10 Profiles and ConformanceUnits
10.1 Conformance Units
This chapter defines the corresponding Conformance Units for the OPC UA Information Model for Machinery – Energy Management.
| Category | Title | Description |
| Server | Machinery Energy Base Structure | Supports at least one MachineryItem supporting the Consumption Object having at least one sub-folder following the predefined BrowseNames of this specification. |
| Server | Machinery Energy Main grouping | Each MachineryItem supporting the Consumption Object with a sub-folder according to this specification provides a Main Object of EnergyMeasurementType for each of those sub-folders. |
| Server | Machinery Energy Non Electrical Base | Supports INonElectricalEnergyType and at least one instance of EnergyMeasurementType implementing the interface. |
| Server | Machinery Energy Non Electrical Mass Flow | Supports IBaseFlowType, IMassFlowType and at least one instance of EnergyMeasurementType implementing IMassFlowType. |
| Server | Machinery Energy Non Electrical Volume Flow | Supports IBaseFlowType, IVolumeFlowType and at least one instance of EnergyMeasurementType implementing IVolumeFlowType. |
| Server | Machinery Energy Contains | Supports the Contains ReferenceType and at least one instance using the ReferenceType. |
10.2 Profiles
10.2.1 Profile list
Table 14 lists all Profiles defined in this document and defines their URIs.
| Profile | URI |
| Machinery Energy Base Server Facet | http://opcfoundation.org/UA-Profile/Machinery/Energy/Server/Base |
10.2.2 Server Facets
10.2.2.1 Overview
The following sections specify the Facets available for Servers that implement the OPC UA for Machinery – Energy Management companion specification. Each section defines and describes a Facet or Profile.
10.2.2.2 Machinery Energy Base Server Facet
Table 15 defines a Profile that describes the base functionality to provide energy consumption information of a MachineryItem.
| Group | Conformance Unit / Profile Title | Mandatory / Optional |
| Profile | Machinery Monitoring Server Facet | |
| ECM | ECM Energy Measurement | M |
| ECM | ECM EnergyProfile E0 | O |
| ECM | ECM EnergyProfile E1 | O |
| ECM | ECM EnergyProfile E2 | O |
| ECM | ECM EnergyProfile E3 | O |
| ECM | ECM EnergyProfile D0 | O |
| ECM | ECM EnergyProfile D1 | O |
| ECM | ECM Energy Measurement Common DataTypes | O |
| ECM | ECM Accuracy Domain Percent full scale | O |
| ECM | ECM Accuracy Domain Percent actual reading | O |
| ECM | ECM Accuracy Domain IEC | O |
| ECM | ECM Accuracy Domain EN | O |
| Machinery Energy | Machinery Energy Base Structure | M |
| Machinery Energy | Machinery Energy Main grouping | O |
| Machinery Energy | Machinery Energy Non Electrical Base | O |
| Machinery Energy | Machinery Energy Non Electrical Mass Flow | O |
| Machinery Energy | Machinery Energy Non Electrical Volume Flow | O |
| Machinery Energy | Machinery Energy Contains | O |
10.2.3 Client Facets