The IAdministrationType provides the interface to administration variables and methods of the device and is formally defined in Table 16.
Table 16 – IAdministrationType definition
Attribute |
Value |
||||
BrowseName |
IAdministrationType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
DisplayLanguage |
0:LocaleId |
0:BaseDataVariableType |
O |
0:HasComponent |
Variable |
DateOfLastChange |
0:DateTime |
0:BaseDataVariableType |
O |
0:HasComponent |
Method |
FactoryReset |
Defined in 9.1 |
O |
|
Conformance Units |
|||||
PA-DIM IAdmin DisplayLanguage |
|||||
PA-DIM IAdmin DateOfChange |
|||||
PA-DIM IAdmin FactoryReset |
DisplayLanguage: is the language used for the local display of the device. ABN597#002 defines language or languages set on the display.
DateOfLastChange: ABN604#001 defines parameter indicating the date and time at which one of the device parameters was changed the last time.
FactoryReset: ABN609#001 property the value of which indicates the kind of reset function to be executed. Note: Properties can be variables or methods according IEC 61987 CDD.
The components of IAdministrationType have additional references which are defined in Table 17.
Table 17 – IAdministrationType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
DisplayLanguage |
0:HasDictionaryEntry |
True |
|
DateOfLastChange |
0:HasDictionaryEntry |
True |
|
FactoryReset |
0:HasDictionaryEntry |
True |
The child Nodes of the IAdministrationType have additional Attribute values defined in Table 18.
Table 18 – IAdministrationType Attribute values for child Nodes
BrowsePath |
Value Attribute |
DisplayLanguage |
en |
DateOfLastChange |
|
The ISignalSetType provides the interface to process variables of the device and is formally defined in Table 19.
Table 19 – ISignalSetType definition
Attribute |
Value |
||||
BrowseName |
ISignalSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Object |
SignalSet |
|
SignalSetType |
O |
Conformance Units |
|||||
PA-DIM ISignal |
SignalSet is a container object for the process variables of the device.
The ICalibrationType provides the interface to calibration variables of the sensor resp. signal and is formally defined in Table 20.
Table 20 – ICalibrationType definition
Attribute |
Value |
||||
BrowseName |
ICalibrationType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasProperty |
Variable |
CalibrationTimestamp |
0:DateTime |
0:PropertyType |
O |
0:HasComponent |
Variable |
TypeOfCalibration |
0:UInt32 |
0:MultiStateDictionaryEntryDiscreteType |
O |
0:HasComponent |
Object |
CalibrationPointSet |
|
CalibrationPointSetType |
O |
Conformance Units |
|||||
PA-DIM ICalibration |
|||||
PA-DIM ICalibration CalibrationTimestamp |
|||||
PA-DIM ICalibration TypeOfCalibration |
|||||
PA-DIM ICalibration CalibrationPointSet |
CalibrationTimestamp is defined by IRDI as ABP544#001 which states “point in time when a measurement channel of a device was calibrated”.
TypeOfCalibration is defined by IRDI as ABH609#001 which states “classification of a calibration according to its intended use”.
CalibrationPointSet is a container object for calibration points of the sensor resp. signal.
The components of ICalibrationType have additional references which are defined in Table 21.
Table 21 – ICalibrationType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
CalibrationTimestamp |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP544#001 |
TypeOfCalibration |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABH609#001 |
The child Nodes of the ICalibrationType have additional Attribute values defined in Table 22.
Table 22 – ICalibrationType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
CalibrationTimestamp |
|
||
TypeOfCalibration |
0 |
||
|
ns=3;s=0112/2///61987#ABP732#001 |
||
|
adjustment |
The IPhCalibrationType provides the interface to pH measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 23.
Table 23 – IPhCalibrationType definition
Attribute |
Value |
||||
BrowseName |
IPhCalibrationType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
SensorSlope |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SensorAsymmetryPotential |
0:Float |
0:AnalogUnitType |
O |
0:HasProperty |
Variable |
SensorT90 |
0:Float |
0:PropertyType |
O |
Conformance Units |
|||||
PA-DIM PhSignalType |
|||||
PA-DIM IPhCalibration SensorT90 |
SensorSlope is defined by IRDI as ABP567#001 which states “slope of a pH sensing element characteristic, expressed as the voltage change of the pH sensor per pH value, determined by the last calibration”.
SensorAsymmetryPotential is defined by IRDI as ABP568#001 which states “asymmetry potential of a pH sensing element characteristic determined by the last calibration”.
SensorT90is defined by IRDI as ABP569#001 which states “t90 settling time determined by the last calibration”.
The components of IPhCalibrationType have additional references which are defined in Table 24.
Table 24 – IPhCalibrationType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
SensorSlope |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP567#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorAsymmetryPotential |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP568#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorT90 |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP569#001 |
The child Nodes of the IPhCalibrationType have additional Attribute values defined in Table 25.
