OPC-10000-15 – OPC Unified Architecture - Part 15: Safety3.1.2.1 fail-safefail-safe ability of a system that, by adequate technical or organizational measures, prevents from hazards either deterministically or by reducing the risk to a tolerable measure Note
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety3.3.1 General conventionsitems, technologies, systems, and units ( fail-safe , functional safe). The default data that are used in case of unit failures or errors, are called fail-safe substitute values
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety5.3 Safety measureswill cease to deliver actual process values to the safety application but will deliver fail-safe substitute values instead. In addition, an indication at the Safety Application Program Interface
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetystandard hardware and software. This principle delimits the assessment effort to the "safe transmission functions". The standard transmission system does not require any additional functional safety assessment ... SafetyBaseID (e.g. by configuration). If this expectation is not fulfilled by the SafetyProvider , fail-safe substitute values are delivered to the safety application instead of the received process values
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety6.2.3.2 OutFlagsTypeSafetyConsumer , see OperatorAckProvider in the SAPI of the SafetyProvider , 6.3.3.2 . ActivateFSV 1 Activation of fail-safe values by the safety application at the SafetyProvider , hereby forwarded to the SafetyConsumer
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety6.3.3.2 SAPI of SafetyProviderforwarded to the SafetyConsumer , where it can be used to trigger a return from fail-safe substitute values ( FSV ) to actual process values ( PV ), see B.3.4 . OperatorAckRequested Boolean O Indicates ... acknowledge is requested by the SafetyConsumer . This flag is received within the RequestSPDU . ActivateFSV ( Fail-safe substitute values) Boolean I By setting this input to "1" the SafetyConsumer
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety6.3.4.2 SAPI of SafetyConsumerSafetyProvider . When changing Enable to "1" the SafetyConsumer will restart safe communication. The variable can be used to delay the start of the safety communication according to this ... communication errors were detected in the past, so the SafetyConsumer decided to switch to fail-safe substitute values. 2) Currently, no communication errors occur, and hence operator acknowledgment is possible
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetyfaulty message, it checks whether the assumption is still valid, and switches to fail-safe substitute values otherwise. Returning to process values then requires an operator acknowledgment. Operator Acknowledge
-
OPC-10000-15 – OPC Unified Architecture - Part 15: SafetySafetyOperatorAckNecessary This parameter determines whether automatic restart (i.e. automatically switching back from fail-safe values to process values ) is possible for the safety function or not. It is expected
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetyincorrect ID. 0x01 A Yes SD_IDerrOA The SafetyConsumer has switched to fail-safe substitute values due to an incorrect ID. Operator acknowledgment is required. Mismatch of SafetyBaseID .2 0x11 ... IDerrOA The SafetyConsumer has switched to fail-safe substitute values due to an incorrect ID. Operator acknowledgment is required. Mismatch of SafetyProviderID . 0x12 B, E Yes SD_IDerrOA The SafetyConsumer
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.1.5 ResponseSPDU: SafetyDataSafetyData is fixed. SafetyData may contain qualifiers for a fine-grained activation of fail-safe substitute values. For valid process values , the respective qualifiers are set to 1 (good), whereas ... value 0 (bad) is used for invalid values. Invalid process values are replaced by fail-safe substitute values in the SafetyConsumer 's safety application
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.2.5 SafetyConsumer state diagramEndif SAPI.FSV_Activated:= 1 RequestSPDU.Flags.FSV_Activated:= 1 NOTE 1 If a safety application prefers fail-safe values other than binary 0, this can be implemented in the safety application
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetyhappened more than SafetyErrorIntervalLimit time units ago. Otherwise, it will make a transition to fail-safe values, which can only be left by manual operator acknowledgment, see 6.3.4.3 . This directly
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetycontroller A suffices for re-establishing the bidirectional connection. Both sides will cease delivering fail-safe values and continue sending process values . This is accomplished by connecting OperatorAckProvider with OperatorAckConsumer
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetycontroller B suffices for re-establishing the bidirectional connection. Both sides will cease delivering fail-safe values and continue sending process values . This is accomplished by the logic circuits shown