The PtContactorAttributesType provides the common asset attributes of a contactor and is formally defined in Table 111. Additional attributes can be found in IEC CDD 62683DB.
Table 111 – PtContactorAttributesType Definition
Attribute |
Value |
||||
BrowseName |
PtContactorAttributesType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the PtAssetAttributesType defined in chapter 7.7 |
|||||
0:HasProperty |
Variable |
OperationalCurrentAC3At400VRated |
0:Float |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberofMainContactsNO |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
ControlVoltageAC50HzRangeRated |
0:Range |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberofAuxiliaryContactsNO |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberofAuxiliaryContactsNC |
0:UInt16 |
0:PropertyType |
M, RO |
Conformance Units |
|||||
Powertrain Attributes Information |
All PtContactorAttributesType properties are described in IEC CDD.
The properties of the PtContactorAttributesType have additional references which are defined in Table 112.
Table 112 – PtContactorAttributesType Additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
OperationalCurrentAC3At400VRated |
0:HasDictionaryEntry |
0:True |
|
NumberofMainContactsNO |
0:HasDictionaryEntry |
0:True |
|
ControlVoltageAC50HzRangeRated |
0:HasDictionaryEntry |
0:True |
|
NumberofAuxiliaryContactsNO |
0:HasDictionaryEntry |
0:True |
|
NumberofAuxiliaryContactsNC |
0:HasDictionaryEntry |
0:True |
The PtElectronicOverloadRelayAttributesType provides the common asset attributes of a contactor and is formally defined in Table 113. Additional attributes can be found in IEC Common Data Dictionary (CDD) 62683DB.
Table 113 – PtElectronicOverloadRelayAttributesType Definition
Attribute |
Value |
||||
BrowseName |
PtElectronicOverloadRelayAttributesType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the PtAssetAttributesType defined in chapter 7.7 |
|||||
0:HasProperty |
Variable |
OverloadCurrentSettingRange |
0:Range |
0:PropertyType |
M, RO |
0:HasComponent |
Variable |
TripClass |
0:UInt16 |
0:MultiStateValueDiscreteType |
M, RO |
0:HasProperty |
Variable |
VoltageRated |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberofAuxiliaryContactsNC |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
PhaseLossSensitiveSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
JamDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
StallDetectionSuported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
GroundEarthFaultDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
Conformance Units |
|||||
Powertrain Attributes Information |
TripClass provides the classification for thermal protective devices regarding the value of the maximum tripping time in seconds. The values of the MultiStateValueDiscreteType variable are defined in Table 114 and shall be used. The values 0-199 are reserved for future extensions of this specification. The values 200-299 shall be used for vendor-specific extensions of this variable.
Table 114 – PtElectronicOverloadRelayAttributesType values for child nodes
BrowsePath |
Value Attribute |
Description Attribute |
||
|
[ { "Value": 0, "DisplayName": "CLASS_2E", "Description": "Thermal protection class 2E" }, { "Value": 1, "DisplayName": "CLASS_3E", "Description": "Thermal protection class 3E" }, { "Value": 2, "DisplayName": "CLASS_5", "Description": "Thermal protection class 5" }, { "Value": 3, "DisplayName": "CLASS_5E", "Description": "Thermal protection class 5E" }, { "Value": 4, "DisplayName": "CLASS_10", "Description": "Thermal protection class 10" }, { "Value": 5, "DisplayName": "CLASS_10A", "Description": "Thermal protection class 10A" }, { "Value": 6, "DisplayName": "CLASS_10E", "Description": "Thermal protection class 10E" }, { "Value": 7, "DisplayName": "CLASS_20", "Description": "Thermal protection class 20" }, { "Value": 8, "DisplayName": "CLASS_20E", "Description": "Thermal protection class 20E" }, { "Value": 9, "DisplayName": "CLASS_30", "Description": "Thermal protection class 30" }, { "Value": 10, "DisplayName": "CLASS_30E", "Description": "Thermal protection class 30E" }, { "Value": 11, "DisplayName": "CLASS_40E", "Description": "Thermal protection class 40E" } ] |
|
The 0:EnumValues of the TripClass have additional CDD entries which are defined in Table 125.