Table 25 – IPhCalibrationType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
SensorSlope |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 12890DisplayName: mVDescription: millivolt |
||
SensorAsymmetryPotential |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 12890DisplayName: mVDescription: millivolt |
||
SensorT90 |
0.0 |
The IConductivityCalibrationType provides the interface to conductivity measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 26.
Table 26 – IConductivityCalibrationType definition
Attribute |
Value |
||||
BrowseName |
IConductivityCalibrationType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
ConductivityCellConstant |
0:Float |
0:AnalogUnitType |
O |
Conformance Units |
|||||
PA-DIM PhSignalType |
ConductivityCellConstant is defined by IRDI as ABF161#001 which states “ratio of the distance between the electrodes to the electrode area”.
The components of IConductivityCalibrationType have additional references which are defined in Table 27.
Table 27 – IConductivityCalibrationType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
|||||
ConductivityCellConstant |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABF161#001 |
|||||
|
0:HasDictionaryEntry |
True |
The child Nodes of the IConductivityCalibrationType have additional Attribute values defined in Table 28.
Table 28 – IConductivityCalibrationType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
ConductivityCellConstant |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4536624DisplayName: cm⁻¹Description: reciprocal centimetre |
The IAmperometricCalibrationType provides the interface to amperometric measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 29.
Table 29 – IAmperometricCalibrationType definition
Attribute |
Value |
||||
BrowseName |
IAmperometricCalibrationType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
AmperometricSensorSlope |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
AmperometricSensorZeroPoint |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
AbsoluteAirPressure |
0:Float |
0:AnalogUnitType |
O |
0:HasProperty |
Variable |
SensorT90 |
0:Float |
0:PropertyType |
O |
Conformance Units |
|||||
PA-DIM AmperometricSignalType |
|||||
PA-DIM IAmperometricCalibration AbsoluteAirPressure |
|||||
PA-DIM IAmperometricCalibration SensorT90 |
AmperometricSensorSlope is defined by IRDI as ABP572#001 which states “slope of an amperometric sensing element characteristic determined by the last calibration”.
AmperometricSensorZeroPoint is defined by IRDI as ABP573#001 which states “zero point of an amperometric sensing element characteristic determined by the last calibration”.
AbsoluteAirPressure is defined by IRDI as ABP574#001 which states “absolute air pressure under which the last calibration was performed”.
SensorT90 is defined by IRDI as ABP569#001 which states “t90 settling time determined by the last calibration”.
The components of IAmperometricCalibrationType have additional references which are defined in Table 30.
Table 30 – IAmperometricCalibrationType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
AmperometricSensorSlope |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP572#001 |
||
|
0:HasDictionaryEntry |
True |
|||
AmperometricSensorZeroPoint |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP573#001 |
||
|
0:HasDictionaryEntry |
True |
|||
AbsoluteAirPressure |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP574#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorT90 |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP569#001 |
The child Nodes of the IAmperometricCalibrationType have additional Attribute values defined in Table 31.
Table 31 – IAmperometricCalibrationType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
AmperometricSensorZeroPoint |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4405040DisplayName: pADescription: picoampere |
||
AbsoluteAirPressure |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4274487DisplayName: hPaDescription: hectopascal |
||
SensorT90 |
0.0 |
The IOpticalFluorescenseQuenchingCalibrationType provides the interface to optical fluorescence quenching measurement specific calibration variables of the sensor resp. signal and is formally defined in Table 32.
Table 32 – IOpticalFluorescenseQuenchingCalibrationType definition
Attribute |
Value |
||||
BrowseName |
IOpticalFluorescenseQuenchingCalibrationType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
OpticalFluorescenseQuenchingSensorSlope |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
OpticalFluorescenseQuenchingSensorZeroPoint |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
AbsoluteAirPressure |
0:Float |
0:AnalogUnitType |
O |
0:HasProperty |
Variable |
SensorT90 |
0:Float |
0:PropertyType |
O |
Conformance Units |
|||||
PA-DIM OpticalFluorescenseQuenchingSignalType |
|||||
PA-DIM IOpticalFluorescenseQuenchingCalibration AbsoluteAirPressure |
|||||
PA-DIM IOpticalFluorescenseQuenchingCalibration SensorT90 |
OpticalFluorescenseQuenchingSensorSlope is defined by IRDI as ABP586#001 which states “slope of an optical fluorescence quenching sensing element characteristic determined by the last calibration”.
OpticalFluorescenseQuenchingSensorZeroPoint is defined by IRDI as ABP587#001 which states “zero point of an optical fluorescence quenching sensing element characteristic determined by the last calibration”.
AbsoluteAirPressure is defined by IRDI as ABP574#001 which states “absolute air pressure under which the last calibration was performed”.
SensorT90 is defined by IRDI as ABP569#001 which states “t90 settling time determined by the last calibration”.
The components of IOpticalFluorescenseQuenchingCalibrationType have additional references which are defined in Table 33.
