9 result(s) for BACnetAnalogType
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information Model7.4.2 ObjectType definitionObjectType definition The BACnetAnalogType is formally defined in Table 12 . Table 12 - BACnetAnalogType Definition Attribute Value BrowseName BACnetAnalogType IsAbstract True References NodeClass BrowseName DataType TypeDefinition Other Subtype of the BACnetObjectType ... HasComponent Object EventReporting BACnetEventReportingType O 0:HasComponent Object FaultEvaluation BACnetFaultEvaluationType O The BACnetAnalogType is an abstract type and cannot be used directly. The components of the BACnetAnalogType have additional subcomponents
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information ModelBACnet properties defined for all BACnet analog object types are mapped to the abstract BACnetAnalogType . The remaining property is mapped to the concrete OPC UA ObjectType BACnetAnalogInputType . Figure 6 shows
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information Model7.4.1 Generaltypes in an OPC UA Address Space . Figure 13 shows an overview for the BACnetAnalogType with its Properties and related ObjectTypes . It is formally defined in Table 12 . Figure ... BACnetAnalogType overview
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information Model7.4.3.3 Variable Status_Flagsrepresents four Boolean flags that represent the general health of a BACnetAnalogType . The flags are IN_ALARM, FAULT, OVERRIDDEN, and OUT_OF_SERVICE
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information Model7.4.3.6 Object EventReportingEventAlgorithm component is changed to TypeDefinition BACnetOutOfRangeAlgorithmType and ModellingRule Mandatory if used in the BACnetAnalogType or one of its subtypes. The BACnetOutOfRangeAlgorithmType is defined in 8.9.3 . On the EventAlgorithm instance
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information Model7.4.3.7 Object FaultEvaluationFaultEvaluation Object contains status and configuration information for the fault evaluation of the BACnetAnalogType . The BACnetFaultEvaluationType is defined in 8.23 . The Object is optional and is not present if fault
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information Model7.5.2 ObjectType definitionValue BrowseName BACnetAnalogInputType IsAbstract False References NodeClass BrowseName DataType TypeDefinition Other Subtype of the BACnetAnalogType 0:HasProperty Variable Device_Type 0:String 0:PropertyType O The BACnetAnalogInputType ObjectType
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information Model7.6.2 ObjectType definitionValue BrowseName BACnetAnalogOutputType IsAbstract False References NodeClass BrowseName DataType TypeDefinition Other Subtype of the BACnetAnalogType 0:HasProperty Variable Device_Type 0:String 0:PropertyType O 0:HasProperty Variable Priority_Array
-
OPC-30030 – OPC UA for BACnet - BACnet: OPC UA Information Model7.7.2 ObjectType definitionValue BrowseName BACnetAnalogValueType IsAbstract False References NodeClass BrowseName DataType TypeDefinition Other Subtype of the BACnetAnalogType 0:HasProperty Variable Priority_Array BACnetPriorityValue [16] 0:PropertyType O 0:HasProperty Variable Relinquish_Default