Table 115 – TripClass CDD entries
0:EnumValues |
CDD entries |
CLASS_2E |
|
CLASS_3E |
|
CLASS_5 |
|
CLASS_5E |
|
CLASS_10 |
|
CLASS_10A |
|
CLASS_10E |
|
CLASS_20 |
|
CLASS_20E |
|
CLASS_30 |
|
CLASS_30E |
|
CLASS_40E |
All other PtElectronicOverloadRelayAttributesType properties are described in IEC Common Data Dictionary (CDD).
The properties of the PtElectronicOverloadRelayAttributesType have additional references which are defined in Table 116.
Table 116 – PtElectronicOverloadRelayAttributesType Additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
|
|
|
|
OverloadCurrentSettingRange |
0:HasDictionaryEntry |
0:True |
|
TripClass |
0:HasDictionaryEntry |
0:True |
|
VoltageRated |
0:HasDictionaryEntry |
0:True |
|
NumberofAuxiliaryContactsNC |
0:HasDictionaryEntry |
0:True |
|
PhaseLossSensitiveSupported |
0:HasDictionaryEntry |
0:True |
|
JamDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
StallDetectionSuported |
0:HasDictionaryEntry |
0:True |
|
GroundEarthFaultDetectionSupported |
0:HasDictionaryEntry |
0:True |
The PtMotorStarterAttributesType provides the common asset attributes of a motor starter and is formally defined in Table 117. Additional attributes can be found in IEC CDD 62683DB.
Table 117 – PtMotorStarterAttributesType Definition
Attribute |
Value |
||||
BrowseName |
PtMotorStarterAttributesType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the PtAssetAttributesType defined in chapter 7.7 |
|||||
0:HasProperty |
Variable |
OverloadCurrentSettingRange |
0:Range |
0:PropertyType |
M, RO |
0:HasComponent |
Variable |
TripClass |
0:UInt16 |
0:MultiStateValueDiscreteType |
M, RO |
0:HasProperty |
Variable |
OperationalCurrentAC3At400VRated |
0:Float |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberofMainContactsNO |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
ControlVoltageAC50HzRangeRated |
0:Range |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberofAuxiliaryContactsNO |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberofAuxiliaryContactsNC |
0:UInt16 |
0:PropertyType |
M, RO |
Conformance Units |
|||||
Powertrain Attributes Information |
TripClass provides the classification for thermal protective devices regarding the value of the maximum tripping time in seconds. The values of the MultiStateValueDiscreteType variable are defined in Table 118 and shall be used. The values 0-199 are reserved for future extensions of this specification. The values 200-299 shall be used for vendor-specific extensions of this variable.
Table 118 – PtMotorStarterAttributesType Values for child nodes
BrowsePath |
Value Attribute |
Description Attribute |
||
|
[ { "Value": 0, "DisplayName": "CLASS_2E", "Description": "Thermal protection class 2E" }, { "Value": 1, "DisplayName": "CLASS_3E", "Description": "Thermal protection class 3E" }, { "Value": 2, "DisplayName": "CLASS_5", "Description": "Thermal protection class 5" }, { "Value": 3, "DisplayName": "CLASS_5E", "Description": "Thermal protection class 5E" }, { "Value": 4, "DisplayName": "CLASS_10", "Description": "Thermal protection class 10" }, { "Value": 5, "DisplayName": "CLASS_10A", "Description": "Thermal protection class 10A" }, { "Value": 6, "DisplayName": "CLASS_10E", "Description": "Thermal protection class 10E" }, { "Value": 7, "DisplayName": "CLASS_20", "Description": "Thermal protection class 20" }, { "Value": 8, "DisplayName": "CLASS_20E", "Description": "Thermal protection class 20E" }, { "Value": 9, "DisplayName": "CLASS_30", "Description": "Thermal protection class 30" }, { "Value": 10, "DisplayName": "CLASS_30E", "Description": "Thermal protection class 30E" }, { "Value": 11, "DisplayName": "CLASS_40E", "Description": "Thermal protection class 40E" } ] |
|
The 0:EnumValues of the TripClass have additional references to the CDD which are defined in Table 119.