Table 33 – IOpticalFluorescenseQuenchingCalibrationType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
OpticalFluorescenseQuenchingSensorSlope |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP586#001 |
||
|
0:HasDictionaryEntry |
True |
|||
OpticalFluorescenseQuenchingSensorZeroPoint |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP587#001 |
||
|
0:HasDictionaryEntry |
True |
|||
AbsoluteAirPressure |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP574#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorT90 |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP569#001 |
The child Nodes of the IOpticalFluorescenseQuenchingCalibrationType have additional Attribute values defined in Table 34.
Table 34 – IOpticalFluorescenseQuenchingCalibrationType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
OpticalFluorescenseQuenchingSensorZeroPoint |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4340024DisplayName: µsDescription: microsecond |
||
AbsoluteAirPressure |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4274487DisplayName: hPaDescription: hectopascal |
||
SensorT90 |
0.0 |
The IGeneralDeviceConditionSetType provides the interface to condition variables of the device and its components and is formally defined in Table 35.
Table 35 – IGeneralDeviceConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IGeneralDeviceConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Object |
GeneralDeviceConditions |
|
GeneralDeviceConditionSetType |
O |
0:HasComponent |
Object |
DeviceComponentConditions |
|
0:BaseObjectType |
O |
Conformance Units |
|||||
PA-DIM IGeneralDeviceConditionSet Interface |
|||||
PA-DIM IGeneralDeviceConditionSet DeviceComponentConditions |
GeneralDeviceConditions is a container object for general condition variables of the device.
DeviceComponentConditions is a container object for condition variables of the device components.
Table 36 – IGeneralDeviceConditionSetType additional subcomponents
BrowsePath |
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
DeviceComponentConditions |
0:HasComponent |
Object |
<DeviceComponentIdentifier> |
|
GeneralDeviceConditionSetType |
OP |
<DeviceComponentIdentifier> is an optional placeholder for an object containing the condition variables related to a specific device component.
The ITocDeviceConditionSetType provides the interface to TOC device specific condition variables and is formally defined in Table 37.
Table 37 – ITocDeviceConditionSetType definition
Attribute |
Value |
||||
BrowseName |
ITocDeviceConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
CarrierGasVolumeFlow |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
CarrierGasGaugePressure |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
ReactorTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SampleWaterVolumeFlow |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
ReferenceInjectionVolume |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
ActualInjectedVolume |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
CoolerTemperature |
0:Float |
0:AnalogUnitType |
O |
Conformance Units |
|||||
PA-DIM TocAnalyserType |
|||||
PA-DIM TocAnalyserType CarrierGasGaugePressure |
|||||
PA-DIM TocAnalyserType SampleWaterVolumeFlow |
|||||
PA-DIM TocAnalyserType ActualInjectedVolume |
CarrierGasVolumeFlow is defined by IRDI as ABP558#001 which states “volume flow of the auxiliary (compressed air) gas supply”.
CarrierGasGaugePressure is defined by IRDI as ABP559#001 which states “overpressure of the auxiliary (compressed air) gas supply in the system due to flow resistance within the complete analytical system”.
ReactorTemperature is defined by IRDI as ABP554#001 which states “measured temperature of a high temperature combustion system”.
SampleWaterVolumeFlow is defined by IRDI as ABP561#001 which states “volume flow of a liquid sample inside the device”.
ReferenceInjectionVolume is defined by IRDI as ABP563#001 which states “volume of liquid that should be injected by the injection system”.
ActualInjectedVolume is defined by IRDI as ABP564#001 which states “volume of liquid that has been injected by the injection system”.
CoolerTemperature is defined by IRDI as ABP555#001 which states “measured temperature of the gas cooler”.
The components of ITocDeviceConditionSetType have additional references which are defined in Table 38.
Table 38 – ITocDeviceConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
CarrierGasVolumeFlow |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP558#001 |
||
|
0:HasDictionaryEntry |
True |
|||
CarrierGasGaugePressure |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP559#001 |
||
|
0:HasDictionaryEntry |
True |
|||
ReactorTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP554#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SampleWaterVolumeFlow |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP561#001 |
||
|
0:HasDictionaryEntry |
True |
|||
ReferenceInjectionVolume |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP563#001 |
||
|
0:HasDictionaryEntry |
True |
|||
ActualInjectedVolume |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP564#001 |
||
|
0:HasDictionaryEntry |
True |
|||
CoolerTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP555#001 |
||
|
0:HasDictionaryEntry |
True |
The child Nodes of the ITocDeviceConditionSetType have additional Attribute values defined in Table 39.
