The EnergyStandbyManagementType ObjectTypes provide access to the Standby Management functionality of one Standby Management Entity. Parallel access of Clients to the read only data shall be possible but write operations and Method invocation can be limited to one Client at a time with the Lock Object.

Table 12 – EnergyStandbyManagementType Definition

Attribute

Value

BrowseName

EnergyStandbyManagementType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType defined in [OPC 10000-5].

0:HasComponent

Variable

StandbyManagementStatus

Byte

0:MultiStateDiscreteType

M, RO

0:HasComponent

Object

EnergySavingModeStatus

EnergySavingModeStatusType

M

0:HasComponent

Object

EnergySavingModes

EnergySavingModesContainerType

O

0:HasComponent

Variable

PauseTime

0:Duration

0:BaseDataVariableType

M, RW

0:HasComponent

Object

2:Lock

2:LockingServicesType

O

0:HasComponent

Method

StartPause

O

0:HasComponent

Method

EndPause

O

0:HasComponent

Method

SwitchToEnergySavingMode

O

The StandbyManagementStatus Variable shall contain the current state of the Standby Management. The value of this Variable shall be consistent with the content of the EnergySavingModeStatus Object.

The values of the 0:EnumStrings of the StandbyManagementStatus shall follow the definition of Table 13. Each instance shall have the values 0 to 8. Element numbers 9-15 are reserved for future use. If vendors add specific elements, the range 9-15 shall be filled with ‘null’-strings.

Table 13 – Defined elements of EnumStrings array of StandbyManagementStatus Variable

Element number (starting with 0)

Message (for locale “en”)

0

Energy saving disabled

1

Power Off

2

Ready to operate

3

Moving to Energy Saving Mode

4

Energy saving mode

5

Moving to ready to operate

6

Moving to Sleep mode WOL

7

Sleep mode WOL

8

Wake up WOL

9-15

‘null’-String

16 – 255

Vendor specific

The Variables of the EnergyStandbyManagementType have additional Attributes defined in Table 14

Table 14 – EnergyStandbyManagementType Attribute values for child Nodes

Source Path

Value Attribute

StandbyManagementStatus

0:EnumStrings

Energy saving disabled

Power Off

Ready to operate

Moving to Energy Saving Mode

Energy saving mode

Moving to ready to operate

Moving to Sleep mode WOL

Sleep mode WOL

Wake up WOL

The EnergySavingModes container Object contains References to EnergySavingModeType Objects representing the supported Energy Saving Modes.

Writing the PauseTime Variable can be used to update the pause time alternatively to the StartPause Method. Setting the PauseTime Variable with a value not equal to 0 shall have the same effect as invoking the StartPause Method passing the PauseTime value. Setting the PauseTime Variable with a value equal to 0 shall have the same effect as invoking the EndPause Method. An additional benefit is that the Variable PauseTime can be used in a PubSub communication scenario where the PauseTime is distributed by a central time management client using a broadcast telegram to which every Standby Management Entity subscribes.

The Lock Object ensures exclusive write access and Method call for one client. Write access and Method calls from Clients shall be blocked unless the client has locked the Object by invoking the InitLock Method of the Lock Object.

The StartPause Method starts the transition to an Energy Saving Mode. The SwitchToEnergySavingMode allows the transition into a specific Energy Saving Mode. The EndPause Method ends the Energy Saving Mode.

A RepresentedBy Reference may connect the Object to the representing PROFIenergy service access point Object (see PeServiceAccessPointType). The BrowseName of the Reference shall be “PESAP”.

This Method starts the transition into an Energy Saving Mode.

Signature

StartPause (

[in] 0:DurationPauseTime

[out] 0:Byte ModeID

[out] 0:DurationCurrentTimeToDestination

[out] 0:DurationRegularTimeToOperate

[out] 0:DurationTimeMinLengthOfStay

[out] 0:Byte ReturnCode

);

Argument

Description

PauseTime

Requested pause time.

ModeID

ID of the destination Energy Saving Mode if successful, otherwise 0.

