2 result(s) for ExpectedPublishedDataSetVersion
-
OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information Model6.2.4.3.9.2 PubSubverify the PublishedDataSet associated with the referenced DataSetWriter for each element in ConnectionEndpointConfigurations . If ExpectedPublishedDataSetVersion MajorVersion is 0, no verification shall be performed. If ExpectedPublishedDataSetVersion MinorVersion is 0, the verification ... MinorVersion shall be skipped. If the ExpectedPublishedDataSetVersion does not match the version of the associated PublishedDataSet , the appropriate element in ConnectionEndpointConfigurationResults CommunicationLinksResult shall be set to Bad_ConfigurationError
-
OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information ModelE.4.7 PubSub DataSetsverification of metadata and DataSet can be minimized if the ConnectionEndpointParameter contains ExpectedPublishedDataSetVersion and/or ExpectedSubscribedDataSetVersion. These Variables can be used to confirm that the current configuration matches what was defined