Table 39 – ITocDeviceConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
CarrierGasVolumeFlow |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4535090DisplayName: l/hDescription: litre per hour |
||
CarrierGasGaugePressure |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5063250DisplayName: mbarDescription: millibar |
||
ReactorTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
SampleWaterVolumeFlow |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 13361DisplayName: ml/minDescription: millilitre per minute |
||
ReferenceInjectionVolume |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5065812DisplayName: mlDescription: millilitre |
||
ActualInjectedVolume |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5065812DisplayName: mlDescription: millilitre |
||
CoolerTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
The IFlameIonisationDeviceConditionSetType provides the interface to FID specific condition variables and is formally defined in Table 40.
Table 40 – IFlameIonisationDeviceConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IFlameIonisationDeviceConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
CatalystTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
FuelGasPressure |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
CombustionAirPressure |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
BlockTemperature |
0:Float |
0:AnalogUnitType |
O |
Conformance Units |
|||||
PA-DIM FlameIonisationDetectorType CatalystTemperature |
|||||
PA-DIM FlameIonisationDetectorType FuelGasPressure |
|||||
PA-DIM FlameIonisationDetectorType CombustionAirPressure |
|||||
PA-DIM FlameIonisationDetectorType BlockTemperature |
CatalystTemperature is defined by IRDI as ABP576#001 which states “measured temperature of a catalyst”.
FuelGasPressure is defined by IRDI as ABP578#001 which states “measured absolute pressure of the fuel gas”.
CombustionAirPressure is defined by IRDI as ABP579#001 which states “measured absolute pressure of the combustion air”.
BlockTemperature is defined by IRDI as ABP577#001 which states “measured temperature of a flame ionisation detector block”.
The components of IFlameIonisationDeviceConditionSetType have additional references which are defined in Table 41.
Table 41 – IFlameIonisationDeviceConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
CatalystTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP576#001 |
||
|
0:HasDictionaryEntry |
True |
|||
FuelGasPressure |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP578#001 |
||
|
0:HasDictionaryEntry |
True |
|||
CombustionAirPressure |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP579#001 |
||
|
0:HasDictionaryEntry |
True |
|||
BlockTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP577#001 |
||
|
0:HasDictionaryEntry |
True |
The child Nodes of the IFlameIonisationDeviceConditionSetType have additional Attribute values defined in Table 42.
Table 42 – IFlameIonisationDeviceConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
CatalystTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
FuelGasPressure |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5063250DisplayName: mbarDescription: millibar |
||
CombustionAirPressure |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5063250DisplayName: mbarDescription: millibar |
||
BlockTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
The INonDispersiveInfraredSignalConditionSetType provides the interface to NDIR measurement signal specific condition variables and is formally defined in Table 43.
Table 43 – INonDispersiveInfraredSignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
INonDispersiveInfraredSignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
ChopperFrequencyDeviation |
0:Float |
0:BaseAnalogType |
O |
0:HasComponent |
Variable |
AbsoluteSampleGasPressure |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SampleCellTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasProperty |
Variable |
SourceResidualLife |
0:Float |
0:PropertyType |
O |
Conformance Units |
|||||
PA-DIM NonDispersiveInfraredSignalType ChopperFrequencyDeviation |
|||||
PA-DIM NonDispersiveInfraredSignalType |
|||||
PA-DIM NonDispersiveInfraredSignalType AbsoluteSampleGasPressure |
ChopperFrequencyDeviation is defined by IRDI as ABP553#001 which states “relative change in the chopper frequency of a detector during a measurement”.
AbsoluteSampleGasPressure is defined by IRDI as ABP560#001 which states “absolute pressure of sample gas inside a detection system”.
SampleCellTemperature is defined by IRDI as ABP556#001 which states “measured temperature of the sample cell”.
SourceResidualLife is defined by IRDI as ABP552#001 which states “degradation of a radiation source expressed as a value between 1 (good) and 0 (bad)”.
The components of INonDispersiveInfraredSignalConditionSetType have additional references which are defined in Table 44.
Table 44 – INonDispersiveInfraredSignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
ChopperFrequencyDeviation |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP553#001 |
||
|
0:HasDictionaryEntry |
True |
|||
AbsoluteSampleGasPressure |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP560#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SampleCellTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP556#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SourceResidualLife |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP552#001 |
The child Nodes of the INonDispersiveInfraredSignalConditionSetType have additional Attribute values defined in Table 45.
Table 45 – INonDispersiveInfraredSignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
ChopperFrequencyDeviation |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 20529DisplayName: % or pctDescription: percent |
||
AbsoluteSampleGasPressure |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5063250DisplayName: mbarDescription: millibar |
||
SampleCellTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
SourceResidualLife |
1.0 |
The ITocSignalConditionSetType provides the interface to TOC measurement signal specific condition variables and is formally defined in Table 46.
