OPC-10000-15 – OPC Unified Architecture - Part 15: Safety6.3.3.3 SPI of SafetyProviderempty string) R/W Identifier describing the DataType of the SafetyData , see 7.2.3.5 . SafetyProviderDelay UInt32 0x0 to 0xFFFFFFFF 0x0 R/W In microseconds (µs). It can be set during the engineering phase ... SafetyProvider or set during online configuration as well. SafetyProviderDelay is the maximum time at the SafetyProvider from receiving the RequestSPDU to start the transmission of ResponseSPDU , see 8.1 . The parameter
-
OPC-10000-15 – OPC Unified Architecture - Part 15: SafetyFormula (2) . Selection of the watchdog parameter SafetyConsumerTimeout SafetyConsumerTimeout >= T_CD_RequestSPDU + SafetyProviderDelay + T_CD_ResponseSPDU + SafetyConsumerDelay (2) where T_CD_RequestSPDU: The worst-case communication delay ... ResponseSPDU can include the occurrence of dropped messages in the standard transmission system . SafetyProviderDelay: The worst-case SafetyProvider delay. Typically, one scan time period of the SafetyProvider . SafetyConsumerDelay: The worst