[RQ7.13] Figure 15 shows a simplified representation of the state diagram of the SafetyProvider. The exact behavior is described in Table 30, Table 31, and Table 32. The SafetyProvider shall implement that behavior. It is not required to literally follow the entries given in the tables, if the externally observable behavior does not change.
Figure 15 – Simplified representation of the state diagram for the SafetyProvider
Table 29 – Symbols used for state machines
Graphical representation |
Type |
Description |
|
Activity State |
Within these interruptible activity states the SafetyProvider waits for new input. |
|
Action State |
Within these non-interruptible action states events like new requests are deferred until the next activity state is reached, see [1]. |
The transitions are fired in case of an event. “Event” in this context means either a method call in the case of Client/Server communication or the detection of a changed RequestSPDU by the OPC UA mapper in the case of PubSub communication.
In case of several possible transitions, so-called guard conditions (refer to […] in UML diagrams) define which transition to fire.
The diagram consists of activity and action states. Activity states are surrounded by bold lines, action states are surrounded by thin lines. While activity states may be interruptible by new events, action states are not. External events occurring while the state machine is in an action state, are deferred until the next activity state is reached.
NOTE The details on how to implement activity states and action states are vendor-specific. Typically, in a real-time system the task performing the SafetyProvider or SafetyConsumer state machine is executed cyclically (see 6.3.5). Whenever the task is woken up by the scheduler of the operating system while it is in an action state, it executes action states until its time slice is used up, or an activity state is reached. Whenever a task being in an activity state is woken up, it checks for input. If no new input is available, it immediately returns to the sleep state without changing state.
If input is available, it starts executing action states until its time-slice is up or until the next activity state is reached.
Table 30 – SafetyProvider instance internal items
INTERNAL ITEMS |
TYPE |
DEFINITION |
RequestSPDU_i |
Variable |
Local Memory for RequestSPDU (required to react on changes). |
SPDU_ID_1_i |
UInt32 |
Local variable to store SPDU_ID_1 |
SPDU_ID_2_i |
UInt32 |
Local variable to store SPDU_ID_2 |
SPDU_ID_3_i |
UInt32 |
Local variable to store SPDU_ID_3 |
BaseID_i |
GUID |
Local variable containing the BaseID (taken either from the SPI or SAPI). |
ProviderID_i |
UInt32 |
Local variable containing the ProviderID (taken either from the SPI or SAPI). |
<Get RequestSPDU> |
Macro |
Instruction to take the whole RequestSPDU from the OPC UA Mapper. |
<Set ResponseSPDU> |
Macro |
Instruction to transfer the whole ResponseSPDU to the OPC UA Mapper |
<Calc SPDU_ID_i> |
Macro |
const uint32 SafetyProviderLevel_ID := … // see 7.2.3.3 If(SAPI.SafetyBaseID == 0) thenBaseID_i := SPI.SafetyBaseIDConfiguredElse BaseID_i := SAPI.SafetyBaseID Endif If(SAPI.SafetyProviderID == 0) thenProviderID_i := SPI.SafetyProviderIDConfiguredElse ProviderID_i := SAPI.SafetyProviderID Endif SPDU_ID_1_i := BaseID_i (bytes 0…3) XOR SafetyProviderLevel_ID SPDU_ID_2_i := BaseID_i (bytes 4…7) XOR SPI.SafetyStructureSignature SPDU_ID_3_i := BaseID_i (bytes 8…11) XOR BaseID_i (bytes 12…15) XOR ProviderID_i // see 7.2.3.2 for clarification |
<build ResponseSPDU> |
Macro |
Take the MNR and the SafetyConsumerID of the received RequestSPDU. Add the SPDU_ID_1_i, SPDU_ID_2_i, SPDU_ID_3_i, Flags, the SafetyData and the NonSafetyData, as well as the calculated CRC. See 7.2.3.1 |
Table 31 – States of SafetyProvider instance
STATE NAME |
STATE DESCRIPTION |
Initialization |
// Initial state SAPI.SafetyData := 0 SAPI.NonSafetyData := 0SAPI.MonitoringNumber := 0SAPI.SafetyConsumerID := 0 SAPI.OperatorAckRequested := 0 RequestSPDU_i := 0 |
S1_WaitForRequest |
// waiting on next RequestSPDU from SafetyConsumer <Get RequestSPDU> |
S2_PrepareSPDU |
ResponseSPDU.Flags.ActivateFSV := SAPI.ActivateFSVResponseSPDU.Flags.OperatorAckProvider := SAPI.OperatorAckProvider ResponseSPDU.Flags.TestModeActivated := SAPI.EnableTestMode <Calc SPDU_ID_i> <build ResponseSPDU> // see 7.2.3.1
|
Table 32 – SafetyProvider transitions
TRAN-SITION |
SOURCE STATE |
TARGET STATE |
GUARD CONDITION |
ACTIVITY |
T1 |
Init |
S1 |
|
|
T2 |
S1 |
S2 |
// RequestSPDU received1 - |
// Process Request RequestSPDU_i := RequestSPDU SAPI.MonitoringNumber := RequestSPDU.MonitoringNumber SAPI.SafetyConsumerID := RequestSPDU.SafetyConsumerID SAPI.OperatorAckRequested := RequestSPDU.Flags.OperatorAckRequested |
T3 |
S2 |
S1 |
// SPDU is prepared - |
<Set ResponseSPDU> |
1 See the preceding explanation in this Subclause 7.2.2.3 of what constitutes events which may trigger this transition. |
NOTE The SafetyProvider does not check for correct configuration. It will reply to requests even if it is incorrectly configured (e.g., its SafetyProviderID is zero). However, SafetyConsumers will never try to communicate with SafetyProviders having incorrect parameters, see Transitions T13/T27 in Table 35 and the macro <ParametersOK?> in Table 33.