CurrentTimeToDestination

Time needed to reach the Energy Saving Mode if successful, otherwise 0.

RegularTimeToOperate

Time needed to reach “Ready to operate” again if the destination Energy Saving Mode will be regularly terminated if successful, otherwise 0.

TimeMinLengthOfStay

Time of minimum stay in the destination Energy Saving Mode if successful, otherwise 0.

ReturnCode

Return code. See Table 16.

The Method Result Codes (defined in Call Service) are defined in Table 15.

This Method initiates a switch to a certain Energy Saving Mode.

Signature

SwitchToEnergySavingMode (

[in] 0:Byte ModeID

[out] 0:Byte EffectiveModeID

[out] 0:DurationCurrentTimeToDestination

[out] 0:DurationRegularTimeToOperate

[out] 0:DurationTimeMinLengthOfStay

[out] 0:Byte ReturnCode

);

Argument

Description

ModeID

ID of the requested Energy Saving Mode.

EffectiveModeID

ID of the effectively chosen Energy Saving Mode if successful, otherwise ID of current mode.

CurrentTimeToDestination

Time needed to reach the destination Energy Saving Mode if successful, otherwise 0.

RegularTimeToOperate

Time needed to reach “Ready to operate” again if the destination Energy Saving Mode will be regularly terminated if successful, otherwise 0.

TimeMinLengthOfStay

Time of minimum stay in the destination Energy Saving Mode if successful, otherwise 0.

ReturnCode

Return code. See table Table 16.

The Method Result Codes (defined in Call Service) are defined in Table 15.

This Method ends the current Energy Saving Mode.

Signature

EndPause (

[out] 0:DurationCurrentTimeToOperate

[out] 0:Byte ReturnCode

);

Argument

Description

CurrentTimeToOperate

Time needed to reach “Ready to operate” if successful, 0.

ReturnCode

Return code. See table Table 16.

The Method Result Codes (defined in Call Service) are defined in Table 15.

Table 15 shows the possible values for the Method call result codes.

Table 15 – Possible Method result codes

Result Code

Description

Good

The Method execution was successful and the ReturnCode parameter has the value 0x00 (”Success”)

Uncertain

The Method execution was successful, but the ReturnCode parameter indicates an error.

Bad_UserAccessDenied

The user has not the right to execute the Method. The client shall not evaluate the ReturnCode parameter.

Bad_UnexpectedError

The server is not able to execute the function because an unexpected error occurred. The device might be temporarily unavailable or unreachable due to network failure. The client shall not evaluate the ReturnCode parameter.

Table 16 shows the possible values for the out parameter ReturnCode.

Table 16 – Possible ReturnCode parameter Values

ReturnCode

Description

0x00

Success.

0x50

No suitable energy-saving mode available.

0x52

No switch to requested energy-saving mode because of invalid mode ID.

0x53

No switch to Energy Saving Mode because of state operate.

0x54

Service or function not available due to internal device status.

Table 17 – EnergySavingModesContainerType Definition

Attribute

Value

BrowseName

EnergySavingModesContainerType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType defined in [OPC 10000-5].

0:HasComponent

Object

<EnergySavingModes>

EnergySavingModeType

MP

Table 18 – EnergySavingModeStatusType Definition

Attribute

Value

BrowseName

EnergySavingModeStatusType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType defined in [OPC 10000-5].

0:HasComponent

Variable

CurrentTransitionData

StandbyModeTransitionDataType

0:BaseDataVariableType

O, RO

0:HasComponent

Variable

StateInformation

EnergyStateInformationDataType

0:BaseDataVariableType

M, RO

The CurrentTransitionData Variable contains details for the state transition indicated by the StateInformation Variable.

The StateInformation Variable contains details for the actual Energy Saving Mode state.

The EnergySavingModeType provides detailed information for a specific Energy Saving Mode.

Table 19 – EnergySavingModeType Definition

Attribute

Value

BrowseName

EnergySavingModeType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType defined in [OPC 10000-5].

