OPC-10000-15 – OPC Unified Architecture - Part 15: Safety6.3.4.4 SPI of the SafetyConsumerSPDU_ID . For these types of errors, OA is mandatory, see 6.3.4.3 . SafetyErrorIntervalLimit UInt16 6, 60, 600 600 R/W Value in minutes. The parameter SafetyErrorIntervalLimit determines the minimal time interval
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safety7.2.2.5 SafetyConsumer state diagramparameter SafetyStructureSignature SPI_SafetyOperatorAckNecessary_i Boolean Local variable to store the parameter SafetyOperatorAckNecessary SPI_SafetyErrorIntervalLimit_i UInt16 Local variable to store the parameter SafetyErrorIntervalLimit MNR_re_sync_i Boolean Local ... errors. If the elapsed time between two consecutive errors is smaller than the value SafetyErrorIntervalLimit , FSV will be activated. Otherwise, the ResponseSPDU is discarded and the SafetyConsumer waits
-
OPC-10000-15 – OPC Unified Architecture - Part 15: Safetylogical safety communication link according to this document depends on the parameter of SafetyErrorIntervalLimit (see Table 26 ) of the link's SafetyConsumer . Whenever the SafetyConsumer detects a mismatch ... only continue operating if the last occurrence of such an error happened more than SafetyErrorIntervalLimit time units ago. Otherwise, it will make a transition to fail-safe values, which