8.1.1 IMonitoringElectric Interface
The IMonitoringElectric Interface specifies the Variables representing electric properties which are components of the Monitoring Folder. Instances of the Monitoring folder shall reference this InterfaceType if the containing Powertrain Axis Object represents an electric Drive.
| Attribute | Value | ||||
| BrowseName | IMonitoringElectric | ||||
| IsAbstract | True | ||||
| References | Node Class | BrowseName | DataType | TypeDefinition | Other |
|---|---|---|---|---|---|
| Subtype of the 0:BaseInterfaceType defined in OPC 10000-5. | |||||
| 0:HasComponent | Variable | BleederTemperature | 0:Float | PtTemperatureVariableType | O, RO |
| 0:HasComponent | Variable | ConverterOutputCosPhi | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterOutputCurrent | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterOutputCurrentTorque | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterOutputCurrentMagnetization | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterOutputFrequency | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterOutputPower | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterOutputVoltage | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterOutputVoltageMagnetization | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterOutputVoltageTorque | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | ConverterTemperature | 0:Float | PtTemperatureVariableType | O, RO |
| 0:HasComponent | Variable | DcBusVoltage | 0:Float | 0:AnalogUnitType | O, RO |
| 0:HasComponent | Variable | LineInputPower | 0:Float | 0:AnalogUnitType | O, RO |
| Conformance Units | |||||
|---|---|---|---|---|---|
| Powertrain Actual and Command Values |
The BleederTemperature Variable contains the actual temperature of the brake resistor.
The ConverterOutputCosPhi Variable contains the actual motor power factor.
The ConverterOutputCurrent Variable contains the actual current measured at the output converter clamp as rms value.
The ConverterOutputCurrentMagnetization Variable contains the motor magnetization related output current of the output converter as rms value.
The ConverterOutputCurrentTorque Variable contains the motor torque related output current of the output converter as rms value.
The ConverterOutputFrequency Variable contains the output frequency of the output converter.
The ConverterOutputPower Variable contains the actual power delivered to the motor.
The ConverterOutputVoltage Variable contains the output voltage RMS of the output converter as rms value.
The ConverterOutputVoltageMagnetization Variable contains the motor magnetization related output voltage of the output converter as rms value.
The ConverterOutputVoltageTorque Variable contains the motor torque related output voltage of the output converter as rms value.
The ConverterTemperature Variable contains the actual converter temperature.
The DcBusVoltage Variable contains the actual DC bus voltage value.
The LineInputPower Variable contains the actual input power consumption of the converter.