0:HasProperty

Variable

ID

0:Byte

0:PropertyType

M, RO

0:HasProperty

Variable

DynamicData

0:Boolean

0:PropertyType

M, RO

0:HasComponent

Variable

TimeMinPause

0:Duration

0:BaseDataVariableType

M, RO

0:HasComponent

Variable

TimeToPause

0:Duration

0:BaseDataVariableType

M, RO

0:HasComponent

Variable

TimeMinLengthOfStay

0:Duration

0:BaseDataVariableType

M, RO

0:HasComponent

Variable

TimeMaxLengthOfStay

0:Duration

0:BaseDataVariableType

M, RO

0:HasComponent

Variable

RegularTimeToOperate

0:Duration

0:BaseDataVariableType

M, RO

0:HasComponent

Variable

ModePowerConsumption

0:Float

0:AnalogUnitType

M, RO

0:HasComponent

Variable

EnergyConsumptionToPause

0:Float

0:AnalogUnitType

M, RO

0:HasComponent

Variable

EnergyConsumptionToOperate

0:Float

0:AnalogUnitType

M, RO

The BrowseName shall contain a unique name for the Energy Saving Mode.

The ID Variable shall contain a unique mode ID for the Energy Saving Mode. The mode ID’s 0x00, 0xF0, 0xFE and 0xFF are reserved for predefined states.

DynamicData shall indicate whether the time, energy consumption and power values can vary (slightly) during runtime.

The TimeMinPause Variable shall contain the minimum pause time for this Energy Saving Mode.

The TimeToPause Variable shall contain the expected time to switch to this Energy Saving Mode.

The TimeMinLengthOfStay Variable shall contain the time of minimum stay in this Energy Saving Mode.

The TimeMaxLengthOfStay Variable shall contain the time of maximum stay in this Energy Saving Mode.

The RegularTimeToOperate Variable shall contain the time value to reach ”Ready to operate” (see Figure 1) if this Energy Saving Mode will be regularly terminated.

The ModePowerConsumption Variable shall contain the power consumption in this Energy Saving Mode. Unit: [kW].

The EnergyConsumptionToPause Variable shall contain the energy consumption from ”Ready to operate” to this Energy Saving Mode. Unit: [kWh].

The EnergyConsumptionToOperate Variable shall contain the energy consumption from this Energy Saving Mode to ”Ready to operate”. Unit: [kWh].

Mapping to PROFIenergy properties:

BrowseName

PE Service

PE Service Data Response Field

ID

List_Energy_Saving_Modes

PE_Mode_ID

TimeMinPause

Get_Mode

Time_min_Pause

TimeToPause

Get_Mode

Time_to_Pause

TimeMinLengthOfStay

Get_Mode

Time_min_length_of_stay

TimeMaxLengthOfStay

Get_Mode

Time_max_length_of_stay

RegularTimeToOperate

Get_Mode

Regular_time_to_operate

ModePowerConsumption

Get_Mode

Mode_Power_Consumption

EnergyConsumptionToPause

Get_Mode

Energy_Consumption_to_pause

EnergyConsumptionToOperate

Get_Mode

Energy_Consumption_to_operate

The Energy Measurement Objects provide access to the Energy Measurement values. For each Metering Point one EnergyMeasurementType Object shall exist.

The EnergyMeasurementType contains References to MeasurementValueType Objects.

Table 20 – EnergyMeasurementType Definition

Attribute

Value

BrowseName

EnergyMeasurementType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType

0:HasProperty

Variable

PeObjectNumber

0:UInt16

0:PropertyType

M, RO

0:HasComponent

Variable

<MeasurementValue>

0:Number

MeasurementValueType

MP, RO

0:HasComponent

Method

ResetEnergyCounter

O

The PeObjectNumber Variable shall contain the Object number of the related PROFIenergy measurement Object.

The MeasurementValue Variable contains one actual measurement value. For each measurement value of a Metering Point one MeasurementValueType Variable shall exist.

If one of the MeasurementValueType Variables is used as energy counter, the ResetEnergyCounter Method can be used to set the value of this Variable to 0. See section 9.1, ”MeasurementValueType” for further details.

