8.1 GsdGenAlarmEventType

This EventType is generated by the GsdGenSubmoduleApplicationType Object. Its representation in the AddressSpace is formally defined in Table 26.

Table 26 – GsdGenAlarmEventType definition
Attribute Value
BrowseNameGsdGenAlarmEventType
IsAbstractFalse
References NodeClass BrowseName DataType TypeDefinition Other
Subtype of the 0:BaseEventType defined in [OPC 10000-5].
0:HasPropertyVariableAPI0:UInt320:PropertyTypeM, RO
0:HasPropertyVariableSlot0:UInt160:PropertyTypeM, RO
0:HasPropertyVariableSubslot0:UInt160:PropertyTypeM, RO
0:HasPropertyVariableChannelNumber0:UInt160:PropertyTypeO, RO
0:HasPropertyVariableAccumulativeGsdGenChannelAccumulativeEnumeration0:PropertyTypeO, RO
0:HasPropertyVariableMaintenanceGsdGenChannelMaintenanceEnumeration0:PropertyTypeO, RO
0:HasPropertyVariableSpecifierGsdGenChannelSpecifierEnumeration0:PropertyTypeM, RO
0:HasPropertyVariableDirectionGsdGenChannelDirectionEnumeration0:PropertyTypeM, RO
0:HasPropertyVariableUserStructureIdentifier0:UInt160:PropertyTypeM, RO
0:HasPropertyVariableChannelErrorType0:UInt160:PropertyTypeM, RO
0:HasPropertyVariableExtChannelErrorType0:UInt160:PropertyTypeO, RO
0:HasPropertyVariableExtChannelAddValue0:UInt320:PropertyTypeO, RO
0:HasPropertyVariableQualifiedChannelQualifier0:UInt320:PropertyTypeO, RO
0:HasPropertyVariableManufacturerData0:ByteString0:PropertyTypeO, RO
0:HasPropertyVariableHelpText0:LocalizedText0:PropertyTypeM, RO
Conformance Units
PNGSDGM Alarm Event

This EventType inherits all Properties of the 0:BaseEventType.

If the variable UserStructureIdentifier indicates manufacturer specific diagnosis information, the variable ManufacturerData contains the manufacturer specific diagnosis data.

The Message variable of the Event and the HelpText variable are retrieved from the GSDML file. If the message includes a dynamic format string, this is replaced by the ExtChannelAddValue.

For an active alarm the Severity variable of the Event must be dependent on the Maintenance and the QualifiedChannelQualifier variables.

The Severity is divided into the 4 categories shown in the following table:

Category Severity Range
Fault750 – 1000
Maintenance demanded500 – 749
Maintenance required250 – 499
Advise2 – 249

If the Maintenance variable is provided, the following mapping is used for the Severity value:

Maintenance Severity
FAULT1000
MAINTENANCE_DEMANDED 612
MAINTENANCE_REQUIRED362

If the QualifiedChannelQualifier is provided, the Severity value depends on the bit set in the UInt32 value of the QualifiedChannelQualifier. The bits 0 – 2 are not used.

The following mapping is used for the Severity value:

Bit Severity
311000
30937
29875
28812
27750
26725
25700
24675
23650
22625
21600
20575
19550
18525
17500
16475
15450
14425
13400
12375
11350
10325
9300
8275
7250
6200
5150
4100
350