OPC-10000-15 – OPC Unified Architecture - Part 15: Safety4.1 Generaluses a MonitoringNumber , a timeout, a set of IDs and a cyclic redundancy check ( CRC )code for the detection of all possible communication errors which can happen in the underlying
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety5.3 Safety measuresInstance of "data integrity assurance" of IEC 61784‑3, based on CRC signature. The SafetyConsumer is specified in such a way that for any communication error according
-
OPC-10000-15 – OPC Unified Architecture - Part 15: SafetyRequirements for CRC calculation [RQ5.4] Any CRC signature calculation shall start with a preset value of "1". [RQ5.5] Any CRC signature calculation resulting ... shall use the value "1" instead. [RQ5.6] SPDUs with all values (incl. CRC signature) being zero shall be ignored by the receiver ( SafetyConsumer and SafetyProvider ). For Client/Server communication
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety6.2.2.3 Method ReadSafetyDataTable 26 . OutMonitoringNumber MonitoringNumber of the ResponseSPDU , see 7.2.1.9 , 7.2.3.1 , and Figure 11 . OutCRC CRC over the ResponseSPDU , see 7.2.3.6 . OutNonSafetyData "Non-safe data" see 7.2.1.11 . Table
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety0x14 B, E Yes CRCerrIgn The SafetyConsumer has discarded a message due to a CRC error (data corruption). 0x05 A Yes CRCerrOA The SafetyConsumer has switched to fail-safe substitute ... values due to a CRC error (data corruption). Operator acknowledgment is required. 0x15 B, C Yes CoIDerrIgn The SafetyConsumer has discarded a message due to an incorrect ConsumerID. 0x06
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.1.1 Generaldetails on the RequestSPDUDataType definition. NOTE 1 The RequestSPDU does not contain a CRC signature. Figure 11 - RequestSPDU Figure 12 shows the structure of a ResponseSPDU which originates
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.1.5 ResponseSPDU: SafetyDatacomprised of only a single basic OPC UA Variable . For the calculation of the CRC signature, the order in which this data is processed by the calculation is important. SafetyProvider
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.1.10 ResponseSPDU: CRCResponseSPDU: CRC [RQ7.7] The ResponseSPDU CRC shall be used to detect data corruption. See 7.2.3.6 on how it is calculated in the SafetyProvider and how it is checked
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.1.11 ResponseSPDU: NonSafetyDatatransmit NonSafetyData values (e.g. diagnostic information) together with SafetyData consistently. NonSafetyData is not CRC -protected and can stem from an unsafe source. [RQ7.9] When presented to the safety application
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.2.4 SafetyProvider state diagramFlags, the SafetyData and the NonSafetyData , as well as the calculated CRC . See 7.2.3.1 Table 31 shows the states of a SafetyProvider instance. The SafetyProvider does not check for correct
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.2.5 SafetyConsumer state diagramCRCCheck_i Boolean Local variable used to store the result of the CRC check SPDUCheck_i Boolean Local variable used to store the result of the additional SPDU checks SPDU ... ResponseSPDU is characterized by a change in the MNR . S15_CRCCheckSPDU // Check CRC uint32 CRC_calc CRCCheck_i:= (CRC_calc == ResponseSPDU.CRC) // see 7.2.3.6 on how to calculate CRC_calc
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.3.1 Build ResponseSPDUcalculation of the SPDU_ID , see 7.2.3.2 . For the calculation of the CRC
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetyorientation using Euler angles. [RQ7.19] SafetyStructureSignature shall be calculated as a 32 bit CRC signature (polynomial: 0xF4ACFB13, see Clause B.1 ) over SafetyStructureIdentifier (encoding: UTF-8), SafetyStructureSignatureVersion and the sequence ... this case. The terminating zero of SafetyStructureIdentifier shall not be considered when calculating the CRC . [RQ7.20] SafetyStructureIdentifier may be visible in the OPC UA Information Model for diagnostic purposes
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.3.6 Calculation of a CRC signatureCalculation of a CRC signature The SafetyProvider calculates the CRC signature ( ResponseSPDU.CRC ) and sends it to the SafetyConsumer as part of the ResponseSPDU . This enables the SafetyConsumer to check ... ResponseSPDU including the SafetyData , flags , MNR , SafetyConsumerID and SPDU_ID by recalculating the CRC signature (CRC_calc). [RQ7.22] The generator polynomial 0xF4ACFB13 shall be used for the 32-Bit CRC
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetymultiplied by the so-called conditional residual error probability Pre,cond. For the CRC mechanism used in this document, it holds: Pre,cond ≤ 4,0 × 10-10 This leads ... justified by extensive numerical evaluation of the 32-bit CRC generator polynomial in use (0xF4ACFB13). The results of this evaluation, executed for all relevant data lengths and all relevant values
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetylisted here. Generally: Number of retries in the underlying standard transmission system : No restrictions CRC polynomials used inside the underlying standard transmission system (e.g. Ethernet, TCP, …): No restrictions Message storing
-
OPC-10000-15 – OPC Unified Architecture - Part 15: SafetySafetyConsumer . Whenever the SafetyConsumer detects a mismatch of the SafetyConsumerID , SPDU_ID , MNR or CRC , it will only continue operating if the last occurrence of such an error happened more
-
OPC-10000-15 – OPC Unified Architecture - Part 15: SafetyRQ5.3 Process and monitor safety measures in the SCL 5.3 Safety measures RQ5.4 Start CRC calculation with value "1" 5.5 Requirements for CRC calculation RQ5.5 Use CRC result ... instead of "0" 5.5 Requirements for CRC calculation RQ5.6 Ignore all-zero SPDUs 5.5 Requirements for CRC calculation RQ6.1 Singleton SafetyACSet Folder 6.2.2.1 SafetyACSet Object RQ6.2 Objects
-
OPC-10000-15 – OPC Unified Architecture - Part 15: SafetyCRC calculation using tables, for the polynomial 0xF4ACFB13 The calculation of a 32-bit CRC signature over an array of N octets with the help of lookup tables, using ... data, see Figure 23 uint32_t result = 1; // seed value for the calculated CRC int16_t i; // index for(i=N-1;i>=0;i--) // process array in reversed