The two SCL-services “SafetyProvider” and “SafetyConsumer” are specified using state diagrams.

Figure 13 and Figure 14 show sequences of requests and responses with SafetyData for this document using OPC UA Client/Server and PubSub communication mechanisms, respectively. Please note that the figures show selected scenarios only and are therefore informative.

image018.png

Figure 13 (informative) – Sequence diagram for requests and responses (Client/Server)

[RQ7.10] In the case of Client/Server communication, a SafetyConsumer’s OPC UA mapper may call a SafetyProvider (either the state machine implementation itself or the SafetyProvider’s OPC UA mapper) with an identical RequestSPDU multiple times in a row. In that case, the SafetyProvider (state machine or OPC UA mapper) shall answer all requests.

NOTE 1 The returned ResponseSPDUs may contain different values (e.g., currently available process values) or contain the initially returned values.

[RQ7.11] For each SafetyProvider, the implemented choice of behavior according to RQ7.10 (i.e., whether currently available process values or initially returned values will be used) shall be documented in the corresponding safety manual.

NOTE 2 Since a SafetyConsumer checks for changed MNRs in ResponseSPDUs (see SafetyConsumer state S14_WaitForChangedSPDU in Table 34 and transition T17 in Table 35), and therefore will use only the first evaluated ResponseSPDU for a given MNR. All further ResponseSPDUs with the same MNR will be ignored.

image019.png

NOTE The bold arrows represent communication with new data values, whereas dashed arrows contain repeated data values.

Figure 14 (informative) – Sequence diagram for requests and responses (PubSub)

NOTE 3 The state machines according to this document do not contain any retry-mechanisms to increase fault tolerance. In contrast, it is assumed that retry is already handled within the OPC UA stack (e.g., when using Client/Server, or by choosing a higher update rate for PubSub). The dashed lines therefore are not part of this document, but rather symbolize the repeated sending of data implemented in the OPC UA stack.

The SafetyConsumerTimeout is the watchdog time checked in the SafetyConsumer. The watchdog is restarted immediately before a new RequestSPDU is generated (transitions T14 and T28 of the SafetyConsumer in Table 35). If an appropriate ResponseSPDU is received in time, and the checks for data integrity, authenticity, and timeliness are all valid, the timer will not expire before it is restarted.

Otherwise, the watchdog timer expires, and the SafetyConsumer triggers a safe reaction. To duly check its timer, the SafetyConsumer is executed cyclically, with period ConsumerCycleTime. ConsumerCycleTime is expected to be smaller than SafetyConsumerTimeout.

The ConsumerCycleTime is the maximum time for the cyclic update of the SafetyConsumer. It is the timeframe from one execution of the SafetyConsumer to the next execution of the SafetyConsumer. The implementation of the monitoring of the ConsumerCycleTime and the reaction in case of exceeding the ConsumerCycleTime are not part of this document; these are vendor-specific.

[RQ7.12] The ConsumerCycleTime shall be monitored in a safety-related way.

[RQ7.13] Figure 15 shows a simplified representation of the state diagram of the SafetyProvider. The exact behavior is described in Table 30, Table 31, and Table 32. The SafetyProvider shall implement that behavior. It is not required to literally follow the entries given in the tables, if the externally observable behavior does not change.

image020.png

Figure 15 – Simplified representation of the state diagram for the SafetyProvider

Table 29 – Symbols used for state machines

Graphical representation

Type

Description

image021.png

Activity State

Within these interruptible activity states the SafetyProvider waits for new input.

image022.png

Action State

Within these non-interruptible action states events like new requests are deferred until the next activity state is reached, see [1].

The transitions are fired in case of an event. “Event” in this context means either a method call in the case of Client/Server communication or the detection of a changed RequestSPDU by the OPC UA mapper in the case of PubSub communication.

In case of several possible transitions, so-called guard conditions (refer to […] in UML diagrams) define which transition to fire.

