OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information Modelfrom more than one ControlGroup . Multiple ControlGroups might exist with different combinations. ListToRestrict and ListToBlock each have their own instances of LockingServices . When a ControlGroup is assigned to a user ... application, the Variables or Methods in ListToBlock or ListToRestrict are associated with that user or application (that user or application becomes the lock owner). The LockingServices exposed in ListToBlock
-
OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information Model6.5.3 EstablishControl methodmethod This Method shall acquire Locks required by the ControlGroup in the ListToRestrict and ListToBlock . If acquiring any Lock fails, all Locks shall be released, and the appropriate LockStatus shall
-
OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information Model6.5.5 ReassignControl methodmethod This Method shall reassign Locks required by the ControlGroup in the ListToRestrict and ListToBlock . It shall reassign the SourceNode of the Controls Reference
-
OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information ModelConfigurationData, and all provided Methods belonging to the interface can be easily determined. The ListToBlock prevents the setting of specific data, for example, SpeedSetpointNormalized, when controlling the AGV with