A RepresentedBy Reference may connect the Object to the representing PROFIenergy service access point Object (see PeServiceAccessPointType). The BrowseName of the Reference shall be “PESAP”. If the PESAP is not part of the Information Model, the RepresentedBy Reference in the EnergyMeasurementType Object is omitted.

Mapping to PROFIenergy properties:

BrowseName

PE Service

PE Service Data Response Field

PeObjectNumber

Get_Measurement_List_with_Object_Number

Object_Number

EnergyMeasurementType Objects should support Interfaces for standardized energy data profiles, so called EnergyProfiles. The supported measurement values demanded by an energy data profile are specified by Interfaces applied to instances of the EnergyMeasurementType.

Table 21 shows the definitions of the Interfaces for the standardized energy data profiles. The EnergyProfiles represent standard Energy Measurement use cases and are therefore the preferred way to represent Energy Measurement data. It is recommended to support at least one of the EnergyProfiles.

Table 21 – Interfaces for EnergyProfiles

EnergyProfile

MeasurementValue

DataType

Accuracy

InterfaceType

BrowseName

Symbol

EngineeringUnit

IEnergyProfileE0Type

E0

AcCurrent

IL1IL2 IL3

A

AcPeDataType

≤10%

IEnergyProfileE1Type

E1

AcActivePowerTotal

∑P

W

Float

≤5%

IEnergyProfileE2Type

E2

AcActivePowerTotal

∑P

W

Float

≤5%

AcActiveEnergyTotalImportLp

∑↓E

W·h

Float

AcActiveEnergyTotalExportLp

∑↑E

W·h

Float

IEnergyProfileE3Type

E3

AcActivePower

PL1PL2 PL3

W

AcPeDataType

≤2%

AcReactivePower

QtotL1 QtotL2 QtotL3

var

AcPeDataType

AcActiveEnergyTotalImportHp

∑↓E

W·h

Double

AcActiveEnergyTotalExportHp

∑↑E

W·h

Double

AcReactiveEnergyTotalImportHp

∑↓EQ

Varh

Double

AcReactiveEnergyTotalExportHp

∑↑EQ

Varh

Double

AcVoltagePe

UL1NUL2NUL3N

V

AcPeDataType

AcVoltagePp

UL1L2 UL2L3 UL3L1

V

AcPpDataType

AcCurrent

IL1IL2 IL3

A

Float

AcPowerFactor

λL1λL2λL3

Float

IEnergyProfileD0Type

D0

DcCurrent

I

A

Float

≤10%

Figure 11 shows an example how different EnergyProfiles can be supported by EnergyMeasurementType Object instances.

image015.png

Figure 11 – Implementing different EnergyProfiles

The IEnergyProfileE0Type contains the References to MeasurementValueType Variables needed for EnergyProfile E0.

Table 22 – IEnergyProfileE0Type Definition

Attribute

Value

BrowseName

IEnergyProfileE0Type

IsAbstract

True

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseInterfaceType defined in [OPC 10001-7]

0:HasComponent

Variable

AcCurrent

AcPeDataType

MeasurementValueType

M

Table 23 – IEnergyProfileE0Type Attribute values for child Nodes

Source Path

Value Attribute

AcCurrent

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4279632

DisplayName: A

Description: ampere

The IEnergyProfileE1Type contains the References to MeasurementValueType Variables needed for EnergyProfile E1.

Table 24 – IEnergyProfileE1Type Definition

Attribute

Value

BrowseName

IEnergyProfileE1Type

IsAbstract

True

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseInterfaceType defined in [OPC 10001-7]

0:HasComponent

Variable

AcActivePowerTotal

0:Float

MeasurementValueType

M

Table 25 – IEnergyProfileE1Type Attribute values for child Nodes

Source Path

Value Attribute

AcActivePowerTotal

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5723220

DisplayName: W

Description: watt

The IEnergyProfileE2Type contains the References to MeasurementValueType Variables needed for EnergyProfile E2.