The diagram consists of activity and action states. Activity states are surrounded by bold lines, action states are surrounded by thin lines. While activity states may be interruptible by new events, action states are not. External events occurring while the state machine is in an action state, are deferred until the next activity state is reached.

NOTE The details on how to implement activity states and action states are vendor-specific. Typically, in a real-time system the task performing the SafetyProvider or SafetyConsumer state machine is executed cyclically (see 6.3.5). Whenever the task is woken up by the scheduler of the operating system while it is in an action state, it executes action states until its time slice is used up, or an activity state is reached. Whenever a task being in an activity state is woken up, it checks for input. If no new input is available, it immediately returns to the sleep state without changing state.

If input is available, it starts executing action states until its time-slice is up or until the next activity state is reached.

Table 30 – SafetyProvider instance internal items

INTERNAL ITEMS

TYPE

DEFINITION

RequestSPDU_i

Variable

Local Memory for RequestSPDU (required to react on changes).

SPDU_ID_1_i

UInt32

Local variable to store SPDU_ID_1

SPDU_ID_2_i

UInt32

Local variable to store SPDU_ID_2

SPDU_ID_3_i

UInt32

Local variable to store SPDU_ID_3

BaseID_i

GUID

Local variable containing the BaseID (taken either from the SPI or SAPI).

ProviderID_i

UInt32

Local variable containing the ProviderID (taken either from the SPI or SAPI).

<Get RequestSPDU>

Macro

Instruction to take the whole RequestSPDU from the OPC UA Mapper.

<Set ResponseSPDU>

Macro

Instruction to transfer the whole ResponseSPDU to the OPC UA Mapper

<Calc SPDU_ID_i>

Macro

const uint32 SafetyProviderLevel_ID := … // see 7.2.3.3

If(SAPI.SafetyBaseID == 0) thenBaseID_i := SPI.SafetyBaseIDConfiguredElse BaseID_i := SAPI.SafetyBaseID

Endif If(SAPI.SafetyProviderID == 0) thenProviderID_i := SPI.SafetyProviderIDConfiguredElse ProviderID_i := SAPI.SafetyProviderID

Endif

SPDU_ID_1_i := BaseID_i (bytes 0…3) XOR SafetyProviderLevel_ID

SPDU_ID_2_i := BaseID_i (bytes 4…7) XOR SPI.SafetyStructureSignature

SPDU_ID_3_i := BaseID_i (bytes 8…11) XOR BaseID_i (bytes 12…15) XOR ProviderID_i

// see 7.2.3.2 for clarification

<build ResponseSPDU>

Macro

Take the MNR and the SafetyConsumerID of the received RequestSPDU. Add the SPDU_ID_1_i, SPDU_ID_2_i, SPDU_ID_3_i, Flags, the SafetyData and the NonSafetyData, as well as the calculated CRC.

See 7.2.3.1

Table 31 – States of SafetyProvider instance

STATE NAME

STATE DESCRIPTION

Initialization

// Initial state

SAPI.SafetyData := 0

SAPI.NonSafetyData := 0SAPI.MonitoringNumber := 0SAPI.SafetyConsumerID := 0

SAPI.OperatorAckRequested := 0

RequestSPDU_i := 0

S1_WaitForRequest

// waiting on next RequestSPDU from SafetyConsumer

<Get RequestSPDU>

S2_PrepareSPDU

ResponseSPDU.Flags.ActivateFSV := SAPI.ActivateFSVResponseSPDU.Flags.OperatorAckProvider := SAPI.OperatorAckProvider ResponseSPDU.Flags.TestModeActivated := SAPI.EnableTestMode

