8.1.2 ICharacteristicsMotorAndControlElectric Interface
The ICharacteristicsMotorAndControlElectric Interface specifies the Variables representing electric properties which are components of the CharacteristicsMotorAndControl Folder. Instances of the CharacteristicsMotorAndControl folder shall reference this InterfaceType if the containing Powertrain Axis Object represents an electric Drive.
| Attribute | Value | ||||
| BrowseName | ICharacteristicsMotorAndControlElectric | ||||
| IsAbstract | True | ||||
| References | Node Class | BrowseName | DataType | TypeDefinition | Other |
|---|---|---|---|---|---|
| Subtype of the 0:BaseInterfaceType defined in OPC 10000-5. | |||||
| 0:HasComponent | Variable | MotorDcBrakingCurrent | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | DcBrakingTime | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | MotorMaxCurrent | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | MotorPeakCurrentConfigured | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | MotorRunUpVoltage | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | MotorThermalLoadLimitConfigured | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasProperty | Variable | MotorUfRatio | 0:Float | 0:PropertyType | O, RO |
| 0:HasComponent | Variable | TimePeriodCurrentControl | 0:Float | 0:AnalogUnitType | O, RO |
| Conformance Units | |||||
|---|---|---|---|---|---|
| Powertrain Actual and Command Values |
The MotorDcBrakingCurrent Variable contains the DC-current applied to the motor during braking.
The DcBrakingTime Variable contains the time needed in DC-braking mode until stand still if the braking current given by the MotorDcBrakingCurrent Variable is applied.
The MotorMaxCurrent Variable contains the maximum current the motor draws from the power supply.
The MotorPeakCurrentConfigured Variable contains the peak current of motor determined by configuration data.
The MotorRunUpVoltage Variable contains the voltage the motor creates at the feeder clamp during start-up.
The MotorThermalLoadLimitConfigured Variable contains the thermal load limit of motor determined by configuration data.
The MotorUfRatio Property contains the constant ratio of voltage and frequency.
The TimePeriodCurrentControl Variable contains the time period for calculation of current control.