OPC UA for the Powertrain - Part 2: Functional Model
11.4 PtEventClassEnumeration
This enumeration contains detailed information for a fault or warning. The values specified for future use may not be used by Servers.
Table 100 - PtEventClassEnumeration Items
Name
Value
Description
UNSPECIFIED
0
Unspecified. May be used for the EventClass parameter of the PtLogbookType GetFilteredLogbookEntries Method only.
MICROCONTROLLER_HARDWARE_OR_SOFTWARE
1
Comprises exceptions in the main CPU of the drive, memory/checksum errors, over-/underrun in control processes, controller self test failed, etc.
MAINS_SUPPLY
2
Comprises exceptions out of the mains supply like phase error, mains over- /undervoltage, etc.
LOW_VOLTAGE_SUPPLY
3
Comprises exceptions out of the low voltage supply supplied to the drive system (e.g. external 24 V supply).
DC_LINK_OVERVOLTAGE
4
Exception because of overvoltage of the DC link, which typically is a result of excessive energy feedback from the motor/process or a faulty dummy load.
POWER_ELECTRONICS
5
Comprises exceptions in the inverter stage of the drive: phase current measurement errors, overcurrent supervision error.
OVERTEMPERATURE_ELECTRONIC_DEVICE
6
Overtemperature because of overload or faulty cooling system.
ISOLATION_FAULT
7
Exception because of over-current resulting from shortage between phase and phase or phase and ground.
MOTOR_OVERLOAD
8
Exception because of over-temperature of the motor. This may be a result from motor overload or a faulty cooling system.
FIELDBUS_SYSTEM
9
Exception from the Communication System between the drive (DU) and the controller. For example, this may be temporary communication frame errors or exceptions in the isochronous operation.
SAFETY_CHANNEL
10
Exception because of a fault in the drive safety function (e.g. results from the redundant safety paths don't match).
FEEDBACK
11
Exception because of an exception in the feedback interface or the feedback sensor (e.g. encoder, position or velocity measurement system).
INTERNAL_COMMUNICATION
12
Exception from the drive internal Communication System if there is a separate physical entity related to the internal Communication System (e.g. communication backplane, bus cable, etc.).
INFEED
13
Comprises exceptions out of the infeed unit of the drive: for example missing DC link voltage, etc.
BRAKE_RESISTOR
14
Exception from the dummy load circuit of the drive: Over-temperature brake resistor, brake resistor no current, etc.
LINE_FILTER
15
Exception from the main line filter in front of the infeed unit if the filter is a separate physical entity (e.g. over-temperature, etc.).
EXTERNAL
16
Exception posted by additional input channels to the drive. For example, a separate custom specific temperature sensor connected to the drive system by an digital input.
TECHNOLOGY
17
Exception from a drive internal process supervision task/system. For example, supervision of a torque limit.
ENGINEERING
18
Exception from differences between real and expected configuration information.
OTHER
19
Necessary because every entry in the actual fault situation of the diagnosis system and the warning mechanism shall result in an exception in one of the PROFIdrive fault classes because of consistency. Therefore, if a drive exception does not match with one of the defined fault classes it shall be mapped with the fault class (Other).
AUXILIARY_DEVICE
20
Exception because of a fault in an auxiliary device of the drive which cannot be mapped to another fault class (e.g. special cooling devices often used for large drives).
Its representation in the AddressSpace is defined in Table 101.
Table 101 - PtEventClassEnumeration definition
Attribute
Value
BrowseName
PtEventClassEnumeration
IsAbstract
False
References
NodeClass
BrowseName
DataType
TypeDefinition
Other
Subtype of the 0:Enumeration type defined in OPC 10000-5.