<Calc SPDU_ID_i>

<build ResponseSPDU> // see 7.2.3.1

Table 32 – SafetyProvider transitions

TRAN-SITION

SOURCE STATE

TARGET STATE

GUARD CONDITION

ACTIVITY

T1

Init

S1

T2

S1

S2

// RequestSPDU received1

-

// Process Request

RequestSPDU_i := RequestSPDU

SAPI.MonitoringNumber := RequestSPDU.MonitoringNumber

SAPI.SafetyConsumerID := RequestSPDU.SafetyConsumerID

SAPI.OperatorAckRequested := RequestSPDU.Flags.OperatorAckRequested

T3

S2

S1

// SPDU is prepared

-

<Set ResponseSPDU>

1 See the preceding explanation in this Subclause 7.2.2.3 of what constitutes events which may trigger this transition.

NOTE The SafetyProvider does not check for correct configuration. It will reply to requests even if it is incorrectly configured (e.g., its SafetyProviderID is zero). However, SafetyConsumers will never try to communicate with SafetyProviders having incorrect parameters, see Transitions T13/T27 in Table 35 and the macro <ParametersOK?> in Table 33.

[RQ7.14] Figure 16 shows a simplified representation of the state diagram of the SafetyConsumer. The exact behavior is described in Table 33, Table 34, and Table 35. The SafetyConsumer shall implement this behavior. It is not required to literally follow the entries given in the tables, if the externally observable behavior does not change.

NOTE In order to avoid unnecessary spurious trips requiring operator acknowledgment, the SafetyConsumers should only be started after an OPC UA connection to a running SafetyProvider has been established, or setting the input SAPI.Enable should be delayed until the SafetyProvider is running.

image023.png

Figure 16 – Principle state diagram for SafetyConsumer

Table 33 – SafetyConsumer internal items

INTERNAL ITEMS

TYPE

DEFINITION

Constants

MNR_min := 0x100

UInt32

// 0x100 is the start value for MNR, also used after wrap-around

// The values 0…0xFF are reserved for future use

Variables

FaultReqOA_i

Boolean

Local memory for errors which request operator acknowledgment

OperatorAckConsumerAllowed_i

Boolean

Auxiliary flag indicating that operator acknowledgment is allowed. It is true if the input SAPI.OperatorAckConsumer has been ‘false’ since FaultReqOA_i was set

MNR_i

UInt32

Local Monitoring Number (MNR)

prevMNR_i

UInt32

Local memory for previous MNR

ConsumerID_i

UInt32

Local memory for SafetyConsumerID in use

CRCCheck_i

Boolean

Local variable used to store the result of the CRC-check

SPDUCheck_i

Boolean

Local variable used to store the result of the additional SPDU-checks

SPDU_ID_1_i

UInt32

Local variable to store the expected SPDU_ID_1

SPDU_ID_2_i

UInt32

Local variable to store the expected SPDU_ID_2

SPDU_ID_3_i

UInt32

Local variable to store the expected SPDU_ID_3

SPI_SafetyConsumerID_i

UInt32

Local variable to store the parameter SafetyConsumerID

SPI_SafetyProviderID_i

UInt32

Local variable to store the parameter SafetyProviderID

SPI_SafetyBaseID_i

UInt128

Local variable to store the parameter SafetyBaseID

SPI_SafetyStructureSignature_i

UInt32

Local variable to store the parameter SafetyStructureSignature

SPI_SafetyOperatorAckNecessary_i

Boolean

Local variable to store the parameter SafetyOperatorAckNecessary

SPI_SafetyErrorIntervalLimit_i

UInt16

Local variable to store the parameter SafetyErrorIntervalLimit

MNR_re_sync_i

Boolean

Local variable used to support re-synchronization of

MNR after detected error

Timers

ConsumerTimer

Timer

This timer is used to check whether the next valid ResponseSPDU has arrived on time. It is initialized using the parameter SPI.SafetyConsumerTimeout

NOTE As opposed to other parameters, a modification of the parameter value SafetyConsumerTimeout takes effect immediately, i.e., not only when state S11 is visited.

ErrorIntervalTimer

Timer

This timer is used to check the elapsed time between errors. If the elapsed time between two consecutive errors is smaller than the value SafetyErrorIntervalLimit, FSV will be activated. Otherwise, the ResponseSPDU is discarded and the SafetyConsumer waits for the next ResponseSPDU.

This timer is initialized using the local variable SPI_SafetyErrorIntervalLimit_i.

