8 OPC UA ObjectTypes ToC Previous Next

8.2 Energy Measurement ToC Previous Next

8.2.2 EnergyMeasurementType ToC Previous Next

The EnergyMeasurementType contains References to MeasurementValueType Objects.

Table 20 – EnergyMeasurementType Definition

Attribute Value        
BrowseName EnergyMeasurementType        
IsAbstract False        
References Node Class BrowseName DataType TypeDefinition Other
Subtype of the BaseObjectType          
0:HasProperty Variable PeObjectNumber 0:UInt16 0:PropertyType M, RO
0:HasComponent Variable <MeasurementValue> 0:Number MeasurementValueType MP, RO
0:HasComponent Method ResetEnergyCounter   O  

The PeObjectNumber Variable shall contain the Object number of the related PROFIenergy measurement Object.

The MeasurementValue Variable contains one actual measurement value. For each measurement value of a Metering Point one MeasurementValueType Variable shall exist.

If one of the MeasurementValueType Variables is used as energy counter, the ResetEnergyCounter Method can be used to set the value of this Variable to 0. See section 9.1, ”MeasurementValueType” for further details.

A RepresentedBy Reference may connect the Object to the representing PROFIenergy service access point Object (see PeServiceAccessPointType). The BrowseName of the Reference shall be “PESAP”. If the PESAP is not part of the Information Model, the RepresentedBy Reference in the EnergyMeasurementType Object is omitted.

Mapping to PROFIenergy properties:

BrowseName PE Service PE Service Data Response Field
PeObjectNumber Get_Measurement_List_with_Object_Number Object_Number