Table 46 – ITocSignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
ITocSignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
ChopperFrequencyDeviation |
0:Float |
0:BaseAnalogType |
O |
0:HasComponent |
Variable |
RelativeReagentLevel |
0:Float{Any} |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SampleCellTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
DetectorZeroSignal |
0:Float |
0:AnalogUnitType |
O |
0:HasProperty |
Variable |
SourceResidualLife |
0:Float |
0:PropertyType |
O |
0:HasComponent |
Variable |
AbsoluteSampleGasPressure |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SampleGasVolumeFlow |
0:Float |
0:AnalogUnitType |
O |
Conformance Units |
|||||
PA-DIM TocSignalType |
|||||
PA-DIM TocSignalType ChopperFrequencyDeviation |
|||||
PA-DIM TocSignalType RelativeReagentLevel |
|||||
PA-DIM TocSignalType AbsoluteSampleGasPressure |
|||||
PA-DIM TocSignalType SampleGasVolumeFlow |
ChopperFrequencyDeviation is defined by IRDI as ABP553#001 which states “relative change in the chopper frequency of a detector during a measurement”.
RelativeReagentLevel is defined by IRDI as ABP557#001 which states “relative filling level of auxiliary reagent”.
SampleCellTemperature is defined by IRDI as ABP556#001 which states “measured temperature of the sample cell”.
DetectorZeroSignal is defined by IRDI as ABP551#001 which states “reading of the detector before injection of the sample”.
SourceResidualLife is defined by IRDI as ABP552#001 which states “degradation of a radiation source expressed as a value between 1 (good) and 0 (bad)”.
AbsoluteSampleGasPressure is defined by IRDI as ABP560#001 which states “absolute pressure of sample gas inside a detection system”.
SampleGasVolumeFlow is defined by IRDI as ABP562#001 which states “volume flow of a sample gas through a detection system”.
The components of ITocSignalConditionSetType have additional references which are defined in Table 47.
Table 47 – ITocSignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
ChopperFrequencyDeviation |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP553#001 |
||
|
0:HasDictionaryEntry |
True |
|||
RelativeReagentLevel |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP557#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SampleCellTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP556#001 |
||
|
0:HasDictionaryEntry |
True |
|||
DetectorZeroSignal |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP551#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SourceResidualLife |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP552#001 |
||
AbsoluteSampleGasPressure |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP560#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SampleGasVolumeFlow |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP562#001 |
||
|
0:HasDictionaryEntry |
True |
The child Nodes of the ITocSignalConditionSetType have additional Attribute values defined in Table 48.
Table 48 – ITocSignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
ChopperFrequencyDeviation |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 20529DisplayName: % or pctDescription: percent |
||
RelativeReagentLevel |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 20529DisplayName: % or pctDescription: percent |
||
SampleCellTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
DetectorZeroSignal |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 13625DisplayName: ppmDescription: part per million |
||
SourceResidualLife |
1.0 |
||
AbsoluteSampleGasPressure |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5063250DisplayName: mbarDescription: millibar |
||
SampleGasVolumeFlow |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4535090DisplayName: l/hDescription: litre per hour |
The IParamagneticSignalConditionSetType provides the interface to paramagnetic measurement signal specific condition variables and is formally defined in Table 49.
Table 49 – IParamagneticSignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IParamagneticSignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
SampleTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SensingElementTemperature |
0:Float |
0:AnalogUnitType |
O |
Conformance Units |
|||||
PA-DIM ParamagneticSignalType |
SampleTemperature is defined by IRDI as ABP575#001 which states “temperature of the sample at the point of measurement”.
SensingElementTemperature is defined by IRDI as ABP565#001 which states “temperature measured at a sensing element”.
The components of IParamagneticSignalConditionSetType have additional references which are defined in Table 50.
Table 50 – IParamagneticSignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
SampleTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP575#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensingElementTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP565#001 |
||
|
0:HasDictionaryEntry |
True |
The child Nodes of the IParamagneticSignalConditionSetType have additional Attribute values defined in Table 51.
Table 51 – IParamagneticSignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
SampleTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
SensingElementTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
The IThermalConductivitySignalConditionSetType provides the interface to thermal conductivity measurement signal specific condition variables and is formally defined in Table 52.
Table 52 – IThermalConductivitySignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IThermalConductivitySignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
SampleTemperature |
0:Float |
0:AnalogUnitType |
O |
Conformance Units |
|||||
PA-DIM ThermalConductivitySignalType |
SampleTemperature is defined by IRDI as ABP575#001 which states “temperature of the sample at the point of measurement”.
The components of IThermalConductivitySignalConditionSetType have additional references which are defined in Table 53.
Table 53 – IThermalConductivitySignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
SampleTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP575#001 |
||
|
0:HasDictionaryEntry |
True |
The child Nodes of the IThermalConductivitySignalConditionSetType have additional Attribute values defined in Table 54.
Table 54 – IThermalConductivitySignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
SampleTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
The ITunableDiodeLaserSignalConditionSetType provides the interface to TDL measurement signal specific condition variables and is formally defined in Table 55.
Table 55 – ITunableDiodeLaserSignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
ITunableDiodeLaserSignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
AbsoluteSampleGasPressure |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SampleTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
TransmissionRatio |
0:Float |
0:DataItemType |
O |
0:HasComponent |
Variable |
SignalNoiseRatio |
0:Float |
0:DataItemType |
O |
0:HasComponent |
Variable |
LaserTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SignalFitQuality |
0:Float |
0:DataItemType |
O |
Conformance Units |
|||||
PA-DIM TunableDiodeLaserSignalType |
|||||
PA-DIM TunableDiodeLaserSignalType SignalFitQuality |
|||||
PA-DIM TunableDiodeLaserSignalType SignalNoiseRatio |
|||||
PA-DIM TunableDiodeLaserSignalType TransmissionRatio |
|||||
PA-DIM TunableDiodeLaserSignalType LaserTemperature |
|||||
PA-DIM TunableDiodeLaserSignalType AbsoluteSampleGasPressure |
AbsoluteSampleGasPressure is defined by IRDI as ABP560#001 which states “absolute pressure of sample gas inside a detection system”.
SampleTemperature is defined by IRDI as ABP575#001 which states “temperature of the sample at the point of measurement”.
TransmissionRatio is defined by IRDI as ABP582#001 which states “ratio of the value of a specified radiation quantity in the centre of a beam of specified radiation quality and under specified geometrical conditions after passage through a material to the value which would be present at the same position without this material in the beam”.
SignalNoiseRatio is defined by IRDI as ABP581#001 which states “linear ratio of the signal level to the noise level as measured under specified conditions”.
LaserTemperature is defined by IRDI as ABP583#001 which states “measured temperature of the element that defines the wavelength of a laser”.
SignalFitQuality is defined by IRDI as ABP580#001 which states “degree of correlation between the calculated and the measured absorption signal”.
The components of ITunableDiodeLaserSignalConditionSetType have additional references which are defined in Table 56.
Table 56 – ITunableDiodeLaserSignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
AbsoluteSampleGasPressure |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP560#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SampleTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP575#001 |
||
|
0:HasDictionaryEntry |
True |
|||
TransmissionRatio |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP582#001 |
||
SignalNoiseRatio |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP581#001 |
||
LaserTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP583#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SignalFitQuality |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP580#001 |
The child Nodes of the ITunableDiodeLaserSignalConditionSetType have additional Attribute values defined in Table 57.
Table 57 – ITunableDiodeLaserSignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
AbsoluteSampleGasPressure |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5063250DisplayName: mbarDescription: millibar |
||
SampleTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
TransmissionRatio |
0.0 |
||
SignalNoiseRatio |
0.0 |
||
LaserTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
SignalFitQuality |
0.0 |
The IZirconiumDioxideSignalConditionSetType provides the interface to Zirconium dioxide measurement signal specific condition variables and is formally defined in Table 58.
Table 58 – IZirconiumDioxideSignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IZirconiumDioxideSignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
RelativeHeatOutput |
0:Float |
0:DataItemType |
O |
0:HasComponent |
Variable |
SensingElementTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SampleGasVolumeFlow |
0:Float |
0:AnalogUnitType |
O |
Conformance Units |
|||||
PA-DIM ZirconiumDioxideSignalType |
|||||
PA-DIM ZirconiumDioxideSignalType RelativeHeatOutput |
|||||
PA-DIM ZirconiumDioxideSignalType SampleGasVolumeFlow |
RelativeHeatOutput is defined by IRDI as ABP585#001 which states “relative heat output refered to the maximum heat output to keep the sensor at its setpoint temperature during operation”.
SensingElementTemperature is defined by IRDI as ABP565#001 which states “temperature measured at a sensing element”.
SampleGasVolumeFlow is defined by IRDI as ABP562#001 which states “volume flow of a sample gas through a detection system”.
The components of IZirconiumDioxideSignalConditionSetType have additional references which are defined in Table 59.
Table 59 – IZirconiumDioxideSignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
RelativeHeatOutput |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP585#001 |
||
SensingElementTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP565#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SampleGasVolumeFlow |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP562#001 |
||
|
0:HasDictionaryEntry |
True |
The child Nodes of the IZirconiumDioxideSignalConditionSetType have additional Attribute values defined in Table 60.
Table 60 – IZirconiumDioxideSignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
RelativeHeatOutput |
0.0 |
||
SensingElementTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
SampleGasVolumeFlow |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4535090DisplayName: l/hDescription: litre per hour |
The IPhSignalConditionSetType provides the interface to pH measurement signal specific condition variables and is formally defined in Table 61.