See Table 26, 6.3.4.3, and 9.4 for more information.

NOTE Tthe local variable SPI_SafetyErrorIntervalLimit_i should not be confused with the parameter SPI.SafetyErrorIntervalLimit. The local variable is copied from the parameter in state S11 (restart). Hence, if the parameter value changes during runtime, the new value will only be used after the connection has been restarted.

Macros <...><...>

<risingEdge x>

Macro

// detection of a rising edge:

If x==true && tmp==false Then result := trueElse result := falseEndif

tmp := x

<Get ResponseSPDU>

Macro

Instruction to take the whole ResponseSPDU from the OPC UA Mapper.

<Use FSV>

Macro

SAPI.SafetyData is set to binary 0

If [<ConsumerTimer expired || SAPI.Enable==0 ?>]Then SAPI.NonSafetyData is set to binary 0

Else SAPI.NonSafetyData is set to ResponseSPDU.NonSafetyData

Endif

SAPI.FSV_Activated := 1

RequestSPDU.Flags.FSV_Activated := 1

NOTE If a safety application prefers fail-safe values other than binary 0, this can be implemented in the safety application by querying SAPI.FSV_Activated.

NOTE The non-safety data is always updated if data is available. In case of a timeout, no data is available, which is indicated using binary zero. If an application needs to distinguish between “no data available” and “binary zero received”, it can add a Boolean variable to the NonSafetyData. This value is set to ‘one’ during normal operation, and to ‘zero’ for indicating that no data is available.

<Use PV>

Macro

SAPI.SafetyData is set to ResponseSPDU. SafetyData

SAPI.NonSafetyData is set to ResponseSPDU.NonSafetyData

SAPI.FSV_Activated := 0

RequestSPDU.Flags.FSV_Activated := 0

RequestSPDU.Flags.CommunicationError := 0

<Set RequestSPDU>

Macro

Instruction to transfer the whole RequestSPDU to the OPC UA Mapper

<(Re)Start ConsumerTimer>

Macro

Restarts the consumer timer.

<(Re)Start ErrorIntervalTimer>

Macro

Restarts the error interval timer.

<ConsumerTimer expired?>

Macro

Yields “true” if the timer is running longer than SPI.SafetyConsumerTimeout since last restart, “false” otherwise.

<ErrorIntervalTimer expired?>

Macro

Yields “true” if the timer is running longer than SPI.SafetyErrorIntervalLimit since last restart, “false” otherwise.

<Assign ConsumerID>

Macro

If SAPI.SafetyConsumerID != 0

Then

ConsumerID_i := SAPI.SafetyConsumerID

Else

ConsumerID_i := SPI_SafetyConsumerID_i

EndifRequestSPDU.SafetyConsumerID := ConsumerID_i

<Calc SPDU_ID_i>

Macro

uint128 BaseID

uint32 ProviderID

const uint32 SafetyProviderLevel_ID := … // see 7.2.3.3

If(SAPI.SafetyBaseID == 0)

Then BaseID := SPI_SafetyBaseID_iElse BaseID := SAPI.SafetyBaseID

Endif If(SAPI.SafetyProviderID == 0)

Then ProviderID := SPI_SafetyProviderID_iElse ProviderID := SAPI.SafetyProviderID

Endif

SPDU_ID_1_i := BaseID (bytes 0…3) XOR SafetyProviderLevel_ID

SPDU_ID_2_i := BaseID (bytes 4…7) XOR SPI_SafetyStructureSignature_i

SPDU_ID_3_i := BaseID (bytes 8…11) XOR BaseID (bytes 12…15) XOR ProviderID

// see 7.2.3.2 for clarification

<ParametersOK?>

Macro

Boolean result := trueIf(SAPI.SafetyBaseID == 0 && SPI_SafetyBaseID_i==0)Thenresult := falseElseEndif

If(SAPI.SafetyProviderID == 0 && SPI_SafetyProviderID_i==0)Thenresult := falseElseEndif

