Search
8 result(s) for DataType Duration
-
OPC-10000-14 – OPC Unified Architecture - Part 14: PubSub6.2.6.2 PublishingIntervalPublishingInterval The PublishingInterval with the DataType Duration defines the interval in milliseconds for publishing NetworkMessages and the embedded DataSetMessages created by the related DataSetWriters . Negative values are invalid ... buffer and all Events that do not fit into the buffer are discarded. The Duration DataType is a subtype of Double and allows configuration of intervals smaller than a millisecond
-
OPC-10000-14 – OPC Unified Architecture - Part 14: PubSub6.2.6.3 KeepAliveTimeKeepAliveTime The KeepAliveTime with DataType Duration defines the time in milliseconds until the Publisher sends a keep alive DataSetMessage in the case where no DataSetMessage was sent in this period
-
OPC-10000-14 – OPC Unified Architecture - Part 14: PubSub6.3.1.1.5 SamplingOffsetSamplingOffset The SamplingOffset with the DataType Duration defines the time in milliseconds for the offset of creating the NetworkMessage in the PublishingInterval cycle. Any negative value indicates that the optional ... necessary to create the NetworkMessage in time for sending at the PublishingOffset . The Duration DataType is a subtype of Double and allows configuration of intervals smaller than a millisecond
-
OPC-10000-14 – OPC Unified Architecture - Part 14: PubSub6.3.1.1.6 PublishingOffsetPublishingOffset The PublishingOffset is an array of DataType Duration that defines the time in milliseconds for the offset in the PublishingInterval cycle of sending the NetworkMessage to the network ... PublishingOffset is not configured and the timing inside the PublishingInterval is application specific. The Duration DataType is a subtype of Double and allows configuration of intervals smaller than a millisecond
-
OPC-10000-14 – OPC Unified Architecture - Part 14: PubSub6.3.1.4.7 PublishingIntervalPublishingInterval The PublishingInterval with DataType Duration indicates the rate the Publisher sends NetworkMessages related to the DataSet . The start time for the periodic execution of the Subscriber shall be calculated
-
OPC-10000-14 – OPC Unified Architecture - Part 14: PubSub6.3.1.4.8 ReceiveOffsetReceiveOffset The ReceiveOffset with DataType Duration defines the time in milliseconds for the offset in the PublishingInterval cycle for the expected receive time of the NetworkMessage for the DataSet from
-
OPC-10000-14 – OPC Unified Architecture - Part 14: PubSub6.3.1.4.9 ProcessingOffsetProcessingOffset The ProcessingOffset with DataType Duration defines the time in milliseconds for the offset in the PublishingInterval cycle when the received DataSet need to be processed by the application
-
OPC-10000-14 – OPC Unified Architecture - Part 14: PubSub6.4.1.3.2 MessageRepeatDelayMessageRepeatDelay The MessageRepeatDelay with DataType Duration defines the time between NetworkMessage repeats in milliseconds. The parameter shall be ignored if the parameter MessageRepeatCount