OPC-30140 – OPC UA for PROFINET6.3.1.6.6 PnSubmoduleStateTypeVariable Maintenance Demanded Boolean BaseDataVariableType Optional HasComponent Variable DiagInfo Boolean BaseDataVariableType Optional HasComponent Variable ARInfo PnSubmoduleARInfoEnumeration BaseDataVariableType Optional HasComponent Variable IdentInfo PnSubmoduleIdentInfoEnumeration BaseDataVariableType Optional Mapping to PROFINET properties: BrowseName Method ... available DiagInfo Read ModuleDiffBlock | SubmoduleState.Fault If entry not found, use: No Fault information available ARInfo Read ModuleDiffBlock | SubmoduleState.ARInfo If entry not found, use: Own IdentInfo Read ModuleDiffBlock | SubmoduleState.IdentInfo If entry