If(SAPI.SafetyConsumerID == 0 && SPI_SafetyConsumerID_i==0)Thenresult := falseElseEndif

If(SPI_SafetyStructureSignature_i==0)Thenresult := falseElseEndif

yield result

<Set Diag(ID,

Boolean isPermanent)>

Macro

// ID is the identifier for the type of diagnostic output, see Table 28// Parameter "isPermanent" is used to indicate a permanent error// Only one diagnostic message is created for multiple permanent // errors in sequence

If(RequestSPDU.Flags.CommunicationError == 0) Then <do vendor-specific function for diagnostic output using ID>Else //do nothingEndif

RequestSPDU.Flags.CommunicationError := isPermanent

// NOTE See Table 28 for possible values for “ID” and their codes.

<ResponseSPDUready for checks>

Macro

Boolean result := false

If MNR_re_sync_i == false

Then If ResponseSPDU.MNR <> prevMNR_i

Then result := true

Else //do nothingEndif

Else

If ResponseSPDU.MNR == MNR_i

Then result := true

Else //do nothingEndif

Endif

yield result

<Handle WDTimeout>

Macro

<Set Diag(CommErrTO,isPermanent:=true)><Use FSV>

If SPI_SafetyOperatorAckNecessary_i == 1Then FaultReqOA_i := 1SAPI.OperatorAckRequested := 0RequestSPDU.Flags.OperatorAckRequested := 0Else // do nothingEndif

External Event

Restart Cycle

Event

The external call of SafetyConsumer can be interpreted as event “Restart Cycle”

NOTE A macro is a shorthand representation for operations described in the according definition.

Table 34 – SafetyConsumer states

STATE NAME

STATE DESCRIPTION

Initialization

// Initial state of the SafetyConsumer instance.

<Use FSV> SAPI.OperatorAckRequested := 0RequestSPDU.Flags.OperatorAckRequested := 0SAPI.OperatorAckProvider := 0FaultReqOA_i := 0OperatorAckConsumerAllowed_i := 0SAPI.TestModeActivated := 0RequestSPDU.Flags.CommunicationError := 0

MNR_re_sync_i:= false

S11_Wait for (Re)Start

// Safety Layer is waiting (Re)Start

// Changes to these parameters are only considered in this state

// Exception: a change of SafetyConsumerTimeout is possible during operation

// Read parameters from the SPI and store them in local variables:

SPI_SafetyConsumerID_i := SPI.SafetyConsumerID

SPI_SafetyProviderID_i := SPI.SafetyProviderIDConfigured

SPI_SafetyBaseID_i := SPI.SafetyBaseIDConfigured

SPI_SafetyStructureSignature_i := SPI.SafetyStructureSignature

SPI_SafetyOperatorAckNecessary_i := SPI.SafetyOperatorAckNecessary

SPI_SafetyErrorIntervalLimit_i := SPI_SafetyErrorIntervalLimit

S12_initialize MNR

// Use previous MNR if known// or random MNR within the allowed range (e.g., after cold start), see 9.2.

MNR_i := (previous MNR_i if known) or (random MNR)

MNR_i := max(MNR_i, MNR_min)1

S13_PrepareRequest

// Build RequestSPDU and send (done in T16)

S14_WaitForChangedSPDU

// Safety Layer is waiting for next ResponseSPDU from SafetyProvider.

// A new ResponseSPDU is characterized by a change in the MNR.

S15_CRCCheckSPDU

// Check CRC

uint32 CRC_calcCRCCheck_i := (CRC_calc == ResponseSPDU.CRC)

// see 7.2.3.5 on how to calculate CRC_calc

S16_CheckResponseSPDU

// Check SafetyConsumerID and SPDU_ID and MNR (see T22, T23, T24)

SPDUCheck_i := ResponseSPDU.SPDU_ID_1 == SPDU_ID_1_i && ResponseSPDU.SPDU_ID_2 == SPDU_ID_2_i && ResponseSPDU.SPDU_ID_3 == SPDU_ID_3_i && ResponseSPDU.SafetyConsumerID == ConsumerID_i && ResponseSPDU.MNR == MNR_i

S17_Error

SAPI.TestModeActivated := 0

S18_ProvideSafetyData

// Provide SafetyData to the application program

S19_SecondWDT_Check

// Second check of WDTimeout

// Prevents restarting of ConsumerTimer if it expired since initial check

1 This ensures that the MNR is greater or equal to MNR_min, in cases the random number generator yielded a smaller value.