Table 119 – TripClass CDD entries
EnumValue |
CDD Entry |
CLASS_2E |
|
CLASS_3E |
|
CLASS_5 |
|
CLASS_5E |
|
CLASS_10 |
|
CLASS_10A |
|
CLASS_10E |
|
CLASS_20 |
|
CLASS_20E |
|
CLASS_30 |
|
CLASS_30E |
|
CLASS_40E |
All other PtMotorStarterAttributesType properties are descripted in IEC Common Data Dictionary (CDD).
The properties of the PtMotorStarterAttributesType have additional references which are defined in Table 120.
Table 120 – PtMotorStarterAttributesType Additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
OverloadCurrentSettingRange |
0:HasDictionaryEntry |
0:True |
|
TripClass |
0:HasDictionaryEntry |
0:True |
|
OperationalCurrentAC3At400VRated |
0:HasDictionaryEntry |
0:True |
|
NumberofMainContactsNO |
0:HasDictionaryEntry |
0:True |
|
ControlVoltageAC50HzRangeRated |
0:HasDictionaryEntry |
0:True |
|
NumberofAuxiliaryContactsNO |
0:HasDictionaryEntry |
0:True |
|
NumberofAuxiliaryContactsNC |
0:HasDictionaryEntry |
0:True |
The PtSoftStarterAttributesType provides the common asset attributes of a soft-starter and is formally defined in Table 121. Additional attributes can be found in IEC CDD 62683DB.
Table 121 – PtSoftStarterAttributesType Definition
Attribute |
Value |
||||
BrowseName |
PtSoftStarterAttributesType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the PtAssetAttributesType defined in chapter 7.7 |
|||||
0:HasProperty |
Variable |
IntegratedByPassSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
OperationalCurrent40CRated |
0:Float |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
OperationalVoltageRangeRated |
0:Range |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
MotorOverloadProtectionIntegrated |
0:Boolean |
0:PropertyType |
M, RO |
Conformance Units |
|||||
Powertrain Attributes Information |
PtSoftStarterAttributesType properties are descripted in IEC Common Data Dictionary (CDD).
The properties of the PtMotorStarterAttributesType have additional references which are defined in Table 122.
Table 122 – PtSoftStarterAttributesType Additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
IntegratedByPassSupported
|
0:HasDictionaryEntry |
0:True |
|
OperationalCurrent40CRated
|
0:HasDictionaryEntry |
0:True |
|
OperationalVoltageRangeRated
|
0:HasDictionaryEntry |
0:True |
|
MotorOverloadProtectionIntegrated
|
0:HasDictionaryEntry |
0:True |
|
The PtMotorManagementDeviceAttributesType provides the common asset attributes of a motor management device and is formally defined in Table 123. Additional attributes can be found in IEC CDD 62683DB.
Table 123 – PtMotorManagmentDeviceAttributesType Definition
Attribute |
Value |
||||
BrowseName |
PtMotorManagementDeviceAttributesType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the PtAssetAttributesType defined in chapter 7.7 |
|||||
0:HasProperty |
Variable |
OverloadCurrentSettingRange |
0:Range |
0:PropertyType |
M, RO |
0:HasComponent |
Variable |
TripClass |
0:UInt16 |
0:MultiStateValueDiscreteType |
M, RO |
0:HasProperty |
Variable |
PhaseLossSensitiveSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
JamDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
StallDetectionSuported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
GroundEarthFaultDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
LoadSheddingSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
OverUnderCurrentDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
OverUnderVoltageDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
CurrentImbalanceDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
PhaseReversalDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
CosPhiVariationDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
VoltageMonitoringSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
UnderPowerDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberOfPtcThermistorInputs |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberOfAnalogInputs |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberOfDigitalOutputs |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberOfDigitalInputs |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
ControlVoltageAC50HzRangeRated |
0:Range |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
HMIPortSupported |
0:Boolean |
0:PropertyType |
M, RO |
Conformance Units |
|||||
Powertrain Attributes Information |
TripClass provides the classification for thermal protective devices regarding the value of the maximum tripping time in seconds. The values of the MultiStateValueDiscreteType variable are defined in Table 124 and shall be used. The values 0-199 are reserved for future extensions of this specification. The values 200-299 shall be used for vendor-specific extensions of this variable.
