcast telegram to which every Standby Management Entity subscribes.
The Lock Object ensures exclusive write access and Method call for one client. Write access and Method calls from Clients shall be blocked unless the client has locked the Object by invoking the InitLock Method of the Lock Object.
The StartPause Method starts the transition to an Energy Saving Mode. The SwitchToEnergySavingMode allows the transition into a specific Energy Saving Mode. The EndPause Method ends the Energy Saving Mode.
A RepresentedBy Reference may connect the Object to the representing PROFIenergy service access point Object (see PeServiceAccessPointType). The BrowseName of the Reference shall be “PESAP”.
This Method starts the transition into an Energy Saving Mode.
Signature
StartPause (
[in] 0:DurationPauseTime
[out] 0:Byte ModeID
[out] 0:DurationCurrentTimeToDestination
[out] 0:DurationRegularTimeToOperate
[out] 0:DurationTimeMinLengthOfStay
[out] 0:Byte ReturnCode
);
Argument |
Description |
PauseTime |
Requested pause time. |
ModeID |
ID of the destination Energy Saving Mode if successful, otherwise 0. |
CurrentTimeToDestination |
Time needed to reach the Energy Saving Mode if successful, otherwise 0. |
RegularTimeToOperate |
Time needed to reach “Ready to operate” again if the destination Energy Saving Mode will be regularly terminated if successful, otherwise 0. |
TimeMinLengthOfStay |
Time of minimum stay in the destination Energy Saving Mode if successful, otherwise 0. |
ReturnCode |
Return code. See Table 16. |
The Method Result Codes (defined in Call Service) are defined in Table 15.
This Method initiates a switch to a certain Energy Saving Mode.
Signature
SwitchToEnergySavingMode (
[in] 0:Byte ModeID
[out] 0:Byte EffectiveModeID
[out] 0:DurationCurrentTimeToDestination
[out] 0:DurationRegularTimeToOperate
[out] 0:DurationTimeMinLengthOfStay
[out] 0:Byte ReturnCode
);
Argument |
Description |
ModeID |
ID of the requested Energy Saving Mode. |
EffectiveModeID |
ID of the effectively chosen Energy Saving Mode if successful, otherwise ID of current mode. |
CurrentTimeToDestination |
Time needed to reach the destination Energy Saving Mode if successful, otherwise 0. |
RegularTimeToOperate |
Time needed to reach “Ready to operate” again if the destination Energy Saving Mode will be regularly terminated if successful, otherwise 0. |
TimeMinLengthOfStay |
Time of minimum stay in the destination Energy Saving Mode if successful, otherwise 0. |
ReturnCode |
Return code. See table Table 16. |
The Method Result Codes (defined in Call Service) are defined in Table 15.
This Method ends the current Energy Saving Mode.
Signature
EndPause (
[out] 0:DurationCurrentTimeToOperate
[out] 0:Byte ReturnCode
);
Argument |
Description |
CurrentTimeToOperate |
Time needed to reach “Ready to operate” if successful, 0. |
ReturnCode |
Return code. See table Table 16. |
The Method Result Codes (defined in Call Service) are defined in Table 15.
Table 15 shows the possible values for the Method call result codes.
Table 15 – Possible Method result codes
Result Code |
Description |
Good |
The Method execution was successful and the ReturnCode parameter has the value 0x00 (”Success”) |
Uncertain |
The Method execution was successful, but the ReturnCode parameter indicates an error. |
Bad_UserAccessDenied |
The user has not the right to execute the Method. The client shall not evaluate the ReturnCode parameter. |
Bad_UnexpectedError |
The server is not able to execute the function because an unexpected error occurred. The device might be temporarily unavailable or unreachable due to network failure. The client shall not evaluate the ReturnCode parameter. |
Table 16 shows the possible values for the out parameter ReturnCode.