NOTE The consumer parameters are accessed only in state S11. In this state, a copy is made, and in all other states and transitions, the copied values are used. This ensures that a change of one of these parameters takes effect only when a new safety connection is established. The only exception from this rule is the parameter SafetyConsumerTimeout. A change of this parameter may become effective immediately. If this is not the desired behavior, i.e., if parameters should be changeable during runtime, this can be accomplished by establishing a second safety connection according to this document with the new parameters, and then switch between these two safety connections at runtime.

Table 35 – SafetyConsumer transitions

TRAN-SITION

SOURCE STATE

TARGET STATE

GUARD CONDITION

ACTIVITY

T12

Init

S11

-

T13

S11

S12

//Start

[SAPI.Enable==1 && <ParametersOK?>]

<(Re)Start ErrorIntervalTimer><calc SPDU_ID_i> // see 7.2.3.2 for clarification

T14

S12

S13

// MNR initialized

<(Re)Start ConsumerTimer>

<Assign ConsumerID>

T15

S18

S11

// Termination

[SAPI.Enable==0]

<Use FSV>

RequestSPDU.Flags.CommunicationError := 0

// necessary to make sure that no diagnostic

// message is lost, see macro <Set Diag ...>

// NOTE Depending on its implementation, it might

// be necessary to stop the ConsumerTimer here.

T16

S13

S14

// Build Request SPDU // and send it

prevMNR_i := MNR_i

If MNR_i == 0xFFFFFFFFFThen MNR_i := MNR_minElse

MNR_i := MNR_i + 1Endif

RequestSPDU.MonitoringNumber := MNR_i

<Set RequestSPDU>

T17

S14

S15

// Changed ResponseSPDU// is received1

<Get ResponseSPDU>2

<ResponseSPDU ready for checks>

// A changed ResponseSPDU is characterized by a change in the MNR.

T18

S14

S17

// WDTimeout

[<ConsumerTimer expired?>]

<Handle WDTimeout>

T19

S15

S13

// When CRC err and SafetyErrorIntervalTimer expired[(crcCheck_i == 0) && <ErrorIntervalTimer expired?>]

MNR_re_sync_i := true

<(Re)Start ErrorIntervalTimer><Set Diag(CRCerrIgn, isPermanent:=false)>

T20

S15

S17

// When CRC err and SafetyErrorIntervalTimer not expired

[(crcCheck_i == 0) && not <ErrorIntervalTimer expired?>]

<(Re)Start ErrorIntervalTimer><Set Diag(CRCerrOA, isPermanent:=true)><Use FSV>

FaultReqOA_i := 1SAPI.OperatorAckRequested := 0RequestSPDU.Flags.OperatorAckRequested := 0

T21

S15

S16

// When CRCCheckOK

[crcCheck_i == 1]

-

T22

S16

S18

// SPDU OK

[SPDUCheck_i==true]

// For clarification, refer to Figure 17;

MNR_re_sync_i := false

// indicate OA from provider

SAPI.OperatorAckProvider := ResponseSPDU.Flags.OperatorAckProvider

// OA requested due to rising edge at ActivateFSV?