Table 124 – PtMotorManagementDeviceAttributesType values for child nodes
BrowsePath |
Value Attribute |
Description Attribute |
||
|
[ { "Value": 0, "DisplayName": "CLASS_2E", "Description": "Thermal protection class 2E" }, { "Value": 1, "DisplayName": "CLASS_3E", "Description": "Thermal protection class 3E" }, { "Value": 2, "DisplayName": "CLASS_5", "Description": "Thermal protection class 5" }, { "Value": 3, "DisplayName": "CLASS_5E", "Description": "Thermal protection class 5E" }, { "Value": 4, "DisplayName": "CLASS_10", "Description": "Thermal protection class 10" }, { "Value": 5, "DisplayName": "CLASS_10A", "Description": "Thermal protection class 10A" }, { "Value": 6, "DisplayName": "CLASS_10E", "Description": "Thermal protection class 10E" }, { "Value": 7, "DisplayName": "CLASS_20", "Description": "Thermal protection class 20" }, { "Value": 8, "DisplayName": "CLASS_20E", "Description": "Thermal protection class 20E" }, { "Value": 9, "DisplayName": "CLASS_30", "Description": "Thermal protection class 30" }, { "Value": 10, "DisplayName": "CLASS_30E", "Description": "Thermal protection class 30E" }, { "Value": 11, "DisplayName": "CLASS_40E", "Description": "Thermal protection class 40E" } ] |
|
The 0:EnumValues of the TripClass have additional CDD entries which are defined in Table 125.
Table 125 – TripClass CDD entries
0:EnumValues |
CDD entries |
CLASS_2E |
|
CLASS_3E |
|
CLASS_5 |
|
CLASS_5E |
|
CLASS_10 |
|
CLASS_10A |
|
CLASS_10E |
|
CLASS_20 |
|
CLASS_20E |
|
CLASS_30 |
|
CLASS_30E |
|
CLASS_40E |
All other PtMotorManagementDeviceAttributesType properties are descripted in IEC Common Data Dictionary (CDD). The properties of the PtMotorManagementDeviceType have additional references which are defined in Table 126.
Table 126 – PtMotorManagementDeviceAttributesType Additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
|
|
|
|
OverloadCurrentSettingRange |
0:HasDictionaryEntry |
0:True |
|
TripClass |
0:HasDictionaryEntry |
0:True |
|
PhaseLossSensitiveSupported |
0:HasDictionaryEntry |
0:True |
|
JamDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
StallDetectionSuported |
0:HasDictionaryEntry |
0:True |
|
GroundEarthFaultDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
LoadSheddingSupported |
0:HasDictionaryEntry |
0:True |
|
OverUnderCurrentDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
OverUnderVoltageDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
CurrentImbalanceDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
PhaseReversalDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
CosPhiVariationDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
VoltageMonitoringSupported |
0:HasDictionaryEntry |
0:True |
|
UnderPowerDetectionSupported |
0:HasDictionaryEntry |
0:True |
|
NumberOfPtcThermistorInputs |
0:HasDictionaryEntry |
0:True |
|
NumberOfAnalogInputs |
0:HasDictionaryEntry |
0:True |
|
NumberOfDigitalOutputs |
0:HasDictionaryEntry |
0:True |
|
NumberOfDigitalInputs |
0:HasDictionaryEntry |
0:True |
|
ControlVoltageAC50HzRangeRated |
0:HasDictionaryEntry |
0:True |
|
HMIPortSupported |
0:HasDictionaryEntry |
0:True |