7 OPC UA ObjectTypes ToC Previous Next

7.5 IOLinkMasterType ObjectType Definition ToC Previous Next

7.5.4 Methods of MethodSet ToC Previous Next

In Table 30, the Methods of the ObjectType, referenced via the MethodSet Object are defined.

Table 30 – MethodSet of IOLinkMasterType

References Node Class BrowseName Modelling Rule
The following Methods are also referenced by the Management Object      
HasComponent Method Restart Mandatory
       
The following Methods are also referenced by the Statistics Object      
HasComponent Method ResetStatisticsOnAllPorts Optional

7.5.4.1 Restart ToC

The Method Restart restarts the IO-Link Master.

Signature

Restart (
[in]	Duration		Delay,
[out]	Int32			Status
);

Argument Description
Delay Time before the restart becomes effective.
Status Returns the status of the operation.
   0: OK, operation successful
-1: Operation already running
-2: Operation cannot be executed
-3: Operation cannot be executed because master reconfiguration is disabled.

7.5.4.2 ResetStatisticsOnAllPorts ToC

The optional Method ResetStatisticsOnAllPorts resets all statistic data, including statistic data of the ports of the IO-Link Master. Statistic data of a port are all Parameters referenced by the Statistics Object of the IOLinkPortType Object starting with “NumberOf” and potentially vendor-specific extensions. Statistic data directly on the IO-Link Master includes the Variable NumberOfIOLinkMasterStarts and potential vendor-specific extensions. As soon as statistic data is provided by the server, the optional Method shall be provided.

Signature

ResetStatisticsOnAllPorts (
[out]	Int32			Status
);

Argument Description
Delay Time before the reset becomes effective.
Status Returns the status of the operation.
   0: OK, operation successful
-1: Operation already running
-2: Operation cannot be executed.

Previous Next