If (<risingEdge ResponseSPDU.Flags.ActivateFSV>&& SPI_SafetyOperatorAckNecessary_i == true)Then FaultReqOA_i := 1;<Set Diag(FSV_Requested,isPermanent:=true)> Else // do nothing

Endif

// Set Flags if OA requested:

If FaultReqOA_i==1 Then SAPI.OperatorAckRequested := 1, RequestSPDU.Flags.OperatorAckRequested := 1, OperatorAckConsumerAllowed_i := 0,FaultReqOA_i := 0Else //do nothingEndif

// Wait until OperatorAckConsumer is not active

If SAPI.OperatorAckConsumer==0

Then

OperatorAckConsumerAllowed_i := 1

Else

//do nothing

Endif

// Reset flags after OA:

If SAPI.OperatorAckConsumer ==1 && OperatorAckConsumerAllowed_i == 1

Then

SAPI.OperatorAckRequested := 0, RequestSPDU.Flags.OperatorAckRequested := 0Else

// do nothing

Endif

If SAPI.OperatorAckRequested==1 || ResponseSPDU.Flags.ActivateFSV==1Then <Use FSV> Else <Use PV>Endif

// Notify safety application that SafetyProvider is in test mode:

SAPI.TestModeActivated := ResponseSPDU.Flags.TestModeActivated

T23

S16

S13

// SPDU NOK and SafetyErrorIntervalTimer expired[SPDUCheck_i == false && <ErrorIntervalTimer expired?>]

<(Re)Start ErrorIntervalTimer>,

MNR_re_sync_i := true

// Send diagnostic message according the// detected error:

If ResponseSPDU.SafetyConsumerID <> ConsumerID_iThen <Set Diag(CoIDerrIgn, isPermanent:=false)>ElseIf ResponseSPDU.MNR<>MNR_iThen <Set Diag(MNRerrIgn,isPermanent:=false)> Else //do nothing EndIf If ResponseSPDU.SPDU_ID_1<> SPDU_ID_1_i || ResponseSPDU.SPDU_ID_2<> SPDU_ID_2_i || ResponseSPDU.SPDU_ID_3<> SPDU_ID_3_iThen <Set Diag(SD_IDerrIgn,

isPermanent:=false)>3 Else // do nothing Endif Endif

T24

S16

S17

// SPDU NOK and SafetyErrorIntervalTimer not expired

[SPDUCheck_i == 0 && not <ErrorIntervalTimer expired?>]

<(Re)Start ErrorIntervalTimer>// Send diagnostic message according the // detected error:

If ResponseSPDU.SafetyConsumerID<> ConsumerID_iThen <Set Diag(CoIDerrOA, isPermanent:=true)>Else If ResponseSPDU.MNR<>MNR_iThen <Set Diag(MNRerrOA,isPermanent:=true)> Else //do nothing Endif If ResponseSPDU.SPDU_ID_1<> SPDU_ID_1_i || ResponseSPDU.SPDU_ID_2<> SPDU_ID_2_i || ResponseSPDU.SPDU_ID_3<> SPDU_ID_3_iThen <Set Diag(SD_IDerrOA,isPermanent:=true)> Else //do nothing Endif Endif

FaultReqOA_i := 1

SAPI.OperatorAckRequested := 0RequestSPDU.Flags.OperatorAckRequested := 0<Use FSV>

T25

S17

S18

// SPDU NOK

-

MNR_re_sync_i := true

T26

S18

S19

// Restart Cycle

[SAPI.Enable==1]

-

T27

S11

S11

// Invalid parameters

[SAPI.Enable==1 && not <ParametersOK?>]

<Set Diag(ParametersInvalid, isPermanent:=true)>

T28

S19

S13

// No WDTimeout

<(Re)Start ConsumerTimer>

T29

S19

S17

// WDTimeout

[<ConsumerTimer expired?>]

<Handle WDTimeout>

1 Another event like “Method completion successful” can be used as guard condition of “Changed ResponseSPDU received” as well.

2 SPDUs with all values (incl. CRC signature) being zero shall be ignored, see requirement RQ5.6.

3 See Table 28.

Figure 17 shows the sequence after the detection of an error requiring operator acknowledge until communication returns to delivering process values again.

image024.png

Figure 17 – Sequence diagram for OA

After the error is gone the sequence follows the logic of T22 in Table 35.