OPC UA for PROFINET GSD Generic Model – Part 30144: PROFINET GSD Generic Model
Annex D OPC UA Data Objects (Normative)
D.1 Data Object attributes
Table 64 and Table 65 define DataObject attributes together with their source.
Table 64 – DataObject attributes obtained from GSDML
Data Object attribute
Source
GSDML Name
Value of “Content” attribute of “Meta” element with “Property” attribute =“opc:Name”
GSDML Type
DataType attribute of ParameterRecordDataItem/Ref element defining the Data Object, mapped according to B.1.
GSDML Range
Value of “Content” attribute of “Meta” element with “Property” attribute =“opc:EURange”
GSDML Unit
Value of “Content” attribute of “Meta” element with “Property” attribute =“opc:EngineeringUnit”
GSDML Folder
Value of “Content” attribute of “Meta” element with “Property” attribute =“opc:FunctionGroupName”
BMP Number
Element of “Content” attribute of “Meta” element with “Property” attribute =“opc:ParameterNumber”, see Table 62.
Table 65 – DataObject attributes obtained using BMP Access
Data Object attribute
Source
BMP Name
“Name” field under subindex 6 of the parameter description (BMP Name, see [PDP], 6.2.1.3 Parameter description, Table 17 ).
BMP Type
First byte of the parameter description element “Identifier(ID)” under subindex 1 of the parameter description (see [PDP], Tables 17 and 18), mapped according to B.2.
BMP Range
Low/high limit under subindices 7 and 8 of the parameter description, see [PDP], 6.2.1.3.
BMP Unit
Obtained as described in [PDP], sec. 6.2.1.3, Variable attribute under subindex 4 of the parameter description, Tables 19 to 23).
BMP Text
Mapped element from the text array assigned to “simple” BMPs as described in [PDP], sec. 6.2.1.4.