Table 26 – IEnergyProfileE2Type Definition

Attribute

Value

BrowseName

IEnergyProfileE2Type

IsAbstract

True

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseInterfaceType defined in [OPC 10001-7]

0:HasComponent

Variable

AcActivePowerTotal

0:Float

MeasurementValueType

M

0:HasComponent

Variable

AcActiveEnergyTotalImportLp

0:Float

MeasurementValueType

M

0:HasComponent

Variable

AcActiveEnergyTotalExportLp

0:Float

MeasurementValueType

M

Table 27 – IEnergyProfileE2Type Attribute values for child Nodes

Source Path

Value Attribute

AcActivePowerTotal

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5723220

DisplayName: W

Description: watt

AcActiveEnergyTotalImportLp

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5720146

DisplayName: W·h

Description: watt hour

AcActiveEnergyTotalExportLp

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5720146

DisplayName: W·h

Description: watt hour

The IEnergyProfileE3Type contains the References to MeasurementValueType Variables needed for EnergyProfile E3.

Table 28 – IEnergyProfileE3Type Definition

Attribute

Value

BrowseName

IEnergyProfileE3Type

IsAbstract

True

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseInterfaceType defined in [OPC 10001-7]

0:HasComponent

Variable

AcActivePower

AcPeDataType

MeasurementValueType

M

0:HasComponent

Variable

AcReactivePower

AcPeDataType

MeasurementValueType

M

0:HasComponent

Variable

AcActiveEnergyTotalImportHp

0:Double

MeasurementValueType

M

0:HasComponent

Variable

AcActiveEnergyTotalExportHp

0:Double

MeasurementValueType

M

0:HasComponent

Variable

AcReactiveEnergyTotalImportHp

0:Double

MeasurementValueType

M

0:HasComponent

Variable

AcReactiveEnergyTotalExportHp

0:Double

MeasurementValueType

M

0:HasComponent

Variable

AcVoltagePe

AcPeDataType

MeasurementValueType

M

0:HasComponent

Variable

AcVoltagePp

AcPpDataType

MeasurementValueType

M

0:HasComponent

Variable

AcCurrent

AcPeDataType

MeasurementValueType

M

0:HasComponent

Variable

AcPowerFactor

AcPeDataType

MeasurementValueType

M

Table 29 – IEnergyProfileE3Type Attribute values for child Nodes

Source Path

Value Attribute

AcActivePower

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5723220

DisplayName: W

Description: watt

AcReactivePower

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4469812

DisplayName: var

Description: var

AcActiveEnergyTotalImportHp

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5720146

DisplayName: W·h

Description: watt hour

AcActiveEnergyTotalExportHp

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5720146

DisplayName: W·h

Description: watt hour

AcVoltagePe

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5655636

DisplayName: V

Description: volt

AcVoltagePp

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 5655636

DisplayName: V

Description: volt

AcCurrent

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4279632

DisplayName: A

Description: ampere

The IEnergyProfileD0Type Interface contains a Reference to a MeasurementValueType Variable representing direct current (EnergyProfile D0).

Table 30 – IEnergyProfileD0Type Definition

Attribute

Value

BrowseName

IEnergyProfileD0Type

IsAbstract

True

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseInterfaceType defined in [OPC 10001-7]

0:HasComponent

Variable

DcCurrent

0:Float

MeasurementValueType

M

Table 31 – IEnergyProfileD0Type Attribute values for child Nodes

Source Path

Value Attribute

DcCurrent

0:EngineeringUnits

NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact

UnitId: 4279632

DisplayName: A

Description: ampere

The EnergyDevicePowerOffType type provides access to the Sleep Mode WOL functionality of the device if supported.

Table 32 – EnergyDevicePowerOffType Definition

Attribute

Value

BrowseName

EnergyDevicePowerOffType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType defined in [OPC 10000-5].

