6.7.7 Stop Method

This Method is used as part of the PackMLMachineStateMachineType. It allows an OPC UA Client to change the state of this state machine to the Stopping state.

Signature

	Stop(
		); 

Method result codes are defined in Table 36

Table 36 - Stop Method result codes
Result Code Description
Bad_MethodInvalidSee OPC 10000-4 – Services for the description of this result code. (The Method id does not refer to a Method for the specified Object.)
Bad_NotImplementedSee OPC 10000-4 – Services for the description of this result code. (Requested operation is not implemented.)
Bad_NodeIdUnknownSee OPC 10000-4 – Services for the description of this result code. (Used to indicate that the specified Object is not valid)
Bad_InvalidStateSee OPC 10000-4 – Services for the description of this result code. (The operation cannot be completed because the Object is closed, uninitialized or in some other invalid state.)

Table 37 specifies the AddressSpace representation for the Stop Method. Stop has no input or output parameters and has no referenced objects or variables.

Table 37 – Stop Method AddressSpace Definition
Attribute Value
BrowseNameStop
References NodeClass BrowseName DataType TypeDefinition ModellingRule