This ObjectType is a container for temperature zones inside of a component of an extrusion line. It is formally defined in Table 10.

Table 10 – ExtrusionTemperatureZonesType Definition

Attribute

Value

BrowseName

ExtrusionTemperatureZonesType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of 0:BaseObjectType defined in OPC 10000-5

0:HasProperty

Variable

0:NodeVersion

0:String

0:PropertyType

M, RO

0:HasComponent

Object

StartTempering

3:StartDeviceType

O

0:HasComponent

Object

Maintenance

3:MaintenanceType

O

0:HasComponent

Object

TemperatureZone_<Nr>

ExtrusionTemperature

ZoneType

OP

0:GeneratesEvent

ObjectType

0:GeneralModelChangeEventType

When instances for temperature zones are created, the BrowseNames shall be “TemperatureZone_<Nr>” where <Nr> is a three-digit number with leading zeros, starting with “001”. The ExtrusionTemperatureZoneType is defined in Table 11.

StartTempering: Main switch for all temperature zones in the container. The single zones have own switches/status AND-connection!

This ObjectType represents one temperature zone inside of a component of an extrusion line. It is formally defined in Table 11.

Table 11 – ExtrusionTemperatureZoneType Definition

Attribute

Value

BrowseName

ExtrusionTemperatureZoneType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of 3:MeasuringDeviceType defined in OPC 40083

0:HasComponent

Variable

NominalHeatingPower

0:Double

0:AnalogUnitType

O, RO

0:HasComponent

Variable

NominalCoolingPower

0:Double

0:AnalogUnitType

O, RO

0:HasComponent

Variable

ControllerOutput

0:Double

0:AnalogUnitType

O, RO

0:HasComponent

Object

ElectricalCurrent

3:MonitoredParameterType

O

NOTES: The temperature of the zone is stored inside the MonitoredParameter object of the MeasuringDeviceType. The TemperatureZoneType differs from the TemperatureZoneType defined in OPC 40083 to make use of the new MeasuringDeviceType.

Indication of the nominal heating power of the zone in kW. If the zone is only a cooling zone, this variable is not used.

Indication of the nominal cooling power of the zone in kW. If the zone is only a heating zone, this variable is not used.

Actual ratio of the used nominal power in %. Values from -100 (=max. cooling) to +100 (max. heating).

Actual electrical current of the zone in A.