0:HasComponent

Variable

RegularTimeToOperate

0:Duration

0:BaseDataVariableType

M, RO

0:HasComponent

Variable

TimeMinPause

0:Duration

0:BaseDataVariableType

M, RO

0:HasComponent

Variable

ModePowerConsumption

0:UInt32

0:BaseDataVariableType

M, RO

0:HasProperty

Variable

WOLMagicPacket

0:ByteString

0:PropertyType

M, RO

0:HasComponent

Method

SwitchOffWOL

M

A RepresentedBy Reference may connect the Object to the representing PROFIenergy service access point Object (see PeServiceAccessPointType). The BrowseName of the Reference shall be “PESAP”. If the PESAP is not part of the Information Model, the RepresentedBy Reference in the EnergyDevicePowerOffType Object is omitted.

The RegularTimeToOperate Variable shall contain the time value to reach the state “Ready to operate” if the Wake-on-LAN sleep mode is terminated by a wake-up (see below).

The ModePowerConsumption Variable shall contain the power consumption in theWake-on-LAN sleep mode. Unit: [kW].

The WOLMagicPacket Variable shall contain the 6 bytes MAC address to be used with the magic packet sent for wake-up (see [PE CAP], chapter 7.3.4.9).

The SwitchOffWOL Method initiates the transition into the Wake-on-LAN sleep mode. In this mode the device is effectively switched off and unavailable for network communication. The device can be awakened using the magic packet (see [PE CAP], chapter 7.3.4.9).

This Method starts the transition into the special Wake-on-LAN mode.

Signature

SwitchOffWOL (

[out] 0:Byte ModeID

[out] 0:Duration CurrentTimeToDestination

[out] 0:Duration RegularTimeToOperate

[out] 0:Duration TimeMinLengthOfStay

[out] 0:Byte ReturnCode

);

Argument

Description

ModeID

ID of the “Sleep Mode WOL” (0xFE) if successful, otherwise 0.

CurrentTimeToDestination

Time needed to reach the Energy Saving Mode if successful, otherwise 0.

RegularTimeToOperate

Time needed to reach “Ready to operate” again if the Wake-on-LAN sleep mode will be regularly terminated if successful, otherwise 0.

TimeMinLengthOfStay

Time of minimum stay in the Wake-on-LAN sleep mode if successful, otherwise 0.

ReturnCode

Return code. See Table 16.

The Method Result Codes (defined in Call Service) are defined in Table 15.

The PeServiceAccessPointType connects the PE Energy Management Objects belonging to one PE Entity. The PeServiceAccessPointType Object could be included in the PE Energy Management model to model the PROFIenergy Service Access Point within PROFINET devices. Independent from the PeServiceAccessPointType Object, the PE Energy Management functionality can be directly managed by OPC UA access.

Table 33 – PeServiceAccessPointType Definition

Attribute

Value

BrowseName

PeServiceAccessPointType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType defined in [OPC 10000-5].

0:HasProperty

Variable

PeClass

PeClassEnumeration

0:PropertyType

O, RO

0:HasProperty

Variable

PeSubclass

PeSubclassEnumeration

0:PropertyType

O, RO

0:HasProperty

Variable

PeVersion

PeVersionDataType

0:PropertyType

M, RO

The BrowseName of a PeServiceAccessPointType instance should be “PESAP@<Subslot>, where <Subslot> shall be the content of the subslot Variable of the Object which is the source of the 0:HasAddin Reference pointing to the service access point Object in hexadecimal number string format.

The PeSubclass Property shall be provided in conjunction with the Class Property: If the Class Property has the value PE_CLASS1 or the value PE_CLASS3, this Property is mandatory.

The PeVersion Property shall contain the implemented PROFIenergy version number.

A Represents Reference with the BrowseName “Standby” is mandatory for PROFIenergy class 1 and class 3 and shall point to the EnergyStandbyManagementType Object representing the Standby Management functionality.

A Represents Reference with the BrowseName “Measurement” is mandatory for PROFIenergy class 2 and class 3 and shall point to the EnergyMeasurementType Object representing the Energy Measurement functionality.

One optional Represents Reference with the BrowseName “EnergyPowerOff” points to an EnergyDevicePowerOffType Object if “Sleep Mode WOL” is supported.