Table 16 – Possible ReturnCode parameter Values
ReturnCode |
Description |
0x00 |
Success. |
0x50 |
No suitable energy-saving mode available. |
0x52 |
No switch to requested energy-saving mode because of invalid mode ID. |
0x53 |
No switch to Energy Saving Mode because of state operate. |
0x54 |
Service or function not available due to internal device status. |
Table 17 – EnergySavingModesContainerType Definition
Attribute |
Value |
||||
BrowseName |
EnergySavingModesContainerType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the BaseObjectType defined in [OPC 10000-5]. |
|||||
0:HasComponent |
Object |
<EnergySavingModes> |
|
EnergySavingModeType |
MP |
Table 18 – EnergySavingModeStatusType Definition
Attribute |
Value |
||||
BrowseName |
EnergySavingModeStatusType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the BaseObjectType defined in [OPC 10000-5]. |
|||||
0:HasComponent |
Variable |
CurrentTransitionData |
StandbyModeTransitionDataType |
0:BaseDataVariableType |
O, RO |
0:HasComponent |
Variable |
StateInformation |
EnergyStateInformationDataType |
0:BaseDataVariableType |
M, RO |
The CurrentTransitionData Variable contains details for the state transition indicated by the StateInformation Variable.
The StateInformation Variable contains details for the actual Energy Saving Mode state.
The EnergySavingModeType provides detailed information for a specific Energy Saving Mode.
Table 19 – EnergySavingModeType Definition
Attribute |
Value |
||||
BrowseName |
EnergySavingModeType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the BaseObjectType defined in [OPC 10000-5]. |
|||||
0:HasProperty |
Variable |
ID |
0:Byte |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
DynamicData |
0:Boolean |
0:PropertyType |
M, RO |
0:HasComponent |
Variable |
TimeMinPause |
0:Duration |
0:BaseDataVariableType |
M, RO |
0:HasComponent |
Variable |
TimeToPause |
0:Duration |
0:BaseDataVariableType |
M, RO |
0:HasComponent |
Variable |
TimeMinLengthOfStay |
0:Duration |
0:BaseDataVariableType |
M, RO |
0:HasComponent |
Variable |
TimeMaxLengthOfStay |
0:Duration |
0:BaseDataVariableType |
M, RO |
0:HasComponent |
Variable |
RegularTimeToOperate |
0:Duration |
0:BaseDataVariableType |
M, RO |
0:HasComponent |
Variable |
ModePowerConsumption |
0:Float |
0:AnalogUnitType |
M, RO |
0:HasComponent |
Variable |
EnergyConsumptionToPause |
0:Float |
0:AnalogUnitType |
M, RO |
0:HasComponent |
Variable |
EnergyConsumptionToOperate |
0:Float |
0:AnalogUnitType |
M, RO |
The BrowseName shall contain a unique name for the Energy Saving Mode.
The ID Variable shall contain a unique mode ID for the Energy Saving Mode. The mode ID’s 0x00, 0xF0, 0xFE and 0xFF are reserved for predefined states.
DynamicData shall indicate whether the time, energy consumption and power values can vary (slightly) during runtime.
The TimeMinPause Variable shall contain the minimum pause time for this Energy Saving Mode.
The TimeToPause Variable shall contain the expected time to switch to this Energy Saving Mode.
The TimeMinLengthOfStay Variable shall contain the time of minimum stay in this Energy Saving Mode.
The TimeMaxLengthOfStay Variable shall contain the time of maximum stay in this Energy Saving Mode.
The RegularTimeToOperate Variable shall contain the time value to reach ”Ready to operate” (see Figure 1) if this Energy Saving Mode will be regularly terminated.
The ModePowerConsumption Variable shall contain the power consumption in this Energy Saving Mode. Unit: [kW].
The EnergyConsumptionToPause Variable shall contain the energy consumption from ”Ready to operate” to this Energy Saving Mode. Unit: [kWh].
The EnergyConsumptionToOperate Variable shall contain the energy consumption from this Energy Saving Mode to ”Ready to operate”. Unit: [kWh].
Mapping to PROFIenergy properties:
BrowseName |
PE Service |
PE Service Data Response Field |
List_Energy_Saving_Modes |
PE_Mode_ID |
|
Get_Mode |
Time_min_Pause |
|
Get_Mode |
Time_to_Pause |
|
Get_Mode |
Time_min_length_of_stay |
|
Get_Mode |
Time_max_length_of_stay |
|
Get_Mode |
Regular_time_to_operate |
|
Get_Mode |
Mode_Power_Consumption |
|
Get_Mode |
Energy_Consumption_to_pause |
|
Get_Mode |
Energy_Consumption_to_operate |