The PtElectronicOverloadRelayAttributesType provides the common asset attributes of a contactor and is formally defined in Table 113. Additional attributes can be found in IEC Common Data Dictionary (CDD) 62683DB.
Table 113 – PtElectronicOverloadRelayAttributesType Definition
Attribute |
Value |
||||
BrowseName |
PtElectronicOverloadRelayAttributesType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the PtAssetAttributesType defined in chapter 7.7 |
|||||
0:HasProperty |
Variable |
OverloadCurrentSettingRange |
0:Range |
0:PropertyType |
M, RO |
0:HasComponent |
Variable |
TripClass |
0:UInt16 |
0:MultiStateValueDiscreteType |
M, RO |
0:HasProperty |
Variable |
VoltageRated |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
NumberofAuxiliaryContactsNC |
0:UInt16 |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
PhaseLossSensitiveSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
JamDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
StallDetectionSuported |
0:Boolean |
0:PropertyType |
M, RO |
0:HasProperty |
Variable |
GroundEarthFaultDetectionSupported |
0:Boolean |
0:PropertyType |
M, RO |
Conformance Units |
|||||
Powertrain Attributes Information |