Table 61 – IPhSignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IPhSignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
PhMeasuringMethod |
0:UInt32 |
0:MultiStateDictionaryEntryDiscreteType |
O |
0:HasComponent |
Variable |
SensingElementTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SensorNextCalibration |
0:UInt32 |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SensingElementImpedance |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SensorReferenceImpedance |
0:Float |
0:AnalogUnitType |
O |
0:HasProperty |
Variable |
SensorCleaningsCounter |
0:UInt32 |
0:PropertyType |
O |
0:HasProperty |
Variable |
SensorSterilisationsCounter |
0:UInt32 |
0:PropertyType |
O |
Conformance Units |
|||||
PA-DIM PhSignalType |
|||||
PA-DIM PhSignalType SensorNextCalibration |
|||||
PA-DIM PhSignalType SensingElementImpedance |
|||||
PA-DIM PhSignalType SensorReferenceImpedance |
|||||
PA-DIM PhSignalType SensorCleaningsCounter |
|||||
PA-DIM PhSignalType SensorSterilisationsCounter |
PhMeasuringMethod is defined by IRDI as ABP640#001 which states “physical measuring method of a pH sensor”.
SensingElementTemperature is defined by IRDI as ABP565#001 which states “temperature measured at a sensing element”.
SensorNextCalibration is defined by IRDI as ABP566#001 which states “time that can elapse until the next calibration, calculated from the configured calibration interval or estimated by the device”.
SensingElementImpedance is defined by IRDI as ABP570#001 which states “absolute value of impedance for a pH sensing element, compensated for a temperature of 25°C”.
SensorReferenceImpedance is defined by IRDI as ABP571#001 which states “absolute value of impedance for a pH reference system, compensated for a temperature of 25°C”.
SensorCleaningsCounter is defined by IRDI as ABP546#001 which states “number of times a sensor has been cleaned in place”.
SensorSterilisationsCounter is defined by IRDI as ABP547#001 which states “number of times a sensor has been sterilized in place”.
The components of IPhSignalConditionSetType have additional references which are defined in Table 62.
Table 62 – IPhSignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
PhMeasuringMethod |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP640#001 |
||
SensingElementTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP565#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorNextCalibration |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP566#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensingElementImpedance |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP570#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorReferenceImpedance |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP571#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorCleaningsCounter |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP546#001 |
||
SensorSterilisationsCounter |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP547#001 |
The child Nodes of the IPhSignalConditionSetType have additional Attribute values defined in Table 63.
Table 63 – IPhSignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
PhMeasuringMethod |
0 |
||
|
ns=3;s=0112/2///61987#ABP718#001 |
||
|
glass electrode |
||
SensingElementTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
SensorNextCalibration |
0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4473177DisplayName: dDescription: day |
||
SensingElementImpedance |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5195853DisplayName: ΩDescription: ohm |
||
SensorReferenceImpedance |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5195853DisplayName: ΩDescription: ohm |
||
SensorCleaningsCounter |
0 |
||
SensorSterilisationsCounter |
0 |
The IConductivitySignalConditionSetType provides the interface to conductivity measurement signal specific condition variables and is formally defined in Table 64.
Table 64 – IConductivitySignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IConductivitySignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
ConductivityMeasuringMethod |
0:UInt32 |
0:MultiStateDictionaryEntryDiscreteType |
O |
0:HasComponent |
Variable |
SensingElementTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
TemperatureCompensationStyle |
0:UInt32 |
0:MultiStateDictionaryEntryDiscreteType |
O |
0:HasProperty |
Variable |
SensorCleaningsCounter |
0:UInt32 |
0:PropertyType |
O |
0:HasProperty |
Variable |
SensorSterilisationsCounter |
0:UInt32 |
0:PropertyType |
O |
Conformance Units |
|||||
PA-DIM PhSignalType |
|||||
PA-DIM ConductivitySignalType SensorCleaningsCounter |
|||||
PA-DIM ConductivitySignalType SensorSterilisationsCounter |
ConductivityMeasuringMethod is defined by IRDI as ABP641#001 which states “physical measuring method of a conductivity sensor”.
SensingElementTemperature is defined by IRDI as ABP565#001 which states “temperature measured at a sensing element”.
TemperatureCompensationStyle is defined by IRDI as ABP642#001 which states “method of temperature compensation that is offered by the device”.
SensorCleaningsCounter is defined by IRDI as ABP546#001 which states “number of times a sensor has been cleaned in place”.
SensorSterilisationsCounter is defined by IRDI as ABP547#001 which states “number of times a sensor has been sterilized in place”.
The components of IConductivitySignalConditionSetType have additional references which are defined in Table 65.
Table 65 – IConductivitySignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
ConductivityMeasuringMethod |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP641#001 |
||
SensingElementTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP565#001 |
||
|
0:HasDictionaryEntry |
True |
|||
TemperatureCompensationStyle |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP642#001 |
||
SensorCleaningsCounter |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP546#001 |
||
SensorSterilisationsCounter |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP547#001 |
The child Nodes of the IConductivitySignalConditionSetType have additional Attribute values defined in Table 66.
