B.1 Recommendation for unique EventCodes for Encoder devices

Table 110 contains unique EventCode definitions for encoders (taken out of ENCP table 54). These unique EventCodes may be used for the VendorEventCode in the log entry instead of a proprietary vendor specific event code definition.

Table 110 - Encoder EventCodes definition
EventCodeEvent nameDescription
100Position error (hardware and signal quality)Fault: Error and malfunction of the encoder position measurement system or the measured value processing unit.
101Position error (frequency/speed exceeded)Fault: A temporary failure in the evaluation of the measurement system due to excessive speed was detected.
102Position inconsistent (for incremental encoders only)Fault: A failure in the counting of increments of the measurement system was detected.
103Safety exceptionFault: An exception (internal event) in the encoder safety process was detected.
104Safety parameterisationFault: An exception because of wrong iParameter in the encoder safety process was detected.
105Commissioning diagnosticsFault: The encoder application process is not operative/working because of a commissioning error (invalid encoder parameter set).
106Commissioning invalid scalingFault: The encoder application process is not operative/working because of a commissioning error (invalid encoder parameter set related to the scaling parameters).
107Invalid parameter setup in RAMWarning: The writing of encoder configuration parameters via the BMP parameter access mechanism has caused an invalid parameter set.
108Communication

Fault: A fault in the communication with the controller (Application Relationship) was detected (IOAR not working any more or cancelled).

Warning: The quality of the cyclic communication service (e.g. because of excessive number of package drops) is fallen below a dedicated (vendor specific) limit.

109Safety CommunicationFault: A fault in the PROFIsafe communication with the safety controller (PROFIsafe driver level) was detected (PROFIsafe communication is not working any more or cancelled).
110Synchronisation fault (isochronous operation only)

Fault: A synchronisation fault in the Isochronous Mode ASE was detected (PLL window error occurred). If a telegram with life sign monitoring is used the additional fault "Masters sign of life fault" is also expected.

Warning: The quality of the synchronisation (e.g. PLL-deviation) is fallen below a dedicated (vendor specific) limit.

111Master's sign of life fault

Fault: A master sign of life evaluation error was detected.

Warning: The master sign of life failure counter exceeded a dedicated (vendor specific) warning level.

112OverspeedWarning: A critical speed limit for the encoder was exceeded. Operation of the encoder beyond this speed limit may cause position and speed acquisition errors or may damage the encoder mechanical system.
113Preset failed (speed to high)Warning: While requesting the preset set or shift to home position functionality (all classes) the speed was to high to execute the preset functionality. Therefore the encoder didn't executed the preset functionality but generated this fault message.
114Preset failed (preset value out of range)Warning: While requesting the preset set or shift to home position functionality (all classes) the chosen preset or shift value was out of valid value range. Therefore the encoder didn't execute the preset or shift functionality but generated this fault message.
115Command not supportedWarning: The activation of a not supported function/command was detected (encoder state machine).
116Undervoltage

Fault: Fault because of an undervoltage situation at the supply line (typically 24V supply) which caused the breakdown of the internal power supply of the encoder.

Warning: An undervoltage limit at the supply line (typically 24V supply) was exceeded but the internal power supply of the encoder is still working.

117Overvoltage

Fault: Fault because of an overvoltage situation at the supply line (typically 24V supply) which caused the breakdown of the internal power supply of the encoder.

Warning: An overvoltage limit at the supply line (typically 24V supply) was exceeded but the internal power supply of the encoder is still working.

118Short circuit

Fault: A short circuit situation was detected with components which are attached to the Encoder device (e.g. external measurement device, digital IOs, probe devices, external switches, …) and this situation causes the malfunction of an active encoder functionality.

Warning: A short circuit situation was detected with components which are attached to the Encoder device (e.g. external measurement device, digital IOs, probe devices, external switches, …) and this situation currently has no influence on the active encoder functionality.

119Overtemperature

Fault: A critical temperature level for the encoder was exceeded. Proper operation of the encoder under this temperature condition can't be guarantied because of malfunction of the position and speed acquisition mechanism.

Warning: A critical temperature level for the encoder was exceeded. Operation of the encoder beyond this temperature limit may cause position and speed acquisition errors or may damage the encoder permanently.

120Excessive Vibration

Fault: A critical level of vibration for the encoder was exceeded. Proper operation of the encoder under this vibration condition can't be guarantied because of malfunction of the position and speed acquisition mechanism.

Warning: A critical level for vibration for the encoder was exceeded. Operation of the encoder beyond this vibration limit may cause position and speed acquisition errors or may damage the encoder permanently.

121CPU Watchdog triggeredWarning: Because of an abnormal condition a reboot of the CPU and runtime system of the encoder was detected.
122Memory errorFault: During the startup of the device or during operation of the device internal memory, a memory fault was detected and the encoder application process was stopped or not started (actual values are invalid).
123Operating time limit

Fault: A critical limit for the encoder life time due to degradation of critical components of the encoder system was exceeded. The encoder is no longer operational and has to be replaced now.

Warning: A critical limit for the encoder life time due to degradation of critical components of the encoder system was exceeded. The remaining life time for the encoder is at its minimum and the encoder device should be replaced now.

124Battery voltage

Fault: A critical limit for the battery power level due to life time degradation of the battery system was exceeded. Some functions of the encoder are not available any more (absolute position). The battery of the encoder has to be replaced now.

Warning: A critical limit for the battery power level due to life time degradation of the battery system was exceeded. The remaining life time for the battery is at its minimum and the battery of the encoder should be replaced now.

199Currently
…Not
999PAssigned, reserved for future Encoder EventCodes