Table 66 – IConductivitySignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
ConductivityMeasuringMethod |
0 |
||
|
ns=3;s=0112/2///61987#ABP721#001 |
||
|
inductive |
||
SensingElementTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
TemperatureCompensationStyle |
0 |
||
|
ns=3;s=0112/2///61987#ABP724#001 |
||
|
no temperature compensation |
||
SensorCleaningsCounter |
0 |
||
SensorSterilisationsCounter |
0 |
The IAmperometricSignalConditionSetType provides the interface to amperometric measurement signal specific condition variables and is formally defined in Table 67.
Table 67 – IAmperometricSignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IAmperometricSignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
SensingElementTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SensorNextCalibration |
0:UInt32 |
0:AnalogUnitType |
O |
0:HasProperty |
Variable |
SensorCleaningsCounter |
0:UInt32 |
0:PropertyType |
O |
0:HasProperty |
Variable |
SensorSterilisationsCounter |
0:UInt32 |
0:PropertyType |
O |
Conformance Units |
|||||
PA-DIM AmperometricSignalType |
|||||
PA-DIM AmperometricSignalType SensorNextCalibration |
|||||
PA-DIM AmperometricSignalType SensorCleaningsCounter |
|||||
PA-DIM AmperometricSignalType SensorSterilisationsCounter |
SensingElementTemperature is defined by IRDI as ABP565#001 which states “temperature measured at a sensing element”.
SensorNextCalibration is defined by IRDI as ABP566#001 which states “time that can elapse until the next calibration, calculated from the configured calibration interval or estimated by the device”.
SensorCleaningsCounter is defined by IRDI as ABP546#001 which states “number of times a sensor has been cleaned in place”.
SensorSterilisationsCounter is defined by IRDI as ABP547#001 which states “number of times a sensor has been sterilized in place”.
The components of IAmperometricSignalConditionSetType have additional references which are defined in Table 68.
Table 68 – IAmperometricSignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
SensingElementTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP565#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorNextCalibration |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP566#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorCleaningsCounter |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP546#001 |
||
SensorSterilisationsCounter |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP547#001 |
The child Nodes of the IAmperometricSignalConditionSetType have additional Attribute values defined in Table 69.
Table 69 – IAmperometricSignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
SensingElementTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
SensorNextCalibration |
0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4473177DisplayName: dDescription: day |
||
SensorCleaningsCounter |
0 |
||
SensorSterilisationsCounter |
0 |
The IOpticalFluorescenseQuenchingSignalConditionSetType provides the interface to optical fluorescence quenching measurement signal specific condition variables and is formally defined in Table 70.
Table 70 – IOpticalFluorescenseQuenchingSignalConditionSetType definition
Attribute |
Value |
||||
BrowseName |
IOpticalFluorescenseQuenchingSignalConditionSetType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Variable |
SensingElementTemperature |
0:Float |
0:AnalogUnitType |
O |
0:HasComponent |
Variable |
SensorNextCalibration |
0:UInt32 |
0:AnalogUnitType |
O |
0:HasProperty |
Variable |
SensorCleaningsCounter |
0:UInt32 |
0:PropertyType |
O |
0:HasProperty |
Variable |
SensorSterilisationsCounter |
0:UInt32 |
0:PropertyType |
O |
Conformance Units |
|||||
PA-DIM OpticalFluorescenseQuenchingSignalType |
|||||
PA-DIM OpticalFluorescenseQuenchingSignalType SensorNextCalibration |
|||||
PA-DIM OpticalFluorescenseQuenchingSignalType SensorCleaningsCounter |
|||||
PA-DIM OpticalFluorescenseQuenchingSignalType SensorSterilisationsCounter |
SensingElementTemperature is defined by IRDI as ABP565#001 which states “temperature measured at a sensing element”.
SensorNextCalibration is defined by IRDI as ABP566#001 which states “time that can elapse until the next calibration, calculated from the configured calibration interval or estimated by the device”.
SensorCleaningsCounter is defined by IRDI as ABP546#001 which states “number of times a sensor has been cleaned in place”.
SensorSterilisationsCounter is defined by IRDI as ABP547#001 which states “number of times a sensor has been sterilized in place”.
The components of IOpticalFluorescenseQuenchingSignalConditionSetType have additional references which are defined in Table 71.
Table 71 – IOpticalFluorescenseQuenchingSignalConditionSetType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
SensingElementTemperature |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP565#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorNextCalibration |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP566#001 |
||
|
0:HasDictionaryEntry |
True |
|||
SensorCleaningsCounter |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP546#001 |
||
SensorSterilisationsCounter |
0:HasDictionaryEntry |
True |
3:0112/2///61987#ABP547#001 |
The child Nodes of the IOpticalFluorescenseQuenchingSignalConditionSetType have additional Attribute values defined in Table 72.
Table 72 – IOpticalFluorescenseQuenchingSignalConditionSetType Attribute values for child Nodes
BrowsePath |
Value Attribute |
||
SensingElementTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
||
SensorNextCalibration |
0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4473177DisplayName: dDescription: day |
||
SensorCleaningsCounter |
0 |
||
SensorSterilisationsCounter |
0 |